Carel pCO5+ User Manual Download Page 20

20

ENG

pC0300020EN rel. 1.2 - 07.11.2013

4.7 I/O 

table

pCO5+ Controllers

pCOE I/O expansion card

Small

M

edium

Lar

ge

Ex

tra

Lar

ge

Built-in 

driv

er

Label

In/Out

T

ipo

PC

OE*

Label

In/Out

T

ype

Universal inputs/
outputs

NTC input

5

8

10

8

8

U

In Universal I/O

4

B

In

Analogue input(*)

PTC input

5

8

10

8

8

U

In Universal I/O

-

-

-

-

PT500 input

5

8

10

8

8

U

In Universal I/O

-

-

-

-

PT1000 input

5

8

10

8

8

U

In Universal I/O

-

-

-

-

PT100 input

max 2

max 3

max 4

max 3

max 3

U

In Universal I/O

-

-

-

-

0 to 1 Vdc/0 to 10 Vdc input  (**)
(powered by controller)

Tot. max 5

5

Tot. max 8

max 6

Tot. max 10

max 6

Tot. max

 8 max 6

Tot. max

 8

max 6

U

In Universal I/O

4

B

In

Analogue input(*)

0 to 1 Vdc/0 to 10 Vdc input (**)
(external power supply)

5

8

10

8

8

U

In Universal I/O

4

B

In

Analogue input(*)

0 to 5 Vdc input

-

-

-

-

-

-

-

-

4

B

In

Analogue input(*)

0 to 20 mA/4 to 20 mA input 
(powered by controller)

Tot. max

 4 max 4

Tot. max

 7 max 6

Tot. max

 9

max 6

Tot. max

 7 max 6

Tot. max

 7

max 6

U

In Universal I/O

4

B

In

Analogue input(*)

0 to 20 mA/4 to 20 mA input
(external power supply)

max 4

max 7

max 9

max 7

max 7

U

In Universal I/O

-

-

-

-

0 to 5 V input for ratiometric probe 
(+5Vref )

max 5

max 6

max 6

max 6

max 6

U

In Universal I/O

4

B

In

Analogue input(*)

Voltage-free contact digital input

5

8

10

8

8

U

In Universal I/O

-

-

-

Digital input

Fast digital inputs

max 2

max 4

max 6

max 4

max 4

U

In Universal I/O

-

-

-

Digital input

Non-optically-isolated 0 to 10 Vdc 
output

5

8

10

8

8

U

Out Universal I/O

-

-

-

Analogue output

Non-optically-isolated PWM output

5

8

10

8

8

U

Out Universal I/O

-

-

-

Analogue output

max tot 5

max tot 8 max tot 10 max tot 8

max tot 8

Digital inputs

Optically-isolated 24 Vac/Vdc input

8

12

14

12

12

ID

In Digital input

4

ID

In

Digital input

24 Vac/Vdc or 230 Vac (50/60 Hz) input

-

2

4

2

2

ID

In Digital input

-

-

-

max tot 8 max tot 14 max tot 18 max tot 14 max tot 14

Analogue outputs

Optically-isolated 0 to 10 Vdc output

4

4

6

4

4

Y

Out Analogue output

1

Y

Out

Optically-isolated PWM output

2

2

2

2

2

Y3, Y4

Out

Analogue output

-

-

-

Output for two-pole stepper motor

-

-

-

-

1/2

1-3-2-4

Out

Analogue output

-

-

-

max tot 4

max tot 4

max tot 6

max tot 4

max tot 6

Digital outputs

NO/NC relay output

1

3

5

3

3

NO/NC

Out Digital output

4

NO/NC Out Digital output

NO relay output

7

10

13

26

10

NO

Out Digital output

-

-

-

24 V SSR output

1

2

3/4

2

2

NO/NC

Out Digital output

-

-

-

230 V SSR output

1

13

3/4

2

2

NO/NC

Out Digital output

-

-

-

max tot 8 max tot 13 max tot 18 max tot 29  max tot 13

25

39

52

55

41

Total  I/O

Power to terminal

1

1

1

1

1

J10

Telephone conn. 

(pLAN) J10

1

1

1

1

1

+Vterm

Add’l power to 

terminal

Power to probes

1

1

1

1

1

+VDC

Power to active 

probes

1

1

1

1

1

+5 VREF

Power to 

ratiometric probes

Power to analogue 
outputs

1

1

1

1

1

VG, VG0

1

VG,VG0

pLAN ports

1

1

1

1

1

J10

Signal and power

1

1

1

1

1

J11

Signal only

Built-in Fieldbus ports

1

1

2

2

1

J23/ J26

Accessory Fieldbus 
ports

1

1

1

1

1

Fbus card

Built-in BMS ports

1

1

1

1

1

J25

Accessory BMS ports

1

1

1

1

1

BMS card

Host USB port (if 
included)

1

1

1

1

1

Slave USB port (if 
included)

1

1

1

1

1

(*) On the pCOE expansion board the inputs can be selected two by two (B1, B2 and B3, B4) via software
(**) pCOE board: only 0...1V inputs

Tab. 4.e 

Summary of Contents for pCO5+

Page 1: ...I n t e g r a t e d C o n t r o l S o l u t i o n s E n e r g y S a v i n g s pCO5 NO POWER SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT Programmable Controller User manual...

Page 2: ......

Page 3: ...corrosive chemicals solvents or aggressive detergents to clean the device Do not use the product for applications other than those speci ed in the technical manual All of the above suggestions likewi...

Page 4: ...4 ENG pCO5plus 0300020EN rel 1 2 07 11 2013...

Page 5: ...12 pCO5 terminals description 24 5 INPUT OUTPUT CONNECTIONS 26 5 1 Power supply 26 5 2 Universal inputs outputs 26 5 3 Digital inputs 29 5 4 Optically isolated analogue outputs 31 5 5 Connecting the...

Page 6: ...6 ENG pCO5plus 0300020EN rel 1 2 07 11 2013...

Page 7: ...ding software and commissioning fast upload download of controller software using a Smart Key or any pendrive provided the controller is equipped with the relative port universal inputs outputs con gu...

Page 8: ...RS485 Sch interfaccia Ethernet BACnet Servocontrollo della serranda BELIMO Valvola di servocontrollo MP BUS Scheda MP BUS 5 8 4 S R s u t a t s GNX RS485 P1 P2 P3 B A Cnet MS TP FieldBus 1 BMS 1 J1 J2...

Page 9: ...s terminal panel installation This model can be installed on the panel Its graphics properties are identical to those of the PGDE000 terminal Accessories for installation telephone connection cable co...

Page 10: ...ntroller consequently acts as a MASTER i e supervisor therefore other con trollers or devices can be connected as SLAVES Up to 64 devices can be connected PCO100TLN0 tech lea et Code 050003270 tLAN an...

Page 11: ...er e g pCO5 Small EVD Evolu tion external Ultracap module pCOE tech lea et code 050003265 Expansion card Increases the number of inputs outputs on the controller A maximum of 5 expan sion cards can be...

Page 12: ...White press together with DOWN and ENTER to change the terminal s address only for PGDE terminal see par 6 4 press to increase value Enter White press to con rm value DOWN White press together with UP...

Page 13: ...NO16 NO17 NO18 C16 ID15H ID15 IDC15 ID16 ID16H Y5 Y6 ID17 ID18 IDC17 U9 GND U10 GND FieldBus card BMS card J23 FBus2 J11 pLAN J25 BMS2 J26 FBus2 4 3 2 1 ONLY FOR LARGE AND EXTRALARGE MODELS Fig 3 a S...

Page 14: ...s2 J11 pLAN pCO5 SLAVE SLAVE Fig 3 d pLAN network J25 BMS2 J26 FBus2 J11 pLAN pCO5 J25 BMS2 J26 FBus2 J11 pLAN pCO5 J25 BMS2 J26 FBus2 J11 pLAN pCO5 MASTER SLAVE MASTER SLAVE MASTER SLAVE Fig 3 e Impo...

Page 15: ...ange of operation see Technical Speci cations large rapid uctuations in room temperature strong magnetic and or radio frequency interference avoid installing near transmitting antennas strong vibratio...

Page 16: ...ompliance with national and local regulations All the very low voltage connections 24 Vac Vdc or 28 to 36 Vdc analogue and digital inputs analogue outputs serial bus connections power supplies must ha...

Page 17: ...nel Terminating resistors are not required L 100m 230 Vac 24 Vac L N J25 BMS2 J26 FBus2 J11 pLAN pCO5 G G0 J25 BMS2 J26 FBus2 J11 pLAN pCO5 G G0 J25 BMS2 J26 FBus2 J11 pLAN pCO5 G G0 Fig 4 c The proce...

Page 18: ...ion slip the connector into terminal J10 until it clicks To remove the connector press lightly on the plastic catch on the connector and slip it out Graphic L 50 m cavo telefonico telephone cable J10...

Page 19: ...onnected to a pCO controller which is itself connected to other controllers in a pLAN network the terminal is directly powered by the controller Be sure to avoid the terminal being powered by two powe...

Page 20: ...ed PWM output 5 8 10 8 8 U Out Universal I O Analogue output max tot 5 max tot 8 max tot 10 max tot 8 max tot 8 Digital inputs Optically isolated 24 Vac Vdc input 8 12 14 12 12 ID In Digital input 4 I...

Page 21: ...J8 J1 4 J10 J1 3 J1 2 J16 J1 7 J18 J15 J6 FieldBus card BMS card J11 pLAN J2 5BMS2 J2 6FBus2 4 3 2 1 4 5 1 6 2 3 3 3 8 9 7 8 10 13 14 11 12 15 18 16 17 Fig 4 r Ref Description Ref Description 1 POWER...

Page 22: ...U7 U8 GND ID9 ID10 ID11 ID12 IDC9 ID13H ID13 IDC13 ID14 ID14H J1 J24 J2 J3 J4 J5 J7 J8 J14 J10 J13 J12 J16 J17 J18 J15 J6 FieldBus card BMS card J23 FBus2 J11 pLAN J25 BMS2 J26 FBus2 4 3 2 1 4 5 1 6...

Page 23: ...nnector 6 VG voltage A to optically isolated analogue output VG0 power to optically isolated analogue output 0 Vac Vdc 18 Fieldbus BMS selector microswitch 7 Analogue outputs 20 Electronic valve A con...

Page 24: ...N RS485 port J11 2 Tx Rx Tx Rx pLAN RS485 port J11 3 GND GND pLAN RS485 port 12 Reserved 13 Reserved 14 Reserved Ref Term Label Description 15 J12 1 C1 Common for relays 1 2 3 J12 2 NO1 Normally open...

Page 25: ...connection J28 2 3 J28 3 2 J28 4 4 22 J30 1 VBAT Power from external Ultracap module J30 2 G0 J30 3 G 23 J29 1 GND Common for power supply to probes J29 2 VREF Power to driver probes J29 3 S1 Probe 1...

Page 26: ...o handle their respective signals from the application program the universal inputs outputs cannot be used as digital outputs Max number of connectable analogue inputs The maximum number of analogue i...

Page 27: ...nical Speci cations table The probe has three wires connect one to GND and the other two to two separate but adjacent universal inputs on the same controller e g U1 U2 GND or U4 U5 GND G G0 U1 U2 U3 G...

Page 28: ...scription Wire colour 5 VREF Power Black GND Power reference Green U1 Signal White Connecting active probes with 0 to 10 V output For information on the maximum number of probes that can be connected...

Page 29: ...ty devices alarms device status indicators and remote switches These inputs are all optically isolated from the other terminals They can work at 24 Vac 10 15 or at 28 to 36 Vdc 20 10 indicated with ID...

Page 30: ...6 ID17 ID18 IDC17 U9 GND U10 GND FieldBus card BMS card 24Vac Fig 5 n 24 Vdc digital inputs The ID digital inputs can be controlled at 24 Vdc Example of connection diagram LARGE model G G0 U1 U2 U3 GN...

Page 31: ...D14H J1 J24 J2 J3 J4 J5 J7 J8 J20 J6 J19 ID15H ID15 IDC15 ID16 ID16H Y5 Y6 ID17 ID18 IDC17 U9 GND U10 GND FieldBus card BMS card 230Vac L N Fig 5 q Example 2 Connection diagram with digital inputs at...

Page 32: ...C13 ID14 ID14H J3 J4 J5 J7 J8 J20 J6 J19 ID15H ID15 IDC15 ID16 ID16H Y5 Y6 ID17 ID18 IDC17 U9 GND U10 GND eldBus card BMS card 24Vac 28 36 Vdc 0 V ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 IDC1 ID9 ID10 ID11 ID...

Page 33: ...2 serial port J26 is however electrically isolated from the driver s serial line this ensures that in case of external faults on the line connected to FBus2 the internal driver can keep on working ind...

Page 34: ...dconsecutively at very close intervals e g star delta motor starter in the order of hundreds of ms use relays belonging to the same group according to the following table RELAY GROUPS FOR CONSECUTIVE...

Page 35: ...G0 Y1 Y2 Y3 Y4 ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 IDC1 out H M NTC NTC G digitalinput9 CP digitalinput10 digitalinput11 digitalinput12 digital input 13 digital input 14 digital output 9 digital output 10...

Page 36: ...Each pCO constantly updates the displays on the private terminals while the shared terminals if present are updated only by the pCO that is controlling the terminal at that time The gure below illust...

Page 37: ...hed the terminal will display a blank screen In this case proceed as follows Procedure 1 Press the UP DOWN and Enter buttons together to go to the screen for setting the terminal address Display addre...

Page 38: ...CO Manager program and a serial converter with RS485 output to connect to the pCO pCO Manager is part of the 1Tool program suite it can also be installed by itself and can be obtained free of charge a...

Page 39: ...the controller immediately executes Autorun and upon con rmation from the terminal performs the operations contained in the le Upload and Download UPLOAD can be performed in three di erent ways 1 manu...

Page 40: ...the clock E is displayed as follows Select a memory to view its status T M E M O R Y S T A T U S P M E M O R Y S T A T U S E M E M O R Y S T A T U S 4 FLASH USB MEMORY Selecting this string displays t...

Page 41: ...llegamento sonde seriali DP 4 th Tune AT PCO100FD10 scheda seriale FieldBus PGD Touch EEV PGD1 Power PSD0 PCOS004850 scheda seriale RS485 PCO10000F0 schede LON PCO10W0BA0 scheda interfaccia BACnet RS4...

Page 42: ...vi terze parti FAN PUMP INVERTER PCOS004850 scheda seriale RS485 PCO10000F0 schede LON PCO10W0BA0 scheda interfaccia BACnet RS485 PCO10W0WB0 pCOWeb sch interfaccia Ethernet BACnet 5 8 4 S R s u t a t...

Page 43: ...43 ENG pCO5plus 0300020EN rel 1 2 07 11 2013...

Page 44: ...EVD200 x EVD Evolution x x CAREL slave devices tLAN x CAREL slave devices 485 x x x x x pCOexp 485 x x x x x pCOexp tLAN x Chiller2 expansion x Hydronic fan coil and CANbus x x PlantVisorPRO local x x...

Page 45: ...serial port protocols PSTN GSM Modbus Slave and CAREL Slave cannot be used on BMS serial port Modbus slave extended with pCOweb Modbus slave extended only for pCOWEB serial card with FW version 1 4 Mo...

Page 46: ...C 1Y in SSR versions Type of disconnection or microswitching microswitching Category of resistance to heat and re Category D UL94 V2 Ageing characteristics operating hours 80 000 No of automatic opera...

Page 47: ...kHz asynchronous 100 Hz asynchronous 5 8 10 Power supply for probes and terminals Vdc Active probes can be powered by the 24 21 Vdc 10 P 5 P 3 available on terminal VDC J2 The max available current i...

Page 48: ...tion of groups Model 1 2 3 4 5 6 7 8 9 10 11 SMALL 1 3 4 6 7 8 Type of relay Type A Type A Type A Type A MEDIUM BUILT IN DRIVER 1 3 4 6 7 8 9 11 12 13 Type of relay Type A Type A Type A Type A Type A...

Page 49: ...10 m or AWG14 shielded 4 wire cable Lmax 50 m Digital input connection Digital input to be activated with voltage free contact or transistor to GND Making current 5mA max length 10 m Probes Max lengt...

Page 50: ...A Non optically isolated BMS2 Non optically isolated Fieldbus2 P 5 B Optically isolated BMS2 Non optically isolated Fieldbus2 P 5 C Optically isolated BMS2 Optically isolated Fieldbus2 P 5 0 No USB p...

Page 51: ...mbols Flashing The key is connecting to the pCO During this phase which may last a few seconds the start button is disabled start Flashing The key has detected the pCO and is checking the access right...

Page 52: ...d corner Choose 1 connessione locale local connection 2 baud rate Auto 3 ricerca dispositivo nd device Auto pLAN As for the port number follow the Wizard s instructions for the port to be identi ed au...

Page 53: ...f the variables logged during monitoring Therefore to con gure Commissioning the following les are required 2CF 2CD and if necessary the DEV le which can be imported or exported For monitoring purpose...

Page 54: ...wnloaded to the pendrive as the directories created can only be numbered with XY 00 to 99 FILE TYPES FOR DOWNLOAD controller pLAN address 1 File extension Directory name Description DWL LOG00_01 Logge...

Page 55: ...and must be entered in the order shown in the table UPLOAD le labels No Label File type No Label File type 1 BIO le bin 6 PVT le pvt 2 IUP le iup 7 LCT le lct 3 BIN le bin blb 8 OED le oed 4 DEV le d...

Page 56: ...OS is updated and then the application The information is shown on the pCO s built in display and on the pGD1 terminal when both are featured Procedure 1 Connect the pendrive to port A USB key BMS car...

Page 57: ...e directory level press ESC Once the upload has started the messages shown on the screen are the same as in automatic and autorun mode Download As mentioned above the DOWNLOAD operation can be managed...

Page 58: ...to con gure pCOnet parameters Con guring pCOWeb When you select PCOWEB settings the following screen will appear D H C P I P A D D R E S S After a short time the elds are populated with the current pa...

Page 59: ......

Page 60: ...L INDUSTRIES Headquarters Via dell Industria 11 35020 Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 e mail carel carel com www carel com Agenzia Agency pCO5plus 0300020EN rel 11 2 07 11 2...

Reviews: