Contents
PLEASE read this first ................................................. 2
Codes and Standards .................................................. 2
1. EZ-66 Oil Nozzle Selections ................................... 3
2. Prepare Site • Assemble Burner • Mount Burner .... 4
3. Prepare Burner ....................................................... 9
4. Adjustment and Verification .................................. 14
5. Annual Start-up and Service ................................. 15
6. Maintenance Procedures...................................... 17
7. Repair Parts.......................................................... 18
User care and maintenance .........................Rear cover
MODEL
EZ-66
Advanced
Oil/Bio Burner
Instruction Manual
Installer/servicer — Except where specifically
stated otherwise, this manual must be used
only by a qualified service technician. Failure
to comply with this or other requirements in this
manual could result in severe personal injury,
death or substantial property damage.
User — The burner Instruction Manual is in-
tended only for your service technician. The
burner and heat exchanger must be inspected
and started at least annually by your service
technician.
The National Oilheat Research Alliance (NORA)
recommends single pipe oil systems and high-
quality filtration for all fuel types. This should in-
clude at least a 10 micron Spin-on filter. Double
filtration provides even greater assurance clean
fuel will get to the pump. Contaminants in the
tank that enter the fuel supply to the burner
can cause pump sticking/seizing. These con-
taminants may increase in the early stages of
transitioning to modern fuels (Ultra Low Sulfur
and Bio Blends). High quality filtration adds
protection against pump sticking
© Copyright 2021 — Carlin Combustion Technology
126 Bailey Road • North Haven, CT 06473
Phone 203-680-9401 • Fax 203-764-1714
T
ech
support
800-989-2275 • carlincombustion.com
Ratings EZ-66
Input:
...............................................0.50 to 3.00 GPH
Fuels:
U.S. ................................ No. 1 or No. 2 Fuel oil
or bio blends not exceeding B20 (U.S. Only)
Canada ...... No. 1 Stove oil or No. 2 Heating oil
Electrical: Power............................... 120V/60 Hz/1-Phase
Motor................Carlin PSC, 1/6 HP, 3450 RPM
Current .................................. Approx. 2.5 amps
Ignition: ..... Carlin Model 45000 electronic, 19,000 volts
Control: U.L. Group I or II primary safety control