Ref.
Description
J3
ID3
Digital input 3
ID5
Digital input 5
+V
Power supply to 4-20 mA active probes
S6
Analogue input 6
VL
Not used
ID4
Digital input 4
O
GND: reference for analogue and digital inputs
S4
Analogue input 4
J4
-
BMS serial port (RS485): Rx/Tx-
+
BMS serial port (RS485): Rx/Tx+
O
BMS serial port (RS485): GND
J5
-
Fieldbus serial port (RS485): Rx/Tx -
+
Fieldbus serial port (RS485): Rx/Tx +
O
Fieldbus serial port (RS485): GND
J6
C
Common for relays 1, 2, 3, 4
NO1
Digital output (relay) 1
NO2
Digital output (relay) 2
NO3
Digital output (relay) 3
NO4
Digital output (relay) 4
J7
C
Common for relay 5
NO5
Digital output (relay) 5
J8
-
Remote terminal connector
J9
O
Input reference
ID6
Digital input 6
O
Input reference
S7
Analogue input 7
J10(*)
G
Ultracap module power supply (future use)
G0
Vbat
Emergency power supply from Ultracap module (future use)
J11
-
(not used)
C
Common for relay 6
NO6
Digital output (relay) 6
J14(*)
Carel ExV unipolar valve connector
Tab.2.a
(*) for DIN Enhanced / High Efficiency models only
2.5
Probe
connection
NTC probes
4-20 mA probes
Fig.2.g
Fig.2.h
0-10 Vdc probes
0-5 V ratiometric pressure probes
Fig.2.i
Fig.2.j
ENG
µC0300053EN rel. 1.0 – 23.07.2018
2. Installation |