44
ENG
c.pCO sis
tem
a
+
0300057EN
re
l. 1.2 - 29.05.2017
2.
Select the files to be loaded onto the controller and click ”Export Ap1”. In
the application package it is possible to include also:
•
the Operating System, selecting the specific path;
•
the web pages for the c.pCO web server functionality (see Chapter 10).
Fig. 6.l
3.
Click “Export” and save the file to a flash drive, under a directory called
“UPGRADE”.
4.
Plug the flash drive into the Host USB port and enter the system
menu (see Chapter 7). On the screen, select UPGRADE and then the
application program to be loaded and confirm by pressing enter.
USB key
A
Fig. 6.m
INFORMATION
SETTINGS
APPLICATION
UPGRADE
LOGGER
DIAGNOSTICS
INFORMATION
SETTINGS
APPLICATION
UPGRADE
LOGGER
DIAGNOSTICS
Important:
•
Before updating the c.pCO controller via USB connection, check in
the system menu that the Host USB port is enabled (Settings --> USB
Settings --> Pen drive, see Chapter 7).
•
Only use flash drives with FAT file system.
•
Do not use both USB ports on the controller at the same time.
•
Do not use mass storage peripherals that have a current draw more
than 500 mA.
Update with file transfer via
F
T
P
The c.pCO family controllers fitted with Ethernet port include an FTP
server that provides access to the public partition of the file system.
Files and directories in this partition can be read, modified, created and
deleted. FTP can also be used to transfer an .ap1 file, for example to
update the image of the operating system or the application program.
This is done using an FTP client, for example “FileZilla”.
To protect the contents of the public file system against unauthorised
access, different users can be created, assigning each a different access
profile, dedicated to each service and adapted to the individual directory
(see Chapter 9). To update via FTP:
1.
Open an FTP client (e.g. FileZilla). Enter the IP address of the c.pCO
controller and the access credentials (default user “anonymous”, no
password).
2.
Drag & drop the software update file from the directory on the
computer to the “UPGRADE” directory on the c.pCO controller.
Fig. 6.n
Nota:
Please use following settings in Filezilla:
•
Edit->Settings->Connection-> set timeout in seconds = 0
•
Edit -> Settings -> Transfers -> set maximum simultaneous transfers to 1
3.
Access the system menu on the c.pCO and select “UPGRADE” (see
Chapter 7).
INFORMATION
SETTINGS
APPLICATION
UPGRADE
LOGGER
DIAGNOSTICS
INFORMATION
SETTINGS
APPLICATION
UPGRADE
LOGGER
DIAGNOSTICS
Note:
when having loaded the update file to the “UPGRADE”
directory via FTP, the update procedure can also be started using the
virtual terminal (see paragraph 10.3).
Update via tE
RA
cloud service.
See paragraph 10.6.