Index Size
Ref.
Type
Min/Max R/W
UoM Description
231
2
S025
REAL
0..999.9
R/W
°C/°F
S025 - Low noise source fan setpoint in cooling
233
1
S026
INT
0..999
R/W
s
S026 - Compr. delay ON since the source pump ON
234
1
S027
INT
0..999
R/W
s
S027 - Source pump delay OFF since the compr. OFF
235
2
S028
REAL
-99.9..999.9 R/W
°C/°F
S028 - Source fan cool setpoint
237
2
S029
REAL
0..99.9
R/W
°C/°F
S029 - Source fan heat setpoint
241
2
S031
REAL
0..999.9
R/W
°C/°F
S031 - Source fan cool setpoint at startup
243
1
S032
INT
0..999
R/W
s
S032 - Source fan cool startup delay
246
2
S034
REAL
0..99.9
R/W
K/R
S034 - Source fan cool differential
248
2
S035
REAL
0..99.9
R/W
K/R
S035 - Source fan heat differential
250
2
S036
REAL
0..100
R/W
%
S036 - Source fan inverter min speed
252
2
S037
REAL
0..100
R/W
%
S037 - Source fan inverter max speed
254
2
S039
REAL
-99.9..99.9
R/W
°C/°F
S039 - Defrost start threshold
256
2
S040
REAL
S039..99.9
R/W
°C/°F
S040 - Defrost start threshold reset
258
1
S041
INT
0..999
R/W
min
S041 - Defrost start delay
259
2
S042
REAL
-99.9..999.9 R/W
°C/°F
S042 - Defrost end threshold
261
1
S044
INT
0..999
R/W
s
S044 - Defrost begin delay before actuating the 4 way valve
262
1
S045
INT
0..999
R/W
s
S045 - Defrost ending delay after actuating the 4 way valve
263
1
S046
INT
0..99
R/W
min
S046 - Defrost min duration
264
1
S047
INT
0..99
R/W
min
S047 - Defrost max duration
265
1
S048
INT
0..999
R/W
s
S048 - Dripping duration
266
1
S049
INT
0..999
R/W
s
S049 - Post dripping duration
267
1
S050
INT
0..999
R/W
min
S050 - Delay between defrosts
272
1
S053
INT
0..2
R/W
S053 - Defrost synchronization type (0=Independent, 1=Separated, 2=Simultaneous)
274
2
S054
REAL
0..999.9
R/W bar/psi S054 - Delta press. to reverse the 4 way valve
278
1
S056
INT
0..999
R/W
s
S056 - Duration of smart start function
279
2
S057
REAL
-99.9..999.9 R/W
°C/°F
S057 - Antifreeze source alarm threshold
281
2
S058
REAL
0..999.9
R/W
K/R
S058 - Antifreeze source alarm differential
283
1
S059
INT
0..999
R/W
s
S059 - Antifreeze source alarm delay time at 1K below threshold
284
2
S060
REAL
-99.9..99.9
R/W
K/R
S060 - Probe offset of Return water/Air temp. from source
286
1
Hc00
INT
0..3
R/W
Hc00 - Analog input 3 config. (0=Not used, 1=Source temp., 2=Discharge temp., 3=Suction temp.)
287
1
Hc01
INT
0..1
R/W
Hc01 - Analog input 4 and 5 config. (0=Pressure, 1=Temp.)
288
1
Hc03
INT
0..3
R/W
Hc03 - Analog input 6 config. (0=Not used, 1=Remote setpoint, 2=Source temp.)
289
1
Hc04
INT
0..1
R/W
Hc04 - Analog input 7 config.(0=Not used, 1=Suction temp.)
290
1
Hc05
INT
0..1
R/W
Hc05 - Analog input 6 config. of Slave board (0=Not used, 1=Remote setpoint)
291
1
Hc06
INT
0..6
R/W
Hc06 - Digital input 4 config. (0=Not used, 1=Compr.2 circ.1 overload, 2=Remote ON/OFF,
3=Cool/Heat, 4=2nd SetPoint, 5=Remote alarm , 6=User pump 1 overload)
292
1
Hc07
INT
0..6
R/W
Hc07 - Digital input 5 config. (0=Not used, 1=Compr.2 circ.1 overload, 2=Remote ON/OFF,
3=Cool/Heat, 4=2nd SetPoint, 5=Remote alarm , 6=User pump 1 overload)
293
1
Hc08
INT
0..6
R/W
Hc08 - Digital input 6 config. (0=Not used, 1=Compr.2 circ.1 overload, 2=Remote ON/OFF,
3=Cool/Heat, 4=2nd SetPoint, 5=Remote alarm , 6=User pump 1 overload)
294
1
Hc09
INT
0..5
R/W
Hc09 - Digital input 4 config. of Slave board (0=Not used, 1=Compr.2 circ.2 overload, 2=Remote
ON/OFF, 3=Cool/Heat, 4=2nd SetPoint, 5=User pump 1 overload)
295
1
Hc10
INT
0..5
R/W
Hc10 - Digital input 5 config. of Slave board (0=Not used, 1=Compr.2 circ.2 overload, 2=Remote
ON/OFF, 3=Cool/Heat, 4=2nd SetPoint, 5=User pump 1 overload)
296
1
Hc11
INT
0..5
R/W
Hc11 - Digital input 6 config. of Slave board (0=Not used, 1=Compr.2 circ.2 overload, 2=Remote
ON/OFF, 3=Cool/Heat 4=2nd SetPoint, 5=User pump 1 overload)
307
2
SEtC
REAL U006..U007 R/W
°C/°F
SEtC - Cool setpoint
309
2
SEtH
REAL U008..U009 R/W
°C/°F
SEtH - Heat setpoint
324
2
C017
REAL
0..999.9
R/W
°C/°F
C017 - Threshold of max high pressure (HP)
326
2
C018
REAL
-99.9..99.9
R/W bar/psi C018 - Threshold of min low pressure (LP)
328
1
E047
INT
0..2
R/W
E047 - Type of ExV driver (0= Disabled, 1= EVD embedded, 2=EVD EVO)
331
2
REAL
0.0…100.0 R/W
%
Power request value from BMS
335
2
P000
REAL
-99.9..999.9 R/W
°C/°F
P000 - Evaporating min temp. custom envelop limit
337
2
P001
REAL
-99.9..999.9 R/W
°C/°F
P001 - Condensing max temp. custom envelop limit
340
1
P003
UINT
0..999
R/W
s
P003 - Out of envelop alarm delay time
341
1
P004
UINT
0..999
R/W
s
P004 - Low pressure difference alarm delay
344
2
P006
REAL
0..100
R/W
%
P006 - Oil recovery min request for activation
ENG
µC0300053EN rel. 1.0 – 23.07.2018
6. Supervisor table |