Digital inputs - Slave circuit 2
Ref. Description
Configuration
parameters
ID1 Pump 2 overload
U061
ID2 Compressor 1 overload
C035
ID3 High pressure switch
C034
ID4 Not present
Hc09; C035;
U059; U058;
U062; U057;
U061
ID5 Remote alarm
Hc10; C035;
U059; U058;
U062; U057;
U061
ID6 Not used
--
Digital outputs - Master circuit 1
Ref.
Description
Configuration
parameters
C-NO1 Compressor 1
C036
C-NO2 Compressor 2
C036
C-NO3 User pump 1
U063
C-NO4 Reversing valve
U066; S063; U065
C5-NO5 Alarm
U064
C6-NO6 Not used
--
Digital outputs - Slave circuit 2
Ref.
Description
Configuration
parameters
C-NO1 Compressor 1
C036
C-NO2 Compressor 2
C036
C-NO3 User pump 2
U063
C-NO4 Reversing valve
U066; S063; U065
C5-NO5 Alarm
U064
C6-NO6 Not used
--
Note:
(*) the configuration of the output depends on the type of unit: heat pump (reverse-cycle) =>
reversing valve; Chiller with free cooling => FC valve; otherwise => Frost protection heater.
Analogue outputs - Master circuit 1
Ref. Description
Type
Notes
Y1 Modulating fan
0-10V
FCS1*0
/CONVONOFF
Y2 Not used
0-10V
Analogue outputs - Slave circuit 2
Ref. Description
Type
Notes
Y1 Modulating fan
0-10V
FCS1*0
/CONVONOFF
Y2 Not used
0-10V
ENG