7. CONFIGURATION PARAMETERS
7.1 Accessing and setting the parameters
T
he
con
fi
guration
parameters
are
used
to
select
and
control
the
functions
and
the
status
of
the
humidi
fi
er
.
From
the
main
screen
press:
•
EN
T
ER
for
2
seconds
,
•
enter
the
password
77
using
UP
or
DOWN
,
•
EN
T
ER
to
con
fi
rm
and
access
the
list
of
parameters
,
•
UP
or
DOWN
to
scroll
the
list
cyclically
,
•
EN
T
ER
to
select
a
parameter
(display:
‘set’)
,
•
UP
to
modify
(increase)
the
value
of
the
parameter
. T
o
scroll
the
values
faster
press
UP
together
with
DOWN
,
•
DOWN
to
modify
(decrease)
the
value
of
the
parameter
. T
o
scroll
the
values
faster
press
DOWN
together
with
UP
,
•
EN
T
ER
to
save
the
new
value
and
return
to
the
list
of
parameters
,
or
ESC
to
return
to
the
list
without
saving
the
new
value
,
Press
ESC
to
return
to
the
main
screen
.
7.2 Basic parameters
Parameter
UO
M
range
def
notes
P0
maximum
production
(also
see
paragraph
6
.
5)
%
20
to
100
100
P1
humidi
fi
cation
di
ff
erential
rH
,
°C
2
.
0
, …,
19
.
9
5
.
0
accessible
only
in
mode
“control”
(
A
0
=
2;3)
P2
Probe
maximum
threshold
rH
,
°C
0
...
100
80
P3
Probe
minimum
threshold
rH
,
°C
0
...
100
20
st
outlet
set
point
rH
,
°C
20
...
100
50
A
0
operating
mode:
0
=
ON/OFF
control
,
1
=
proportional
,
2
=
room
probe
,
3
=
temperature
probe
-
0
to
1
1
A
1
unit
of
measure:
0
=
kg/h;
1
=
lb/h
-
0
to
1
0
A
2
type
of
production
request
signal
(displayable
parameter
are
with
A
0
≠
0)
1
=
0
...
10
V;
2
=
2
...
10
V;
3
=
0
...
20
m
A
;
4
=
4
...
20
m
A
;
5
=
N
T
C
-
1
...
5
1
A
3
room
probe
minimum
value
rH
,
°C
-
99
...
212
0
accessible
only
in
mode
“control”
(
A
0
=
2;3)
A
4
room
probe
maximum
value
rH
,
°C
0
...
100
0
A
5
probe
o
ff
set
control
,
for
non
-
C
A
REL
probes
rH
,
°C
-
100
...
+100
0
A
6
Relay
M14
activation
delay
for
signalling
presence
of
steam
production
request
/
activating
external
fan
s
0
to
300
0
Visible
only
if
function
activated
(parameter
b1
,
see
par
11
.
6)
A
7
Relay
M14
deactivation
delay
for
signalling
presence
of
steam
production
request
/
deactivating
external
fan
s
0
to
300
180
Visible
only
if
function
activated
(parameter
b1
,
see
par
11
.
6)
C0
value
normally
displayed
1
=
input/control
signal;
2
=
steam
prod
.
;
3
=
hour
counter;
4
=
conductivity;
5
=
current
-
1
to
5
2
7.3 Advanced parameters
Parameter
UO
M
range
def
notes
b1
optional
functions
(see
paragraph
11
.
6)
-
0
to
127
0
b2
delay
time
when
shutting
down
s
0
to
120
0
b4
Override
conductivity
of
the
water
0
=
automatic
measurement
μS/cm
0
to
1250
0
Visible
only
if
function
activated
(parameter
b1
,
see
par
11
.
6)
b5
conductivity
pre
-
alarm
threshold
(*)
μS/cm
0
to
2000
1500
b6
conductivity
alarm
threshold
(*)
μS/cm
0
to
.
2000
2000
b7
foam
threshold
setting
0
=
no
foam
detection;
1
=
max
.
foam
detection
sensitivity;
100
=
min
.
foam
detection
sensitivity
%
0
to
100
50
b8
conductivity
setting
inside
the
cylinder
in
steady
operation
compared
to
rated
value
%
50
to
200
100
b9
duration
of
the
drain
to
dilute
cycle
%
50
to
200
100
bb
cylinder
maintenance
limit
time
(in
hours)
0
=
the
cylinder
life
alarm
“Cy”
and
maintenance
required
alarm
“Mn”
are
not
shown
(*)
h
0
to
4000
3000
bE
time
limit
between
two
periodical
drain
cycles
(if
periodical
drain
is
enabled
,
b1
=
64)
h
1
to
240
24
bf
days
delay
for
drain
due
to
inactivity
(if
the
drain
due
to
inactivity
has
been
disabled
,
8
set
for
b1)
days
1
to
199
3
(*)
after
999
the
display
shows
to
indicate
1000
(only
three
digits
plus
point
-
between
the
fi
rst
and
the
second
digit
-
are
displayed)
.
7.4 Serial connection parameters
Parameter
UO
M
range
def
notes
C3
serial
address
-
1
to
207
1
C4
baud
rate:
0
=
9
,
600;
1
=
19
,
200
-
0
to
1
1
C5
supervisor:
frame
(character
bits
,
parity
,
stop
bits):
0
=
8
,
N
,
2
1
=
8
,
N
,
1
2
=
8
,
E
,
2
3
=
8
,
E
,
1
4
=
8
,
O
,
2
5
=
8
,
O
,
1
6
=
7
,
N
,
2
7
=
7
,
N
,
1
8
=
7
,
E
,
2
9
=
7
,
E
,
1
10
=
7
,
O
,
2
11
=
7
,
O
,
1
0
to
11
0
C6
serial
response
transmission
delay
ms
0
to
199
0
C7
protocollo:
0
=
supervisione
C
A
REL;
1
=
Modbus®
-
0
...
1
0
C8
maximum
time
with
no
data
(sent
to
controller)
over
RS485
to
generate
stop
production
and
“SU”
alarm
0
.
1s
(ex:
50
=
5s)
0
to
3000
50
see
variable
“I”
62
7.5 Read-only parameters
Parameter
UO
M
range
def
notes
d1
display
signal
measured
by
external
controller
(only
if
A
0
=
1)
%
0
.
0
to
199
-
d3
display
steam
production
(instant
value)
kg/h
0
.
0
to
199
-
d5
conductivity
of
the
supply
water
(*)
μS/cm
0
to
1500
-
d6
current
A
0
.
0
to
199
-
d7
display
maximum
production
(releated
to
P0
set
range)
kg/h
0
.
0
to
199
-
d9
rated
steam
production
kg/h
0
.
0
to
199
-
da
cylinder
hour
counter
(
resettable
)
h
db
unit
hour
counter
(
read
only
)
h
(*)
after
999
the
display
shows
to
indicate
1000
(only
three
digits
plus
point
-
between
the
fi
rst
and
the
second
digit
-
are
displayed)
.