11
ENG
“UE
B
A
SIC”
+0300042IE
-
rel
.
1
.
6
-
21
.
11
.
2019
Fittings
p
rovided
for
the
w
ater
connections:
M
ode
l
s
UE00
1
to
UE0
1
8
M
ode
l
s
UE0
2
5
to
UE06
5
B
A
A
B
C
Key:
A
.
supply
water
inlet
B
.
drain
water
outlet
C
.
bottom
tank
drain
water
outlet
(models
UE025
to
UE065
only)
Fig.
2
.b
H
ydraulic
interfaces
dimensions
Interfaces
dimensions
drain/
fill
dimensions
mm
(
inc
)
UE00
1
to
UE0
1
8
D
72
.
6
(28
.
6)
D’
125
.
4
(49
.
4)
E
52
.
6
(20
.
7)
E’
107
.
5
(42
.
3)
Interfaces
dimensions
steam
out
l
et
and
condensed
drain
dimensions
mm
(
inc
)
UE00
1
to
UE0
1
8
F
126
.
7
(50
.
0)
F’
224
(88
.
2)
G
137
.
9
(54
.
3)
G’
21
.
7
(8
.
6)
Interfaces
dimensions
drain/
fill
dimensions
mm
(
inc
)
UE0
2
5
to
UE06
5
I
40
(15
.
8)
I’
72
(28
.
3)
I’’
10
.
2
(4
.
0)
L
123
.
2
(48
.
5)
L’
231
.
2
(91
.
0)
L’’
49
.
1
(19
.
3)
Interfaces
dimensions
steam
out
l
et
and
condensed
drain
dimen
.
mm
(
inc
)
UE0
2
5
to
UE04
5
UE04
5
*
to
UE06
5
M
172
(67
.
7) 223
.
7
(88
.
1)
M
’
30
.
2
(11
.
9) 30
.
2
(11
.
9)
N
181
(71
.
3) 181
(71
.
3)
N’
---
100
(39
.
4)
N’’
55
(21
.
7)
61
(24
.
0)
*
230
Vac
models
only
2.1 Supply water
Only
use
mains
water
with:
•
pressure
between
0
.
1
and
0
.
8
MPa
(14
.
5
and
116
PSI)
,
temperature
between
1
and
40
°C
(33
.
8
and104
°F)
and
an
instant
fl
ow
-
rate
no
lower
than
the
rated
fl
ow
of
the
fi
ll
solenoid
valve
,
the
connection
is
G3/4M
(see
par
.
“11
.
2
T
echnical
speci
fi
cations”);
•
range
hardness
10
to
40
°F
(equal
to
400
ppm
of
CaCO
3
)
,
conductivity:
75
to
1250
μS/cm;
•
no
organic
compounds
.
supp
l
y
w
ater
characteristics
unit
of
measure
norma
l
w
ater
w
ater
w
ith
l
o
w
sa
l
t
content
min
.
max
.
min
.
max
.
Hydrogen
ions
(pH)
7
8
.
5
7
8
.
5
Speci
fi
c
conductivity
at
20°C
(
σ
R
,
20
°C
)
μS/cm
300
1250
75
350
T
otal
dissolved
solids
(c
R
)
mg/l
(
1
)
(
1
)
(
1
)
(
1
)
Dry
residue
at
180°C
(R
180
)
mg/l
(
1
)
(
1
)
(
1
)
(
1
)
T
otal
hardness
(
T
H)
mg/l
CaCO
3
100
(2)
400
50
(2)
150
T
emporary
hardness
mg/l
CaCO
3
60
(3)
300
30
(3)
100
Iron
+
Manganese
mg/l
Fe+Mn
=
0
,
2
=
0
,
2
Chlorides
ppm
Cl
=
30
=
20
Silica
mg/l
SiO
2
=
20
=
20
Residual
chlorine
mg/l
Cl
-
=
0
,
2
=
0
,
2
Calcium
sulphate
mg/l
CaSO
4
=
100
=
60
Metallic
impurities
mg/l
0
0
0
0
Solvents
,
thinners
,
detergents
,
lubricants
mg/l
0
0
0
0
T
ab.
3.a
(1)
=
values
depend
on
the
speci
fi
c
conductivity;
in
general:
T
DS
#
0
,
93
*
σ
R
,
20
°C
;
R
180
#
0
,
65
*
σ
R
,
20
°C
(2)
=
not
less
than
200%
of
the
chloride
content
in
mg/l
CL
(3)
=
not
less
than
300%
of
the
chloride
content
in
mg/l
CL
-
T
here
is
not
reliable
relationship
between
hardness
and
conductivity
of
the
water
Important:
•
do
not
treat
the
water
with
softeners
,
this
may
cause
the
entrainment
of
foam
,
a
ff
ecting
the
operation
of
the
unit;
•
do
not
add
disinfectants
or
anticorrosive
compounds
to
the
water
,
as
these
are
potential
irritants;
•
the
use
of
well
water
,
industrial
water
or
water
from
cooling
circuits
and
,
in
general
,
any
potentially
chemically
or
bacteriologically
contaminated
water
is
not
recommended
.
2.2 Drain water
•
this
contains
the
same
substances
dissolved
in
the
supply
water
,
however
in
larger
quantities;
•
it
may
reach
a
temperature
of
100
°C
(212
°F);
•
it
is
not
toxic
and
can
be
drained
into
the
sewerage
system
.