User
Display
Code
Description
Def.
Min
Max UOM
R/W
Modbus
1=Remote set point
M
Hc06
ID4 configuration
0=Not used
1=Comp 2 circuit 1 overload
2=Remote ON/OFF
3=Cooling/Heating
4=2nd set point
5=Remote alarm
6=User pump 1 overload
0
0
6
-
R/W
HR291
M
Hc07
ID5 configuration
0=Not used
1=Comp. 2 circuit 1 overload
2=Remote ON/OFF
3=Cooling/Heating
4=2nd set point
5=Remote alarm
6=User pump 1 overload
5
0
6
-
R/W
HR292
M
Hc08
ID6 configuration
0=Not used
1=Comp. 2 circuit 1 overload
2=Remote ON/OFF
3=Cooling/Heating
4=2nd set point
5=Remote alarm
6=User pump 1 overload
4
0
6
-
R/W
HR293
M
Hc09
ID4 configuration (Slave)
0=Not used
1=Comp. 2 circuit 2 overload
2=Remote ON/OFF
3=Cooling/Heating
4=2nd set point
5=User pump 1 overload
0
0
5
-
R/W
HR294
M
Hc10
ID5 configuration (Slave)
0=Not used
1=Comp. 2 circuit 2 overload
2=Remote ON/OFF
3=Cooling/Heating
4=2nd set point
5=User pump 1 overload
0
0
5
-
R/W
HR295
M
Hc11
ID6 configuration (Slave)
0=Not used
1=Comp. 2 circuit 2 overload
2=Remote ON/OFF
3=Cooling/Heating
4=2nd set point
5=User pump 1 overload
0
0
5
-
R/W
HR299
M
Hc12
NO6 configuration
0=Frost protection
1=Source fan/pump
0
0
1
-
R/W
CS049
S
Hc13
Buzzer
0/1=No/Yes
0
0
1
-
R/W
CS050
Tab.6.f
Note:
(1) Max = 3 with Panel model, Max = 2 with DIN model.
ENG
µC0300053EN rel. 1.0 – 23.07.2018
6. Parameter table |
85
Summary of Contents for MuChiller UCHBD00001130
Page 2: ......
Page 6: ......
Page 106: ...ENG 106 Chiller 0300053EN rel 1 0 23 07 2018...