8
ENG
pC0300020EN rel. 1.2 - 07.11.2013
1.2 Functional
layout
The fi gure below shows the functional layout of an air handling
unit. Damper actuators and valve actuators are fi eld devices that
communicate through Fieldbus 1 (ref. C). Fieldbus 2 (ref. E) is the medium
through which the serial probes communicate the values measured,
and through which the humidifi er control board and the fans exchange
data and receive setpoints from the controller. The built-in terminal and
the remote terminal, which communicate via pLAN (ref. A), are used for
installing the application program and for commissioning the system.
The PGD touchscreen terminal, intuitive and simple to use, can be used
while the unit is normally working to set switch-on and switch-off times,
to enter the main parameters, to perform other advanced functions of
the application program and to view any alarms triggered. In this case the
data is communicated through the BMS2 serial port (ref. D). The system
can be connected to a supervision system (Konnex®, LON®, BACnet™, etc.)
after installing the relative BMS1 expansion card (ref. B).
BELIMO
Scheda seriale RS485
Scheda interfaccia
LonWorks®
Scheda interfaccia
BACnet™ RS485
Sch. interfaccia
Ethernet™ /BACnet™
Servocontrollo
della serranda
BELIMO
Valvola di
servocontrollo
MP -BUS
Scheda MP-BUS
5
8
4
S
R
s
u
t
a
t
s
G NX
RS485
+
–
P1
P2
P3
B A Cnet
™
MS/TP
FieldBus 1
BMS 1
J1
J24
J2
J3
J4
J5
J7
J8
J20
J21
J14
J10
J13
J12
J22
J16
J17
J18
J15
J6
J19
Fie l dB u s c a r d
B M S card
J23 FBus2
J11 pLAN
J25 BMS2
J26 FBus2
4
3
2
1
Sonde seriali
Terminale PGD
touch screen
Terminale
Scheda controllo
umidificatori
Dispositivo
terze parti
FAN
FieldBus 2
D
E
BMS2
A
pLAN
C
B
Fig. 1.a
Ref. Serial port/Connectors
Connection to:
A
pLAN/J10, J11
up to 3 terminals
up to 32 devices in a pLAN network (pCO controllers, EVD Evolution valve drivers, terminals)
B
BMS 1 Serial Card
a building automation system, after installing the relative BMS card (see par. 1.4)
C
FieldBus 1 Serial Card
sensors, actuators, etc., on a Fieldbus, after installing the relative card (see par. 1.5)
D
BMS 2 / J25*
pGD Touch terminals, GPRS connection modules (built-in card)
E
Fieldbus 2/J26 (and J23 on Large and
Extralarge versions)
sensors, actuators, etc., on a Fieldbus (built-in card)
(*) available on P+5... models; not available on P+3... models; see par. 8.3.
Terminal
PGD touchscreen
terminal
Serial probes
Humidifi er control
board
Device
MP-BUS card
Servo-control
valve
Damper servo-
control
RS485 serial card
BACnet
TM
RS485
interface card
Ethernet
TM
/BACnet
TM
interface card
LonWorks interface
card*