onnecting current-output pressure probes
For information on the maximum number of probes that can be connected
see the table at the beginning of this paragraph. For details on the operating
range see the data sheets supplied with the probes. The controller can
be connected to all CAREL SPK* series active pressure probes or any
commercially available pressure probes with 0 to 20 mA or 4 to 20 mA signals.
G
G0
U1
U2
U3
GND
+VDC
+V
term
GND
+5 V
REF
U4
GND
U5
GND
VG
VG0
Y1
Y2
Y3
Y4
ID
1
ID
2
ID
3
ID
4
J1
J24
J2
J3
J4
FieldBus card
B M S card
U1
U
2
U
3
GND
+V
DC
U4
GND
U
5
GND
1
1
2
2
1
2
Fig. 5.f
Key
Controller
terminals
Current-output pressure probe
1
2
+VDC
Wire 1 power
brown
Wire 1 power
brown
U1
Wire 2 Signal
white
-
U2
Wire 2 Signal
white
C
onnecting 0 to 5 V ratiometric pressure probes
For information on the maximum number of probes that can be
connected see the table at the beginning of this paragraph. For details
on the operating range see the probe data sheets. The controller can
be connected to all CAREL SPKT series active pressure probes or any
commercially available pressure probes with 0 to 5 V ratiometric signals.
Important:
•
ratiometric probes are powered by the controller via te5 VREF;
•
ratiometric probes cannot be powered by an external source.
G
G0
U1
U2
U3
GND
+VDC
+V
term
GND
+5 V
REF
U4
GND
U5
GND
VG
VG0
Y1
Y2
Y3
Y4
ID
1
J1
J24
J2
J3
J4
FieldBus card
B M S card
U1
U
2
U
3
GND
GND
+
5
V
R
EF
+V
DC
Fig. 5.g
Key
Controller terminals
Description
Wire colour
+5 Vref
Power
black
GND
Power reference
green
U1
Signal
white
C
onnecting active probes with 0 to 10 V output
For information on the maximum number of probes that can be
connected see the table at the beginning of this paragraph. For details
on the operating range see the data sheets supplied with the probes.
G
G0
U1
U2
U3
GND
+VDC
+V
term
GND
+5 V
REF
U4
GND
U5
GND
VG
VG0
Y1
Y2
Y3
Y4
ID
1
ID
2
ID
3
ID
4
J1
J24
J2
J3
J4
FieldBus card
B M S card
U1
U
2
U
3
GND
+V
DC
M
o
u
t
T
+
(G)
o
u
t
H
Fig. 5.h
Key
Controller terminals
Active probes with 0 to 10 V output
GND
Reference
+VDC
Power
U1
Signal 1
U2
Signal 2
Max. number of connectable digital inputs
The controller allows the universal inputs/outputs to be configured as
non-optically isolated, voltage-free digital inputs. In any case, the inputs
must be connected to a voltage-free contact.
Maximum number of dig. inputs connectable
to universal inputs/outputs
Type of signal
c.pCO
mini Small
Medium/ Built-in
driver/ Extralarge
Large
Digital
inputs
(not opto-
isolated)
- volt-free
contacts
10
5
8
10
- fast
inputs
max 2 max 2
4
(max 2 on U1...U5,
max 2 on U6..U8)
6
(max 2 on U1...U5,
max 2 on U6...U8,
2 on U9...U10)
Tab. 5.c
Important:
the maximum current allowed on the digital input is 10
mA. Therefore the rating of the external contact must be at least 10 mA.
C
onnecting
ON
/
OFF
inputs
There is no particular restriction on the maximum number of inputs that
can be connected. For details on the operating range see the Technical
Specifications table (see chap. 12).
G
G0
U1
U2
U3
GND
+VDC
+V
term
GND
+5 V
REF
U4
GND
U5
GND
VG
VG0
Y1
Y2
Y3
Y4
ID
1
ID
2
ID
3
ID
4
ID
5
ID
6
ID
7
J1
J24
J2
J3
J4
J5
FieldBus card
B M S card
U4
U
5
GND
GND
Fig. 5.i
Key
Controller terminals
Description
U4
Digital input 1
GND
U5
Digital input 2
GND
C
onnecting fast digital inputs
Important:
the wires connecting the fast digital inputs/counters
must be shielded to avoid causing electromagnetic interference with the
probe cables.
G
G0
U1
u2
U3
GND
+VDC
+V
term
GND
+5 V
REF
U4
GND
U5
GND
J1
J24
J2
J3
FieldBus card
U4
GND
U5
GND
J3
E
xterna
l
imp
ul
se
generator
Fig. 5.j