20
Screen/Button
Display
Function
Summary
9
Press Scan (
SCAN
)
Cnt lcl
Control Lower
Hysteresis
The degree decrease in temperature from the
setpoint that will trigger the unit to stop cooling to
prevent the unit from getting too cold.
10
Press Scan (
SCAN
)
door AJAr
Door Alarm Time
The approximate time the door can remain open
before the door ajar alarm activates in minutes.
11
Press Scan (
SCAN
)
AdP dEF
Adaptive Defrost
Setting for adaptive defrost ON (01) or
OFF (00).
12
Press Scan (
SCAN
)
dEF Int
Defrost Interval
The time interval between defrost cycles in hours.
13
Press Scan (
SCAN
)
dEF dur
Defrost Duration
The maximum amount of time the defrost cycle
will run in minutes. Value will be "nA" for units with
hot gas defrost.
14
Press Scan (
SCAN
)
dEF Hi
Defrost Temp Out
The maximum temperature that the
defrost probe can reach before stopping
the defrost cycle.
15
Press Scan (
SCAN
)
PAn Hi
Drip Pan Temp
Out
Maximum temperature drip pan probe
can reach before stopping the defrost drip time.
16
Press Scan (
SCAN
)
qUA
Quality Mode
Normally OFF(00). Used for production
line testing.
17
Press Scan (
SCAN
)
bot
BOT mode
Normally OFF(00). If ON(01), the unit is forced to
run at coldest possible temperature for
approximately 24 hours. Defrosts will still occur at
scheduled.
18
Press Scan (
SCAN
)
PEr
Perimeter heater
Duty Cycle
Controls the perimeter heater ON time.
19
Press Scan (
SCAN
)
Cnt prb
Control Probe
Temperature
Displays control probe temperature
(Read Only).
20
Press Scan (
SCAN
)
Anb prb
Ambient Probe
Temperature
Displays ambient probe temperature in
deck (Read Only).
21
Press Scan (
SCAN
)
dEF Prb
Defrost Probe
Temperature
Displays defrost probe temperature
(Read Only).
22
Press Scan (
SCAN
)
PAn Prb
Defrost Drip
Pan Probe
Temperature
Displays defrost drip pan probe
temperature.
23
Press Scan (
SCAN
)
---
Enter Defrost cycle
Pressing the scan button after displaying the
defrost Drip Pan probe temperature while not in
an alarm mode will force the unit into a defrost
cycle. To avoid defrost cycle, leave unit screen idle
for approximately 30 seconds.