4.3.6 Defrost setting parameters (d*)
display
indicat.
parameter and description
default
level
min.
max.
U.O.M.
variat.
default
visibility supervis.
variable
Modbus variable
type
d01
Defrosting cycle/Condenser antifreeze
0= no;
1= yes, with shared defrosting
U
0
1
Flag
1
0
-
7 (R/W)
7
Digital
d02
Time-or temperature-based defrosting
0= time
1= temp. - press
2= pressure start, temperature end
3= activate sliding defrost
U
0
3
Flag
1
0
D
90 (R/W)
297
Integer
d03
Start defrosting temperature
Condenser antifreeze alarm set point
U
-400
d04
°C/°F
0.1
-50
DN
19 (R/W)
19
Analog
Start defrosting pressure
Condenser antifreeze alarm set point
U
/11
d04
Dbar
0.1
35
DP
18 (R/W)
18
Analog
d04
End defrost temperature
U
d03
/12
Dbar
0.1
140
DP
20 (R/W)
20
Analog
End defrost pressure
d03
1760
°C/°F
0.1
200
DN
21 (R/W)
21
Analog
d05
Min. time to start a defrosting cycle
U
10
150
s
1
10
D
37 (R/W)
244
Integer
d06
Min. duration of a defrosting cycle
U
0
150
s
1
0
D
38 (R/W)
245
Integer
d07
Max. duration of a defrosting cycle
U
1
150
min
1
5
D
39 (R/W)
246
Integer
d08
Delay between 2 defrosting cycle requests within the same
circuit
U
10
150
min
1
30
D
40 (R/W)
247
Integer
d09
Defrosting delay between the 2 circuits
U
0
150
min
1
10
D
41 (R/W)
248
Integer
d10
Defrost by external contact
0= disables function
1= external contact start
2= external contact end
3= external contact start and end
F
0
3
Flag
1
0
D
42 (R/W)
249
Integer
d11
Antifreeze heater in defrost
U
0
1
Flag
1
0
D
9 (R/W)
9
Digital
d12
Waiting time before defrosting
F
0
3
min
1
0
D
43 (R/W)
250
Integer
d13
Waiting time after defrosting
F
0
3
min
1
0
D
44 (R/W)
251
Integer
d14
End defrosting with 2 refrigerating circuits
0= Indipendent
1= If both at end defrost
2= If at least one at end defrost
F
0
2
Flag
1
0
D
45 (R/W)
252
Integer
d15
Start defrost with 2 circuits
0= Indipendent
1= If both at start defrost
2= If at least one at start defrost
F
0
2
Int
1
0
D
46 (R/W)
253
Integer
d16
Forced ventilation time at the end of the defrosting
F
0
360
s
1
0
D
47 (R/W)
254
Integer
d17
Set/enable light defrost
F
0
800
°C/°F
0.1
0
D
22 (R/W)
22
Analog
d18
Max. outside temperature (sliding defrost)
F
-400
800
°C/°F
0.1
-100
D
62 (R/W)
62
Analog
d19
Start defrost diff erential (sliding defrost)
F
-400
800
°C/°F/bar
0.1
30
D
63 (R/W)
63
Analog
d20
Outside temperature diff erential (sliding defrost)
F
10.0
800
°C/°F
0.1
100
D
64 (R/W)
64
Analog
Table 4.f
4.3.7 Fan setting parameters (F*)
display
indicat.
parameter and description
default
level
min.
max.
U.O.M.
variat.
def.
visibility supervis.
variable
Modbus
variable
type
F01
Enable Fan output
0=not present
1=present
F
0
1
Flag
1
0
-
10 (R/W)
10
Digital
F02
Fan operating mode
0= always ON
1= depending ON the compressor (in parallel operation
mode)
2= depending ON the compressors in ON/OFF control
3= depending ON the compressors in speed control
mode
U
0
3
Int
1
0
F
48 (R/W)
255
Integer
F03
Min. voltage threshold for Triac
F
0
F04
step
1
35
F
49 (R/W)
256
Integer
F04
Max. voltage threshold for Triac
F
F03
100
step
1
75
F
50 (R/W)
257
Integer
F05
Speed temp. set point in Cooling mode
U
-400
1760
°C/°F
0.1
350
FN
24 (R/W)
24
Analog
Pressure value for min. speed Cooling
U
/11
/12
Dbar
0.1
130
FP
23 (R/W)
23
Analog
F06
Diff erential value for max. speed Cooling
U
0
500
°C/°F
0.1
100
FN
26 (R/W)
26
Analog
Pressure value for max. speed Cooling
U
0
300
Dbar
0.1
30
FP
25 (R/W)
25
Analog
F07
Fan shut-down diff erential in Cooling mode
U
0
500
°C/°F
0.1
150
FN
28 (R/W)
28
Analog
Fan shut-down pressure in Cooling mode
U
0
F05
Dbar
0.1
50
FP
27 (R/W)
27
Analog
F08
Speed temp. set point in Heating mode
U
-400
1760
°C/°F
0.1
350
FN
30 (R/W)
30
Analog
Pressure value for max speed in Heating
U
/11
/12
Dbar
0.1
130
FP
29 (R/W)
29
Analog
F09
Max. speed diff . in Heating mode
U
0
500
°C/°F
0.1
50
FN
32 (R/W)
32
Analog
Pressure value for max speed in Heating
U
0
F08
Dbar
0.1
40
FP
31 (R/W)
31
Analog
F10
Fan shutdown diff . in Heating mode
U
0
F08
°C/°F
0.1
50
FN
34 (R/W)
34
Analog
Pressure to turn OFF the fan in Heating
U
0
300
Dbar
0.1
30
FP
33 (R/W)
33
Analog
F11
Fan starting time
U
0
120
s
1
0
F
51 (R/W)
258
Integer
F12
Triac impulse duration (fan start)
F
0
10
s
1
2
F
52 (R/W)
259
Integer
F13
Fan management in defrost mode
0= Fans deactivated
1= Fans in chiller mode
2= Maximum speed after defrost
F
0
2
Int
1
0
F
53 (R/W)
260
Integer
F14
Fan with high condensing temperature when starting
U
0
999
-
1
0
FN
91 (R/W)
298
Integer
F15
Low noise activation
0= deactivated
1= activated in cooling
2= activated in heating
3= activated in cooling and heating
U
0
3
-
1
0
F
85 (R/W)
292
Integer
F16
Low noise diff . in cooling
F
0
500
°C/°F/
bar
0.1
0
L
35 (R/W)
35
Analog
F17
Low noise diff . in heating
F
0
500
°C/°F/
bar
0.1
0
L
36 (R/W)
36
Analog
Table 4.g
Summary of Contents for uC2SE
Page 1: ...C2 SE electronic control User manual...
Page 2: ......
Page 4: ...4 E N G L I S H C2 SE 030220426 rel 2 1 09 06 2010...
Page 6: ...6 E N G L I S H C2 SE 030220426 rel 2 1 09 06 2010...
Page 72: ...72 E N G L I S H C2 SE 030220426 rel 2 1 09 06 2010...
Page 73: ...73 E N G L I S H C2 SE 030220426 rel 2 1 09 06 2010...
Page 74: ...74 E N G L I S H C2 SE 030220426 rel 2 1 09 06 2010...
Page 75: ......