ENG
User
Display
Code
Description
Def.
Min
Max
UOM
R/W
Modbus
M
C014
Min time between consecutive compressor starts
360
300
999
s
R/W
HR163
M
C017
Max high pressure threshold (HP)
65.0
0.0
999.9
°C
R/W
HR324 (2R)
M
C018
Min low pressure threshold (LP)
0.2
-99.9
99.9
bar
R/W
HR326 (2R)
M
C020
Maximum circuit destabilisation time
240
5
999
min
R/W
HR168
S
C022
Circuit 1: discharge temp. offset
0.0
-99.9
99.9
K
R/W
HR170 (2R)
S
C023
Circuit 1:suction temp. offset
0.0
-99.9
99.9
K
R/W
HR172 (2R)
S
C024
Circuit 2: discharge temp. offset
0.0
-99.9
99.9
K
R/W
HR174 (2R)
S
C025
Circuit 2: suction temp. offset
0.0
-99.9
99.9
K
R/W
HR176 (2R)
S
C026
Circuit 1: discharge pressure offset
0.0
-99.9
99.9
bar
R/W
HR178 (2R)
S
C027
Circuit 1: suction pressure offset
0.0
-99.9
99.9
bar
R/W
HR180 (2R)
S
C028
Circuit 1: condensing temp. offset
0.0
-99.9
99.9
K
R/W
HR182 (2R)
S
C029
Circuit 1: evaporation temp. offset
0.0
-99.9
99.9
K
R/W
HR184 (2R)
S
C030
Circuit 2: discharge pressure offset
0.0
-99.9
99.9
bar
R/W
HR186 (2R)
S
C031
Circuit 2: suction pressure offset
0.0
-99.9
99.9
bar
R/W
HR188 (2R)
S
C032
Circuit 2: condensing temp. offset
0.0
-99.9
99.9
K
R/W
HR190 (2R)
S
C033
Circuit 2: evaporation temp. offset
0.0
-99.9
99.9
K
R/W
HR192 (2R)
M
C034
HP pressure switch: input logic
0/1=NC/NO
0
0
1
-
R/W
CS027
M
C035
Compressor overload protector: input logic
0/1=NC/NO
0
0
1
-
R/W
CS028
M
C036
Compressor: output logic
0/1=NO/NC
0
0
1
-
R/W
CS029
M
C037
Suction pressure: probe type
0=0-5V
1=4-20mA
0
0
1
-
R/W
HR194
M
C038
Suction pressure probe: min value
0.0
-1.0
99.9
bar
R/W
HR195 (2R)
M
C039
Suction pressure probe: max value
17.3
0.0
99.9
bar
R/W
HR197 (2R)
M
C040
Discharge pressure: probe type
0=0-5V
1=4-20mA
0
0
1
-
R/W
HR199
M
C041
Discharge pressure probe: min value
0.0
-1.0
99.9
bar
R/W
HR200 (2R)
M
C042
Discharge pressure probe: max value
45.0
0.0
99.9
bar
R/W
HR202 (2R)
M
C044
Enable destabilisation
0/1=No/Yes
1
0
1
-
R/W
CS030
S
C045
Refrigerant
3=R407C
4=R410a
6=R290
10=R744
22=R32
0
0
30
-
R
HR205
M
C046
No. of unit circuits
1
1
2
-
R/W
HR206
M
C047
Type of compressors used
0=1 On/Off
1=2 On/Off
2=1 BLDC
3= 1 BLDC+On/Off
0
0
3
-
R/W
HR207
M
C048
Compressor rotation type
1=FIFO
2=Time
1
1
2
-
R/W
HR208
Tab.6.b
Note:
(1) C045 is a read-only parameter.
80
| 6. Parameter table
µC0300053EN rel. 1.0 – 23.07.2018
Summary of Contents for MuChiller UCHBD00001130
Page 2: ......
Page 6: ......
Page 106: ...ENG 106 Chiller 0300053EN rel 1 0 23 07 2018...
Page 107: ...ENG Chiller 0300053EN rel 1 0 23 07 2018 107...