4.3.9 Firmware parameters (F-r*)
display
indicat.
parameter and description
default
level
min.
max.
U.O.M. variat.
default
visibility
supervis.
variable
Modbus
variable
type
H99
Software version, Driver 2
D
0
999
Int
-
22
-
1 (R)
208
Integer
H98
Software version, Driver 1
D
0
999
Int
-
0
X
2 (R)
209
Integer
H97
Expansion software version
D
0
999
Int
-
0
V
3 (R)
210
Integer
H96
Software version (displayed when powering up
the instrument)
D
0
999
Int
-
0
XV
4 (R)
211
Integer
Table 4.i
4.3.10 Alarm setting parameters (P*)
display
indicat.
parameter and description
default
level
min.
max.
U.O.M. variat. def.
visibility supervis.
variable
Modbus
variable
type
P01
Flow switch alarm delay when starting the pump
U
0
150
s
1
20
-
63 (R/W)
270
Integer
P02
Flow switch alarm delay during steady operation
U
0
120
s
1
5
-
64 (R/W)
271
Integer
P03
Low pressure alarm delay at compressor start-up
U
0
200
s
1
40
-
65 (R/W)
272
Integer
P04
Enable compressor capacity-control with high pressure
0= capacity control deactivated
1= capacity-control with high pressure active
2= capacity-control with low pressure active
3= capacity-control with high and low pressure active
U
0
3
Flag
1
0
P
66 (R/W)
273
Integer
P05
Alarm reset
0= HP1-2/LP1-2/A1-2/Lt manual
1= HP1-2/LP1-2/A1-2/Lt automatic
2= HP1-2/A1-2/Lt manual LP1-2 automatic
3= HP1-2 manual LP1-2/A1-2/Lt automatic
4= HP1-2/LP1-2 manual A1-2/Lt automatic
5= HP1-2/LP1-2 (thrice per hour) manual A1-2/Lt automatic
6= HP1-2/LP1-2 (thrice per hour) manual; A1-2/Lt manual
F
0
6
Flag
1
0
-
67 (R/W)
274
Integer
P06
Cooling/heating logic
0=:
Chiller,
: Heat pump
1=:
Heat pump,
: Chiller
F
0
1
Flag
1
0
-
19 (R/W)
19
Digital
P07
Low pressure alarm with pressure probe
0= Disabled
1= Enabled
F
0
1
Flag
1
0
P
68 (R/W)
275
Integer
P08
Digital input 1 selection
0= N
1=FL man.
2=FL auto.
3=TP man.
4=TP auto
5= TC1
man.
6= TC1 auto.
7= TC2 man.
8= TC2
auto.
9= Cool/
heat
10= Cool/heat with
delay
11= LA man.
12= LA
auto.
13= 2° Set
14= 2° Set timer
15= stop defrost
c.1
16= stop
defrost c.2
17= start
defrost c.1
18= start defrost c.2
19= step 1
20 = step 2 21= step 3
22= step 4
23= remote ON/
OFF
24=Comp.
alarm1
25=Comp.
alarm2
26=Comp. alarm3
27=Comp. alarm4
F
0
23
Int
1
0
-
69 (R/W)
276
Integer
P09
Digital input 2 selection
F
0
27
Int
1
0
-
70 (R/W)
277
Integer
P10
Digital input 6 selection
F
0
27
Int
1
0
X
71 (R/W)
278
Integer
P11
Digital input 7 selection
F
0
27
Int
1
0
X
72 (R/W)
279
Integer
P12
Digital input 10 selection
F
0
27
Int
1
0
X
73 (R/W)
280
Integer
P13
Confi guration of B4 as P8 if /4=1 (digital input)
F
0
27
Int
1
0
-
74 (R/W)
281
Integer
P14
Confi guration of B8 as /8=1 (digital input)
F
0
27
Int
1
0
X
75 (R/W)
282
Integer
P15
Select low pressure alarm
0= not active with compressor OFF
1= active with compressor OFF
F
0
1
Flag
1
0
-
76 (R/W)
283
Integer
P16
High temperature alarm set
U
-400
1760
°C/°F
0.1
800
-
38 (R/W)
38
Analog
P17
High temperature alarm delay at start-up
U
0
250
s
1
30
-
77 (R/W)
284
Integer
P18
High pressure alarm set from transducer
F
P33
999
Dbar
0.1
200
P
39 (R/W)
39
Analog
P19
System low temperature alarm set point
U
-400
1760
°C/°F
0.1
100
-
40 (R/W)
40
Analog
P20
Enable system start-up protection
0= Disabled
1= Enabled
U
0
1
Flag
1
0
-
20 (R/W)
20
Digital
P21
Alarm relay output logic
0= normally de-activated
1= normally activated
F
0
1
-
1
0
-
8 (R/W)
8
Digital
P22
Low pressure alarm delay at start-up
Compressor in heat pump
U
0
200
s
1
40
-
86 (R/W)
293
Integer
P23
Low pressure alarm delay at compressor start-up in defrost
U
0
999
s
1
40
-
87 (R/W)
294
Integer
P24
Deactivate compressors with HP and LP capacity-control
D
0
1
-
1
0
P
21 (R/W)
21
Digital
P25
Select digital output 2
F
0
17
Int
1
0
-
108 (R/W) 315
Integer
P26
Select digital output 3
F
0
17
Int
1
0
-
109 (R/W) 316
Integer
P27
Select digital output 4
F
0
17
Int
1
0
-
110 (R/W) 317
Integer
P28
Select digital output 5
F
0
17
Int
1
0
-
111 (R/W) 318
Integer
P29
Select digital output 7
F
0
17
Int
1
0
X
112 (R/W) 319
Integer
P30
Select digital output 8
F
0
17
Int
1
0
X
113 (R/W) 320
Integer
P31
Select digital output 9
F
0
17
Int
1
0
X
114 (R/W) 321
Integer
P32
Select digital output 10
F
0
17
Int
1
0
X
115 (R/W) 322
Integer
P33
Low pressure alarm threshold
F
0
P18
Dbar
0.1
10
P
76 (R/W)
76
Analog
P34
Select digital input 5
F
0
23
Int
1
23
-
122 (R/W) 329
Integer
P35
Mute alarm with “mute“ button
0= no
1= yes
F
0
1
-
1
0
-
23 (R/W)
23
Digital
P36
Type of high pressure alarm management
0= always
1= only if compressor active and 2 s after activation
F
0
1
-
1
0
-
24 (R/W)
24
Digital
Table 4.j
Summary of Contents for uC2SE
Page 1: ...C2 SE electronic control User manual...
Page 2: ......
Page 4: ...4 E N G L I S H C2 SE 030220426 rel 2 1 09 06 2010...
Page 6: ...6 E N G L I S H C2 SE 030220426 rel 2 1 09 06 2010...
Page 72: ...72 E N G L I S H C2 SE 030220426 rel 2 1 09 06 2010...
Page 73: ...73 E N G L I S H C2 SE 030220426 rel 2 1 09 06 2010...
Page 74: ...74 E N G L I S H C2 SE 030220426 rel 2 1 09 06 2010...
Page 75: ......