![Carel uC2SE User Manual Download Page 69](http://html1.mh-extra.com/html/carel/uc2se/uc2se_user-manual_2557337069.webp)
69
120 Vac
250 Vac 30 Vdc
AC 120 V cosø =0.7
AC 250 V cosø =0.7
250 Vac cosø =0.4
30 Vdc
120 Vac cosø =0.4
30 Vdc
300
200
100
50
30
20
10
5
3
2
1
0
1
2
3
4
5
ENGLISH
μC
2
SE - +030220426 - rel. 2.1 - 09.06.2010
Description
Code
μC
2
SE single circuit, 2 compressors, panel mounting
MCH2001030
μC
2
SE single circuit, 2 compressors, panel mounting (20 pcs. multiple package)
MCH2001031
μC
2
SE
expansion board for 2nd. circuit maximum 4 compressors
MCH2000020
μC
2
SE
expansion board for 2nd. circuit maximum 4 compressors (10 pcs. multiple
package)
MCH2000021
RS485 optional board for μC
2
SE panel version
MCH2004850
Programming key for μC
2
SE
PSOPZKEY00
ON/OFF fan card (only screw terminals)
CONVONOFF0
PWM - 0 to 10 V fan card (only screw terminals)
CONV0/10A0
Temperature probes for regulation or condensation control
***depending on the length (015= 1.5 m, 030= 3 m, 060=6 m)
NTC***WP00
Pressure probes for condensing pressure control
** depending on the pressure (13= 150 PSI, 23= 75 PSI, 33= 500 PSI)
SPK*R*
Connectors kit for code MCH2000001 (multiple package 20 pcs)
MCH2CON001
Connectors kit for code MCH2000001 (multiple package 10 pcs)
MCH2CON021
Minifi t connectors kit + 1 meter length for code MCH2**
MCHSMLCAB0
Minifi t connectors kit + 2 meter length for code MCH2**
MCHSMLCAB2
Minifi t connectors kit + 3 meter length for code MCH2**
MCHSMLCAB3
Remote terminal for MCH20000** for panel installation MCH200TP0*
MCH200TP0*
Remote terminal for MCH20000** for wall-mounting MCH200TW0*
MCH200TW0*
Supervisor serial connection kit for remote terminal
MCH200TSV0
Fan speed PWM 4 A/230 Vac
MCHRTF04C0
Fan speed PWM 8 A/230 Vac
MCHRTF08C0
Fan speed PWM 12 A/230 Vac
MCHRTF12C0
Fan speed PWM 10 A/230 Vac 1 Pc. Nor. Ind.
MCHRTF10C0
Fan speed PWM 10 A/230 Vac 10 Pc. Nor. Ind.
MCHRTF10C1
Table 9.a
10. TECHNICAL SPECIFICATIONS AND SOFTWARE UPDATES
10.1 Technical specifi cations
Electrical specifi cations
In the following specifi cations “Group A” defi nes the grouping of the following outputs: valve,
pump, compressor, heater.
Power supply
24 Vac, range +10/–15 %; 50/60 Hz
Maximum power input: 3W
Fuse (compulsory) in series with the power supply to the μC
2
SE: 315mAT
12 pin connector
Max. current 2 A for each relay output, extendable to 3 A for one single
output
Relays
Max current at 250 Vac: EN60730: resistive: 3A, Inductive: 2A cos
=0.4
60,000 cycles
UL: Resistive: 3A, 1 FLA, 6 LRA cos
=0.4 30,000 cycles
For further information refer to the characteristics shown in Figure 10.a
Minimum interval between communications (each relay): 12 s (the
manufacturer of the unit that the device is integrated into must ensure
the correct confi guration so as to respond to this specifi cation
Type of microswitching: 1 C
Insulation between relays in group A: functional
Insulation between the relays in group A and the very low voltage parts:
reinforced
Insulation between relays in group A and the signal relays: primary
Insulation between the signal relays and the very low voltage parts:
reinforced
Insulation between the relays and the front panel: reinforced
Digital inputs
Electrical standard: voltage-free contacts
Closing current to earth: 5 mA
Maximum closing resistance: 50 W
Analogue inputs
B1, B2, B3, B4: NTC CAREL temperature probes (10 kW at 25 °C)
The response time depends on the component used, typical value 90 s
B4: NTC temp. probes (10 kW at 25 °C) or CAREL 0 to 5 V ratiometric
pressure probes SPKT00**R*
Fan output
Control signal for CAREL modules MCHRTF****, CONVONOFF* and
CONV0/10A*
Phase width modulation (settable width) or modulation of the duty cycle
No-load voltage: 5V ± 10%
Short-circuit current: 30 mA
Minimum output load: 1 kW
Front panel index of
protection
IP55
Storage conditions
-10T70 °C – humidity 80 % rH non-condensing
Operating conditions
-10T55 °C – humidity <90 % rH non-condensing
Degree of pollution
Normal
Cat. of resist. to heat and
fi re
D (RU94 V0)
PTI of the insulating
materials
All the insulating materials have PTI
250 V
Software class and structure A
Period of electric stress
across insulating parts
Long
Homologations
CE/RU (File EI98839 sez.16)
Table10.a
Nota:
all the relays must have the common terminals (C1/2, C3/4, C6/7, C8/9) connected
together.
Fig. 10.a
current on contacts (A)
number of operations (x 10
4
)
Summary of Contents for uC2SE
Page 1: ...C2 SE electronic control User manual...
Page 2: ......
Page 4: ...4 E N G L I S H C2 SE 030220426 rel 2 1 09 06 2010...
Page 6: ...6 E N G L I S H C2 SE 030220426 rel 2 1 09 06 2010...
Page 72: ...72 E N G L I S H C2 SE 030220426 rel 2 1 09 06 2010...
Page 73: ...73 E N G L I S H C2 SE 030220426 rel 2 1 09 06 2010...
Page 74: ...74 E N G L I S H C2 SE 030220426 rel 2 1 09 06 2010...
Page 75: ......