background image

2.  Prepare Site • Assemble Burner • Mount Burner

Inspect/repair/replace vent system

  Do not install this burner unless you have verified the entire 

vent system and the appliance are in good condition and 
comply with all applicable codes. And ...

 

•  The vent and chimney must be sized and constructed in 
accordance with all applicable codes. 

 

•  Do not install or use an existing manual damper in the 
breeching (vent connector) or chimney.

 

•  Do not connect the appliance vent connector to a chimney 
or vent serving a fireplace, incinerator or solid-fuel-burning 
apparatus.

 

•  In a cold climate, do not vent into a masonry chimney that 
has one or more sides exposed to the outside. Install a listed 
stainless steel liner to vent the flue products.

 

•  A defective vent system could result in severe personal 
injury, death or substantial property damage.

Prepare vent/chimney

•  Secure all metal vent joints with screws, following the vent manufacturer’s 

instructions. Seal all joints in the vent system and chimney. Repair masonry 
chimney lining and repair all mortar joints as needed.

•  Install a barometric draft regulator in the vent piping if specified in the 

appliance manual. (The damper must be located in the same space as the 
appliance.)

•  Provide support for the vent piping. Do not rest the weight of any of the 

vent piping on the appliance flue outlet.

Table 1 

Minimum combustion/ventilation air openings

Combustion/ventilation air openings

Check appliance manual and applicable codes for required sizing/design/
placement of combustion/ventilation air openings. You can use the follow-
ing general guidelines, taken from NFPA 31, provided they meet all local 
requirements.

Louvers/screens

•  Air opening sizes are always given in free area. This means after deduction 

for louver obstruction. If you can’t find the louver reduction for the grilles 
used, assume free area is 20% of total for wood louvers, or 60% of total 
for metal louvers.

•  Screens can be no finer than ¼-inch mesh, and must be accessible for 

cleaning.

Residential installations

Unconfined spaces (at least 7,000 cubic feet per GPH)
•  An unconfined space means a room with at least 7,000 cubic feet volume 

for each GPH input (or 50 cubic feet per MBH) of all appliances in the room. 
Example: For each 1 GPH oil input, the room must have 7,000 cubic feet 
(875 square feet with an 8-foot ceiling height.)

•  Open basements and crawl spaces are usually large enough, and will 

generally allow enough air infiltration so special provisions will seldom be 
required.

•  If the building is tightly constructed, you will have to provide outside air 

openings into the building. The total free area of the openings must be 

at least 1 square inch per 5,000 Btuh (28 square inches per GPH) of all 
appliances in the space.

• 

See Table 1 for summary

.

Confined spaces (less than 7,000 cubic feet per GPH)

•  Air taken from inside building only —

•  Provide two openings — one near floor, the other near ceiling. Provide free 

area of 140 square inches per GPH input. If building is tightly constructed, 
provide air opening(s) into building providing 30 square inches per GPH as 
well.

•  Air taken from outside —

•  Direct through outside wall or vertical ducts: Provide two openings — one 

near floor, the other near ceiling. Provide free area of 35 square inches per 
GPH input.

•  Through horizontal ducts: Provide two openings — one near floor, the other 

near ceiling. Provide free area of 70 square inches per GPH input.

•  Ventilation air from inside/combustion air from outside

•  Size openings to interior to provide 140 square inches free area per GPH 

input. Size outside air duct to provide 28 square inches free area per 
GPH.

•  See Table 1 for summary.

MN66-3P  090721

– 4 –

Carlin Select EZ-66 Oil/Bio Fuel Burner Instruction Manual

Summary of Contents for EZ-66

Page 1: ...NORA recommends single pipe oil systems and high quality filtration for all fuel types This should in clude at least a 10 micron Spin on filter Double filtration provides even greater assurance clean...

Page 2: ...ke the user aware of all potential hazards and perform the training outlined below Train the user To properly operate the burner appliance per this manual and the appliance instructions see User s inf...

Page 3: ...for the Installation of Oil Burning Equipment ANSI NFPA 70 National Electrical Code and all applicable local codes Canadian installations Burner appliance installations in Canada must comply with the...

Page 4: ...uver obstruction If you can t find the louver reduction for the grilles used assume free area is 20 of total for wood louvers or 60 of total for metal louvers Screens can be no finer than inch mesh an...

Page 5: ...ther guidelines of this manual and the appliance manual Welded flange burners 1 Verify the bolt pattern on the appliance chamber matches the flange pattern 2 Verify the insertion depth UTL matches the...

Page 6: ...ssary to ensure reliable contact with the electrodes Install nozzle check electrodes 1 Loosen the clamp screw on the retention ring assembly see Figure 5 page 7 Slide the retention ring assembly off o...

Page 7: ...the lead edge of the slide aligns to the number given in Table 2 page 8 Lock in place by first tightening the oil line thumb nut then tightening the locking screw Air shutter 1 The air shutter is fix...

Page 8: ...d Air band Head Air band Head Air band Head GPH 100 PSI open Dim A open Dim A open Dim A open Dim A 15 20 0 15 0 15 20 0 15 20 0 15 20 0 20 0 20 0 1 25 1 70 2 2 15 2 60 4 0 4 75 2 3 20 2 3 65 5 5 4 5...

Page 9: ...oil has higher viscosity which can affect atomization ignition combustion and fuel consumption The nozzle line heater avoids this problem by heating the nozzle line oil to between 120 F and 130 F resu...

Page 10: ...d sized designed correctly o Oil tank has oil and oil line valves are open o Wiring installed per burner appliance instructions o Burner appliance and all components inspected and in good condition 3...

Page 11: ...he burner is properly set up for your installation Appliances with positive pressure in the chamber may require a wider air opening See appliance instructions for details Verify adjust settings by tes...

Page 12: ...ance flue damper or barometric draft regulator so the draft or pressure in the vent complies with the appliance manufacturer s instruc tions Heating units designed for natural draft operation are norm...

Page 13: ...inants in the vicinity of the burner appliance 4 Adjustment and Verification cont Perform the following This burner must be started and serviced at least annually by a qualified service technician Fai...

Page 14: ...nce perform a complete operational test after reassembly to verify the burner operates correctly Failure to verify operation could result in severe personal injury death or substantial property damage...

Page 15: ...pling 9 98109 Air Band Shutter 10 51593S Head positioning slide bar kit 11 51854 Combustion Head Assembly 7 12 62885A Thumb Nut Nozzle Line Item Part Desctiption 13 60103 Electrode Bracket 14 1440700K...

Page 16: ...n a serious explosion Never attempt to burn refuse or use any fuel other than 1 or 2 heating oil and bio blends not exceeding B20 U S Only ASTM D396 EZ 66 Oil Bio Fuel Burner User care and maintenance...

Reviews: