20
Fig. 7.a
Mode
135
30
86
POWER
MODE
HUM
SLEEP
CLOCK
TEMP
ENGL
ISH
µAD +030220465 - rel. 1.1 - 15.12.2010
7 TECHNICAL FEATURES
Power supply voltage (according to EN60730-1)
24 Vac ±15 %, 50/60 Hz 70 mA 1,5 VA
or31 Vdc ± 29 % 70 mA
Classifi cation according to UL873:
Power supply input:
24 V ac, 50-60Hz, Class 2
25.5 - 36.25 V dc, Class 2
Power consumption, max 1 watt
Output: serial link RS485, Class 2
Functioning conditions
0T50 °C;
10...85% U.R. non condensing.
Storage conditions
-20T70 °C;
0...85 % U.R. non condensing.
Dimensions
see Figure below
Environmental pollution
normal
Level of pollution
level II
Category f resistance to heat and fi re
A
Class and structure of the software
A
Level of protection against atmospheric agents
IP30
Temperature of the ball pressure test on the plastic casing
100 °C
Classifi cation according to protections against electric shocks
( EN 60730-1)
III, to integrate into class I or II appliances
Period of electrical stress of the isolated parts s
long
Control device envisioned to be supplied to:
manufacturers, installation technicians
and maintenance technicians
Protection against short-circuits
must be guaranteed by the manufacturer
of the appliance into which the µAD
is integrated or by the fi nal installation
technician
Immunity against over-voltage
category 1
Wire sections
from 0.5 to 1.5 mm
2
Precision of the temperature measurement
+/-2 °C
Precision of the humidity measurement (in the models with
humidity probe)
+/-10% rH
Tab. 6.4