31
ENGLISH
μC
2
SE - +030220426 - rel. 2.1 - 09.06.2010
4.3.11 Control setting parameters (r*)
display
indicat.
parameter and description
default
level
min.
max.
U.O.M. variat. def.
visibility supervis.
variable
Modbus
variable
type
r01
Cooling set point
D
r13
r14
°C/°F
0.1
12.0
-
41 (R/W) 41
Analog
r02
Cooling diff erential
D
3
500
°C/°F
0.1
30
-
42 (R/W) 42
Analog
r03
Heating set point
D
r15
r16
°C/°F
0.1
400
-
43 (R/W) 43
Analog
r04
Heating diff erential
D
3
500
°C/°F
0.1
30
-
44 (R/W) 44
Analog
r05
Compressor rotation
0= disabled;
1= FIFO type
2= hour control
3= direct relation between (D.I. and compressors D.O.)
F
0
3
Flag
1
0
-
78 (R/W) 285
Integer
r06
Type of compressor control
0= proportional on inlet
1= proportional on inlet + dead zone
2= proportional on outlet
3= proportional on dead zone
4= time on outlet with dead zone
F
0
4
Flag
1
0
-
79 (R/W) 286
Integer
r07
Dead zone diff erential
F
1
500
°C/°F
0.1
20
-
45 (R/W) 45
Analog
r08
Maximum control output activation time
F
0
999
s
1
120
-
80 (R/W) 287
Integer
r09
Minimum control output activation time
F
0
999
s
1
100
-
81 (R/W) 288
Integer
r10
Maximum control output deactivation time
F
0
999
s
1
120
-
82 (R/W) 289
Integer
r11
Minimum control output deactivation time
F
0
999
s
1
100
-
83 (R/W) 290
Integer
r12
Compressor deactivation diff erential
F
0
500
°C/°F
0.1
20
-
46 (R/W) 46
Analog
r13
Minimum set point in Cooling
U
-400
r14
°C/°F
0.1
-400
-
47 (R/W) 47
Analog
r14
Max. Cooling set point
U
r13
1760
°C/°F
0.1
800
-
48 (R/W) 48
Analog
r15
Min. Heating set point
U
-400
r16
°C/°F
0.1
-400
-
49 (R/W) 49
Analog
r16
Max. Heating set point
U
r15
1760
°C/°F
0.1
800
-
50 (R/W) 50
Analog
r17
Cooling compensation constant
U
-50
50
-
0.1
0
-
51 (R/W) 51
Analog
r18
Maximum distance from the set point
U
3
200
°C/°F
0.1
3
-
52 (R/W) 52
Analog
r19
Start compensation temperature in cooling mode
U
-400
1760
°C/°F
0.1
300
-
53 (R/W) 53
Analog
r20
Start compensation temperature in heating mode
U
-400
1760
°C/°F
0.1
0
-
54 (R/W) 54
Analog
r21
Second cooling set point from external contact
D
r13
r14
°C/°F
0.1
120
-
55 (R/W) 55
Analog
r22
Second heating set point from external contact
D
r15
r16
°C/°F
0.1
400
-
56 (R/W) 56
Analog
r23
Select automatic changeover probe
D
0
8
Flag
1
0
-
84 (R/W) 291
Integer
r24
Automatic changeover set point
D
r15
r16
°C/°F
0.1
400
-
61(R/W)
61
Analog
r25
Outside temp set point to stop compressors
D
-400
800
°C/°F
0.1
-400
-
65 (R/W) 65
Analog
r26
Cooling set point in dehumidifi cation
D
r13
r14
°C/°F
0.1
120
-
66 (R/W) 66
Analog
r27
Enable accumulation vessel suppression
0= Disabled
1= Enabled in cool
2= Enabled in Heat
3= Always enabled
F
0
3
Flag
1
0
-
88 (R/W) 295
Integer
r28
Min. compressor running time for low load/damper travel time
F
0
999
s
1
60
-
89 (R/W) 296
Integer
r29
Chiller low load diff erential/freecooling diff erential
F
10
500
°C/°F
0.1
30
-
58 (R/W) 58
Analog
r30
Heat pump low load diff erential/freeheating diff erential
F
10
500
°C/°F
0.1
30
-
59 (R/W) 59
Analog
r31
Heating compensation constant
U
-50
50
-
0.1
0
-
60 (R/W) 60
Analog
r32
Hot Start set point
D
r15
r16
°C/°F
0.1
120
-
71(R/W)
71
Analog
r33
Hot Start diff erential
F
3
500
°C/°F
0.1
30
-
72 (R/W) 72
Analog
r34
Enable Freecooling/Freeheating
0= disabled
1= freecooling / without compressors / cooling only
2= freecooling / with compressors / cooling only
3= freeheating / without compressors / heating only
4= freeheating / with compressors / heating only
5= freecooling and freeheating / without compressors / freecooling
cooling only and freeheating heating only
6= freecooling and freeheating / with compressors / freecooling cooling
only and freeheating heating only
7= freecooling / without compressors / always
8= freecooling / with compressors / always
9= freeheating / without compressors / always
10= freeheating / with compressors / always
11= freecooling and freeheating / without compressors / always
12= freecooling and freeheating / with compressors / always
F
0
12
Flag
1
0
-
116
(R/W)
323
Integer
r35
Compressor deactivation time with freecooling/freeheating active
F
0
999
s
1
240
-
117
(R/W)
324
Integer
r36
Maximum damper operating time
F
0
600
s
1
20
-
118
(R/W)
325
Integer
r37
Damper opening duty cycle diff erential
F
03
500
°C/°F
0.1
30
-
73 (R/W) 73
Analog
r38
Damper closing duty cycle diff erential
F
03
500
°C/°F
0.1
30
-
74 (R/W) 74
Analog
r39
Autotuning correction coeffi
cient
F
11
30
-
0.1
13
-
75 (R/W) 75
Analog
r40
Indicates when to operate minimum damper opening
0= never
1= only in freecooling
2= only in freeheating
3= in freecooling and in freeheating
4= only if the freecooling and freeheating conditions end
5= only if the freeheating conditions are not present
6= only if the freecooling conditions are not present
7= always
F
0
7
-
1
0
-
119
(R/W)
326
Integer
r41
Minimum damper opening
F
0
100
%
1
0
-
120
(R/W)
327
Integer
r42
Freecooling operating threshold with compressors disabled.
U
A07
1760
°C/°F
0.1
50
-
81 (R/W) 81
Analog
r43
Heater set point
0= A4, A8 and A11 absolute values
1= A4 absolute value, A8 and A11 values relative to the set point
2= A4 value relative to the set point, A8 and A11 absolute values
3= A4, A8 and A11 values relative to the set point
F
0
3
-
1
0
-
121
(R/W)
328
Integer
r44
Inactivity time in Freecooling control
F
0
240
-
1
5
-
123
(R/W)
330
Integer
Table 4.k
Summary of Contents for uC2SE
Page 1: ...C2 SE electronic control User manual...
Page 2: ......
Page 4: ...4 E N G L I S H C2 SE 030220426 rel 2 1 09 06 2010...
Page 6: ...6 E N G L I S H C2 SE 030220426 rel 2 1 09 06 2010...
Page 72: ...72 E N G L I S H C2 SE 030220426 rel 2 1 09 06 2010...
Page 73: ...73 E N G L I S H C2 SE 030220426 rel 2 1 09 06 2010...
Page 74: ...74 E N G L I S H C2 SE 030220426 rel 2 1 09 06 2010...
Page 75: ......