compactSteam
Cod. +030221905 – rel 1.0 - 18 Jannuary 2006
14
3.5
Power wiring
Check that the power supply voltage to be connected matches the value indicated on the
rating plate inside the electrical panel.
Insert the power and ground connection cables into the electrical panel compartment using
the strain reliefs supplied, and connect to the terminals. An external fused disconnect
must be installed.
All wiring must be in accordance with local, state and national electric codes.
NOTE:
to avoid unwanted interference, the power cables should be kept separate from
any control wiring.
F
F
ig. 3.n
Model Code
Power supply
(single phase)
Steam Output
(lbs/hr)
Steam Output
(kg/h)
POWER
(kW)
CURRENT
(A)
EXTERNAL POWER WIRES EXTERNAL FUSE (A)
CH*01VX000 110Vac 50/60Hz
3
.
5
1
.
6
1
.
18
10
.
74
AWG12
16
CH*02VX000 110Vac 50/60Hz
5
.
5
2
.
5
1
.
86
16
.
88
AWG10
32
CH*01VD000 230Vac 50/60Hz
3
.
5
1
.
6
1
.
18
5
.
14
AWG14
10
CH*03VD000 230Vac 50/60Hz
7
3
.
2
2
.
36
10
.
27
AWG12
16
CH*05VD000 230Vac 50/60Hz
12
5
.
4
4
.
05
17
.
61
AWG10
32
NOTE:
Tolerance allowed on main voltage = -15% to +10%
Connect power wires to the power terminal block located at the bottom left of the control module.
Fig. 3.o
Connect the wiring ground wire to the unit’s chassis ground, located just behind the power wiring terminal block.
Fig. 3.p