20
ENG
“compactsteam” +0300092IE - rel. 1.3 - 16.08.2021
3.12 RS485 supervisor card (standard for
P/Ns CH***N2003)
Fig. 3.ab
Description of connections on the RS485 card
Fig. 3.ac
The RS485 card is used for communication with a supervisor using the
ModBus protocol. For the list of variables, see the table below.
Caution:
• for model CH004N0003, the CHK4850000 accessory is required
• for RS485 connections in household (IEC EN 55014-1) and residential
(IEC EN 61000-6-3) environments, use shielded cable (with shield
connected to PE both on the terminal and controller ends), maximum
length specifi ed by the EIA RS485 protocol, equivalent to European
standard CCITT V11, using AWG26 twisted pair cable; the input
impedance of the 485 stage is 1/8 unit-load (96 kOhms).
3.12.1 Parameter
table
DESCRIPTION
TYPE
R/W
CAREL
ADD
MODBUS
ADD
DEFAULT
MIN
MAX
UNIT
VOLATILE
Humidifi er ready (no alarms)
DIGITAL
R
11
11
0
0
1
-
Anti-foam wash
DIGITAL
R
12
12
0
0
1
-
Flag indicating the fi rst 50 operating hours
DIGITAL
R
26
26
-
0
1
-
Unit disabled via remote (display shows -)
DIGITAL
R/W
28
28
0
0
1
YES
0 = humidistat - 1 = 0-10 V controller (set to 0 if control via super-
visor and set the % of production using parameter PO)
INTEGER
R/W
12
267
0
0
1
NO
Maximum production (PO)
INTEGER
R/W
13
268
100
20
100
%
NO
Proportional hour counter
INTEGER
R
14
269
-
0
-
hour
-
Real hour counter
INTEGER
R
19
274
-
0
-
hour
-
Days of inactivity before wash
INTEGER
R/W
50
305
3
0
10
NO
Select protocol
0=CAREL
1-24 = MODBUS (see table of Modbus values)
INTEGER
R/W
52
307
0
0
24
NO (unit power off
neededf )
Alarm identifi cation (see table)
INTEGER
R
83
338
0
0
65535
-
Display current input
ANALOGUE R
16
16
-
0
14.5
A
-
Production in kg/h
ANALOGUE R
17
17
-
0
4.5
kg/h
-
Tab. 3.j
3.12.2 Alarm
table
(16-bit multi-bit variable number 83 Carel, 339 Modbus)
BIT NUMBER DESCRIPTION
ALARM CODE
1
MAINTENANCE WARNING
(rated current not reached)
E6
2
DRAIN ALARM
E5
3
FILL ALARM
E4
4
MAINTENANCE WARNING (perc. hour counter >
600)
E6
5
HIGH CURRENT ALARM
E1
6
PARAMETERS NOT DOWNLOADED ALARM
E0
7
NOT USED
8
LOW PRODUCTION WARNING
E2
9
FOAM WARNING
E7
10
END OF CYLINDER LIFE ALARM
E8
11
NOT USED
12
NOT USED
13
NO VOLTAGE-CURRENT CONFIGURATION
WARNING
EH
Tab. 3.k
3.12.3 Modbus
table
To avoid malfunctions, disable any hardware fl ow control on the
supervisor application level
TABLE OF MODBUS VALUES (C7)
TYPE
BAUD RATE
0
CAREL
19200
1
MODBUS 8,N,2
19200
2
MODBUS 8,N,1
19200
13
8,N,2
9600
14
8,N,1
9600
Tab. 3.l
Summary of Contents for compactSteam
Page 2: ......
Page 3: ...3 ITA compactsteam 0300092IE rel 1 3 16 08 2021 Manuale d uso ...
Page 6: ......
Page 8: ...8 ITA compactsteam 0300092IE rel 1 3 16 08 2021 ...
Page 31: ...3 ENG compactsteam 0300092IE rel 1 3 16 08 2021 User manual ...
Page 34: ......
Page 36: ...8 ENG compactsteam 0300092IE rel 1 3 16 08 2021 ...
Page 59: ......