58
ENG
c.pCO sis
tem
a
+
0300057EN
re
l. 1.2 - 29.05.2017
11.1 Devices that can be connected to the c.pCO
Device
seriale zero -
pLAN o display port
seriale one - BMS1
seriale two
– FBus 1
seriale three -
BMS 2
seriale four -
FBus 2
USB Master
(Host)
USB Slave
(Device)
Ethernet
connec
tor J11
connec
tor J10
connec
tor
J3 Disp
.
PC
OS004850
PC
O10000F0
PC
O10W0WB0
PC
O10W0BA0
PC
OS00KXB0
PC
O100FD10
PC
OS00KXF0
connec
tor J25
connec
tor J6
BMS
connec
tor J26
(and J23 su
L - XL)
connec
tor J4
FBus
pGD1 terminal
x
x
PCOT - pCOI terminal
(pGD1 version only)
x
x
pLDPRO terminal
x
x
EVD Evolution
x
x
x
CAREL Slave devices (485)
x
x
x
pCOexp 485
x
x
x
c.pCOe
x
x
x
PlantVisorPRO x
x
x
x
x
x
x
x
PlantWatchPRO
x
x
x
x
x
x
x
x
PCGate
x
x
x
x
x
x
x
x
WebGate
x
x
x
x
x
x
x
x
GATEWAY**0
x
x
x
x
x
x
x
x
LON - Echelon FTT10
x
BACnet MS/TP (RS485)(*)
x
x
x
x
Konnex
x
x
HTTP client
x
x
BACnet/Ethernet
x
BACnet/IP
x
x
SNMP v1, SNMP v2C
x
Modbus TCP/IP
x
x
Modbus supervisor (RTU)
x
x
x
x
x
Modbus Slave devices
x
x
x
Power +
x
x
x
Pendrive (USB flash drive )
x
PC Mass Storage
x
th-Tune terminal
x
x
x
pGD Touch
x
x
x
x
x
x
x
Tab. 11.a
(*) the BACnet MS/TP protocol is available on BMS2 / FBus2 / Ethernet, if the additional license is enabled on the controller (the protocol is active on 1 port at a time).
12. TEC
H
NICAL SPECIFICATIONS
12.1 c.pCO technical specifications
Physical specifications
Dimensions
MINI
panel
147.3 x 81.3 x 70.5 mm
4 DIN modules
70 x 110 x 63 mm
SMALL
13 DIN modules 110 x 227,5 x 60 mm
MEDIUM, LARGE, EXTRALARGE
18 DIN modules 110 x 315 x 60 mm
BUILT-IN DRIVER
18 DIN modules 110 x 315 x 75 mm
Plastic case
Assembly
on DIN rail in accordance with DIN 43880 and IEC EN 50022 / or panel
Material
technopolymer
Flammability
V2 (UL94) and 850 °C (in accordance with IEC 60695)
Ball pressure test temperature
125 °C
Resistance to creeping current
≥ 250 V
Colour
White RAL 9016
Built-in terminal
PGD1 (132x64 pixel) with backlit keypad
Other specifications
Operating conditions
c.pCO: P+5**SE***0** (w/o built-in terminal): -40T70 °C, 90% RH non-condensing(*)
c.pCOmini: P+(D)*******0** (w/o built-in terminal): -40T70 °C, 90% RH non-cond.
c.pCO:P+5**SE***E** (with built-in term.): -20T60 °C, 90% RH non-condensing
c.pCOmini: P+(D,P)*******E** (with built-in term.): -20T60 °C, 90% RH non-cond.
(*) with Ultracap module fitted: -40T60°C
Storage conditions
c.pCO: P+5**SE***0** (w/o built-in terminal): -40T70 °C, 90% RH non-condensing
c.pCOmini: P+(D)*******0** (w/o built-in terminal): -40T70 °C, 90% RH non-cond.
c.pCO: P+5**SE***E** (with built-in terminal): -30T70 °C, 90% RH non-cond.
c.pCOmini: P+(D,P)*******E** (with built-in terminal): -30T70 °C, 90% RH non-cond.
Ingress protection
c.pCO: IP20 on the front panel only
c.pCOmini: P+P********** (panel): IP 65; P+D********** (DIN): IP 40
Controller pollution class
2
Class according to protection against electric
shock
c.pCO: to be integrated into Class I and/or II equipment in versions without valve driver, Class I in versions with
valve driver
c.pCOmini: to be integrated into Class I and/or II equipment (Basic/Enhanced) - Class I (High-End)
PTI of insulating materials
PCB: PTI 250 V; insulating material: PTI 175
Period of electrical stress across the insulating parts
long
Type of action
1C; 1Y for SSR versions
Type of disconnection or microswitching
microswitching
Heat and fire resistance category
Category D (UL94-V2)
Ageing characteristics (operating hours)
80,000
No. of automatic operating cycles
100,000 (EN 60730-1); 30,000 (UL60730)
Rated impulse voltage
c.pCO: 2500V