17

4.

 

Start-Up 

IMPORTANT WARNINGS: 

1.

 

Before starting, check that the humidifier is in perfect condition, that there are no water leaks and that the electrical parts are dry; 

2.

 

Do not connect power if the humidifier is damaged or even partially wet! 

 
When installation is completed, flush the supply pipe for around 10 minutes by piping water directly into the drain, without sending it into the humidifier; 

this will eliminate any scale or residues that may cause foam when boiling. 
 
 

4.1

 

Startup Checklist 

Before starting the humidifier, the following should be checked: 
 

 Water is connected, the line has been flushed, and external valves are open. 
 Drain is connected, run to an open drain, and has a trap under the unit. 
 Electricity is connected in accordance with instructions, local codes and data labels in the unit. 
 The power fuses are installed and intact. 
 All control wiring is done and tested. 
 Airflow switch is wired to open on air flow loss. 
 Hi-limit humidistat is wired to open on humidity rise above set point. 
 Unit wires have been checked to make sure they and all connectors are tight from shipping. 
 The steam hose(s) are run correctly with no sags or kinks and sloped properly according to the manual. 
 Condensate hoses are run correctly with no sags or kinks and sloped properly according to the manual. 

 

NOTE

: If you ordered a factory startup, this checklist will be required.  Failure to complete this checklist may result in additional charges. 

 
 
 

4.2

 

The compactSteam Controller 

he 

compactSteam

 controller features a comprehensive information display that shows the operation of the system at a glance: 

 
Legenda: 
1. 

Display is % of nominal capacity 

2. Maintenance 

required 

3. 

Display is amperage (default) 

4. 

Steam is being produced 

5. Cylinder 

filling 

6. Foaming 
7. Cylinder 

full 

8. Cylinder 

draining 

9. 

LEDs indicate: power (yellow), operation (green) and alarms (red) 

10. 

Drain button for manual draining of cylinder and confirming parameter values 

11. ON/OFF 

button 

12. 

Reset button to reset alarms and access parameters 

13. 

Level of output: 33%, 66%, 100% 

14. 

Fan relay is activated 

1

2

4
5

6

9

10

12

13

14

11

3

7
8

 

Fig. 4.a 

Summary of Contents for compactSteam CH002V1000

Page 1: ...compactSteam residential light commercial steam humidifiers User manual...

Page 2: ......

Page 3: ...all items have been received Notify Carel USA of any shortages or damaged parts You must notify Carel USA within 5 working days of any shortages The conditions of the environment and the power supply...

Page 4: ......

Page 5: ...p Checklist 17 4 2 The compactSteam Controller 17 4 3 Starting compactSteam 18 4 4 Starting with a new cylinder 18 5 Operating compactSteam 19 5 1 3 1 Displaying Information 19 5 2 Changing The Maximu...

Page 6: ......

Page 7: ...en begin to warm and produce steam If the water reaches the cylinder full probes 8 prior to reaching the desired current level the fill valve 1 will be closed to prevent overflow and the drain valve 1...

Page 8: ...ischarge ss nominal steam flow in kg h read table on page 14 for the complete list of nominal steam flow c control type v power supply 1 110 VAC 1 phase 2 230 VAC 1 phase xx customisation r release Ex...

Page 9: ...h and the amount of condensate Certain clearances must be maintained around the unit for safety and maintenance F Fig 3 a With room distributor units other clearances apply C D Fig 3 b Unit Dimensions...

Page 10: ...river to remove the four cover screws Then simply pull the front cover away from the back part of the unit Return it in reverse order Be careful not to overtighten the screws Fig 3 d Fig 3 e 3 2 2 Fas...

Page 11: ...2 Water drain The compactSteam also requires connection to a drain The drain water characteristics are Fig 3 h The drain line can be 1 1 4 schedule 40 PVC or CPVC 1 1 4 copper or 1 1 4 Polypropylene...

Page 12: ...densate return 2 Apply silicone sealant to the mounting plate and insert the pipe through the hole and secure it with 4 sheet metal screws 3 Connect the steam and condensate hoses using the hose clamp...

Page 13: ...for instructions 20 5 5 FT max IFNO TRAP 20 20 5 10 FT max 20 FT max GENTLEBEND OBSTRUCTION SUPPORTED STEAM HOSE AND ORCOPPERPIPE NO SLOPE NO SLOPE KINKED NO TRAP UNDRAINED ELBOW UNDRAINED ELBOW NO D...

Page 14: ...ould be kept separate from any control wiring F F ig 3 n Model Code Power supply single phase Steam Output lbs hr Steam Output kg h POWER kW CURRENT A EXTERNAL POWER WIRES EXTERNAL FUSE A CH 01VX000 1...

Page 15: ...ting signal 5 Press drain min 1 second when done to confirm the new value of P1 and exit to the normal operating mode 6 Switch compactSteam off you can now proceed with connecting the control wiring F...

Page 16: ...ing diagram of controller DRAIN VALVE STEAM BOILERUNIT DT EVF HL POWERSUPPLY 110 VAC1 PHASE50 60 HZ OR 230 VAC1 PHASE50 60 HZ 24 VACFOR EXTERNAL HUMIDISTATS EXTERNALDUCTFAN ALARM HUMIDIST AT REMOTEON...

Page 17: ...n air flow loss Hi limit humidistat is wired to open on humidity rise above set point Unit wires have been checked to make sure they and all connectors are tight from shipping The steam hose s are run...

Page 18: ...wo buttons 3 Keep pressed reset sel until the display shows 04 WARNING do NOT confirm any value higher than 04 In case press reset sel until the display goes back to the normal operating mode and rest...

Page 19: ...y shows 00 and the spanner blinks then release the two buttons 3 Keep pressed reset sel until the display shows 01 WARNING do NOT confirm any value higher than 04 In case press reset sel until the dis...

Page 20: ...ayed 50 hrs later until the hour counter is reset and the cylinder replaced Change cylinder not urgent E4 Fill alarm unable or slow fill current does not increase within timeout Press reset sel key fo...

Page 21: ...idifier wets the floor below 1 the humidifier drain is blocked 2 the supply water or overflow circuit has leaks 3 the condensate drain pipe does not bring the water back to the drain pan 4 the steam h...

Page 22: ...use protective gloves To replace the cylinder completely drain the cylinder by pressing and holding the drain button until the cylinder is empty turn the humidifier off and disconnect the main power...

Page 23: ...team CY0SD0000 12 lbs h 5 4 kg h 230 low 125 350 KITCY0FG00 Internal filter and gasket valid for all cylinders Item Part No Description 1 Read the table below Steam generator cylinder CHMCONT10 Contro...

Page 24: ...e use for a period of 2 years and 1 month from the date of shipment The OEM controls warranty is 2 years from date of manufacture humidifier replacement parts warranty is 90 days from date of Invoice...

Page 25: ...______________________________________________________________________________ _______________________________________________________________________________________________________________________ _...

Page 26: ...______________________________________________________________________________ _______________________________________________________________________________________________________________________ _...

Page 27: ......

Page 28: ...CAREL S p A Via dell Industria 11 35020 Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 http www carel com e mail carel carel com Agenzia Agency cod 030221905 rel 1 0 18 Jannuary 2006...

Reviews: