6.

 

Trouble-Shooting 

 

problem causes 

solutions 

The humidifier does not turn on  

1. no electrical power 
2. on/off switch of the humidifier in position 0 (open) 
3. control connectors improperly connected 
4. blown fuses 
5. transformer failure  

1. check the safety devices upstream from the humidifier and the 
presence of power 
2. close the switch on the panel: position I 
3. check that the connectors are properly inserted in the terminal block 
4. check the condition of fuses  
5. check that the proper voltage is connected and turned on 

The humidifier does not start operation 

1. remote ON/OFF contact open 
2. the humidistat has not been connected correctly 
3. humidistat failure 
4. control signal not compatible with the type set 
5. value measured by the sensor/s higher than the 
corresponding set point  
 

1. close ON/OFF contacts 
2. check the external connection 
3. replace the humidistat 

The humidifier fills with water without producing 
steam 

1. high steam back pressure 
2. fill valve strainer clogged 
3. mineral in the fill cup 
4. drain solenoid valve leaking  

1. check that the steam hose is not kinked or sagging, trapping 
condensate 
2. clean the fill valve strainer 
3. clean the fill cup 
4. check for voltage at the drain solenoid valve and/or drain solenoid 
replacement  
 

The humidifier wets the duct  

1. the distributor is not installed correctly (too near the 
top of the duct or the condensate return is blocked) 
2.system over-sized 
3.humidifier active when the fan in the duct is off  

1. check that the steam distributor is installed correctly 
2. decrease the steam production set on the control 
3. check the connection of the device (flow switch or differential 
pressure switch) slaving the humidifier to the ventilation in the duct 
 

The humidifier wets the floor below  

1. the humidifier drain is blocked 
2. the supply water or overflow circuit has leaks 
3. the condensate drain pipe does not bring the water 
back to the drain pan 
4. the steam hose is not properly fastened to the cylinder  
 

1. clean the drain assembly and pan 
2. check the entire water circuit 
3. check the correct position of the condensate drain hose in the drain 
pan 
4. check the fastening of the hose clamps on the steam outlet  

 
 

problem causes 

solutions 

Water in the cylinder turns black 

1. minerals in the cylinder have overconcentrated and 
are deteriorating the electrodes. 

 

1. Check for sags & kinks that could trap condensate in the steam 
hoses that could cause a back pressure on the cylinder.  
2. Check the duct static pressure.  
3. Check the fill valve and inlet strainer.  
4. Check the drain valve operation.  
5. Correct installation problems and replace cylinder.

 

Heavy arcing occurs within hours of startup 

1. The feed water contains large amounts of Iron, 
Copper or other conductive contaminants.  

1. Contact the factory for an optional drain timer to force additional 
drains to control the minerals. 
2. If you are using a softener, check the salt being used. If it contains 
any additives, discontinue use, flush all lines and convert to pure salt 
or unsoftened water. 
3. Check the electrodes in the cylinder to be sure they were not 
damaged in shipping. 

Humidifier continuously fills and drains without 
producing steam 

1. Mineral has bridged between the electrodes. 
2. There is back pressure from the steam hoses or duct. 
3. The flow regulator in the fill valve is broken or out  
of place. 
4. Water conductivity is very high. 
5. Water is foaming excessively. 

1. Clean or replace the cylinder. 
2. Check the steam hoses for kinks or gullies that might be trapping 
condensate. 
3. Replace the fill valve. 
4. Consider using a mix of demineralized water with raw water. 
5. Check cylinder - replace if exhausted. If feed water contains silica 
or nitrates, install a 1 micron water filter. 

 

 

Summary of Contents for compactSteam CH002V1000

Page 1: ...compactSteam residential light commercial steam humidifiers User manual...

Page 2: ......

Page 3: ...all items have been received Notify Carel USA of any shortages or damaged parts You must notify Carel USA within 5 working days of any shortages The conditions of the environment and the power supply...

Page 4: ......

Page 5: ...p Checklist 17 4 2 The compactSteam Controller 17 4 3 Starting compactSteam 18 4 4 Starting with a new cylinder 18 5 Operating compactSteam 19 5 1 3 1 Displaying Information 19 5 2 Changing The Maximu...

Page 6: ......

Page 7: ...en begin to warm and produce steam If the water reaches the cylinder full probes 8 prior to reaching the desired current level the fill valve 1 will be closed to prevent overflow and the drain valve 1...

Page 8: ...ischarge ss nominal steam flow in kg h read table on page 14 for the complete list of nominal steam flow c control type v power supply 1 110 VAC 1 phase 2 230 VAC 1 phase xx customisation r release Ex...

Page 9: ...h and the amount of condensate Certain clearances must be maintained around the unit for safety and maintenance F Fig 3 a With room distributor units other clearances apply C D Fig 3 b Unit Dimensions...

Page 10: ...river to remove the four cover screws Then simply pull the front cover away from the back part of the unit Return it in reverse order Be careful not to overtighten the screws Fig 3 d Fig 3 e 3 2 2 Fas...

Page 11: ...2 Water drain The compactSteam also requires connection to a drain The drain water characteristics are Fig 3 h The drain line can be 1 1 4 schedule 40 PVC or CPVC 1 1 4 copper or 1 1 4 Polypropylene...

Page 12: ...densate return 2 Apply silicone sealant to the mounting plate and insert the pipe through the hole and secure it with 4 sheet metal screws 3 Connect the steam and condensate hoses using the hose clamp...

Page 13: ...for instructions 20 5 5 FT max IFNO TRAP 20 20 5 10 FT max 20 FT max GENTLEBEND OBSTRUCTION SUPPORTED STEAM HOSE AND ORCOPPERPIPE NO SLOPE NO SLOPE KINKED NO TRAP UNDRAINED ELBOW UNDRAINED ELBOW NO D...

Page 14: ...ould be kept separate from any control wiring F F ig 3 n Model Code Power supply single phase Steam Output lbs hr Steam Output kg h POWER kW CURRENT A EXTERNAL POWER WIRES EXTERNAL FUSE A CH 01VX000 1...

Page 15: ...ting signal 5 Press drain min 1 second when done to confirm the new value of P1 and exit to the normal operating mode 6 Switch compactSteam off you can now proceed with connecting the control wiring F...

Page 16: ...ing diagram of controller DRAIN VALVE STEAM BOILERUNIT DT EVF HL POWERSUPPLY 110 VAC1 PHASE50 60 HZ OR 230 VAC1 PHASE50 60 HZ 24 VACFOR EXTERNAL HUMIDISTATS EXTERNALDUCTFAN ALARM HUMIDIST AT REMOTEON...

Page 17: ...n air flow loss Hi limit humidistat is wired to open on humidity rise above set point Unit wires have been checked to make sure they and all connectors are tight from shipping The steam hose s are run...

Page 18: ...wo buttons 3 Keep pressed reset sel until the display shows 04 WARNING do NOT confirm any value higher than 04 In case press reset sel until the display goes back to the normal operating mode and rest...

Page 19: ...y shows 00 and the spanner blinks then release the two buttons 3 Keep pressed reset sel until the display shows 01 WARNING do NOT confirm any value higher than 04 In case press reset sel until the dis...

Page 20: ...ayed 50 hrs later until the hour counter is reset and the cylinder replaced Change cylinder not urgent E4 Fill alarm unable or slow fill current does not increase within timeout Press reset sel key fo...

Page 21: ...idifier wets the floor below 1 the humidifier drain is blocked 2 the supply water or overflow circuit has leaks 3 the condensate drain pipe does not bring the water back to the drain pan 4 the steam h...

Page 22: ...use protective gloves To replace the cylinder completely drain the cylinder by pressing and holding the drain button until the cylinder is empty turn the humidifier off and disconnect the main power...

Page 23: ...team CY0SD0000 12 lbs h 5 4 kg h 230 low 125 350 KITCY0FG00 Internal filter and gasket valid for all cylinders Item Part No Description 1 Read the table below Steam generator cylinder CHMCONT10 Contro...

Page 24: ...e use for a period of 2 years and 1 month from the date of shipment The OEM controls warranty is 2 years from date of manufacture humidifier replacement parts warranty is 90 days from date of Invoice...

Page 25: ...______________________________________________________________________________ _______________________________________________________________________________________________________________________ _...

Page 26: ...______________________________________________________________________________ _______________________________________________________________________________________________________________________ _...

Page 27: ......

Page 28: ...CAREL S p A Via dell Industria 11 35020 Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 http www carel com e mail carel carel com Agenzia Agency cod 030221905 rel 1 0 18 Jannuary 2006...

Reviews: