background image

6

Operating instructions

1. Plug the power cord into the wall socket and turn on the power to the

heater, see figure 1. Use of an extension cord is not recommended.

2. For control lay-out refer to figure 2.

3. To turn heater on press switch to POWER ON position. There  is a 5

second delay before the burner ignites. At this setting the burner is on

LOW and the fan speed is on LOW. Refer figure 3.

The burner will ignite on both HIGH and LOW settings.

4. To turn burner to HIGH setting, press switch for HIGH setting. Refer

figure 4.

User instructions

1

2

4

3

19

page 11, figures 11 and 12, of the installation instructions.

2. Disconnect the fan plug from the plug carrier. Remove the two M5

wing nuts which locate the fan to the fan chamber underside. Lower

fan from male thread.

3. Disconnect the silicon tube from the fan pressure switch, rotate the

fan scroll 90

°

 and remove the silicon tube from the venturi located

in the fan scroll. Remove fan from fan chamber.

4. Replacement fan. Remove the blanking piece from the fan scroll.

Remove the venturi and bracket from the fan removed from the

heater. Insert and secure the venturi and bracket on replacement

fan.

5. Insert fan into fan chamber ensuring that the venturi is not disturbed.

Replace silicon tube onto the venturi and locate fan onto male thread.

Secure with M5 wing nuts, ensuring rubber buffer locates over

thread.

6. Replace silicon tube onto fan pressure switch and reconnect fan

plug into plug carrier.

7. Test operation of room circulation fan and fan pressure switch - turn

heater on high burner, low fan. The room fan should operate instan-

taneously and a possible 5 - 10 second delay for the fan pressure

switch to energise dependant on room temperature. The burner

should now operate on high setting.

To replace the fan pressure switch

1. Remove the lower pedestal front by unscrewing four M3 screws.

Refer page 11, figures 11 and 12, of the installation instructions.

2. Remove the connecting wiring (3) from the pressure switch.
3. Remove the silicon tube from the pressure switch.
4. The pressure switch is secured onto the rear of the fan chamber

housing by four M4 screws. Remove screws.

5. Replace in reverse order.

To remove the heat exchanger

Please refer to manufacturer. Contact details page 3 of this manual.

To replace the burner and spark/sense electrodes

1. Refer pages 11 and 12, steps 9 to 11, of the installation instruc-

tions.

2. Remove the logs from the burner chamber.
3. Remove the burner chamber front, 4 screws.
4. Disconnect the 16mm nut at the outlet of the gas control.
5. Disconnect the spark and sense electrodes from the ignition (mod-

ule) device.

6. Remove the burner fixing brackets (2) from the RH and LH side of

the burner. Lift the burner assembly upward and carefully remove

from the burner chamber.

7. Replace in reverse order checking location of spark/sense elec-

trodes, refer page 21, figure 37. Spark gap between electrode

and surface of burner is 4 - 6mm. Check for gas tightness. For log

placement refer page 16 of this manual

Summary of Contents for FITZFS-SDSEB-NG

Page 1: ...proved for use with Natural and Propane gases Please leave instructions with the owner FITZROY FREESTANDING USER INSTRUCTIONS INSTALLATION INSTRUCTIONS SERVICE INSTRUCTIONS FREESTANDING MODELS FITZFS...

Page 2: ...g installation Gas control Gas pressure point Installation tips Flue installation 16 17 Flue kit Service instructions 18 20 General To replace primary glass To replace outer glass To replace the gas c...

Page 3: ...ith manufacturer s instruc tions this warranty may be void The customer must keep their Tax Invoice as proof of purchase of this product and compliance certificate as proof of required installation Mo...

Page 4: ...ammable material on or near the heater 4 Keep curtains clothing furniture and other flammable materials at least 900mm from front rear and sides of the heater At the owner s discretion curtain clearan...

Page 5: ...Testing the effectiveness of the flue Before testing the flue confirm air vents are unobstructed If an exhaust fan or other heating appliances are present switch them on This is to test that there is...

Page 6: ...ol lay out refer to figure 2 3 To turn heater on press switch to POWER ON position There is a 5 second delay before the burner ignites At this setting the burner is on LOW and the fan speed is on LOW...

Page 7: ...switch for LOW setting Refer figure 7 On low burner setting it is more efficient to operate the fan speed on LOW 8 If the burner fails to ignite wait 20 seconds and repeat the ignition procedure See...

Page 8: ...heater fitted with the glass front All cleaning should be carried out when the heater is cold Clean the outer glass with a liquid solution such as Windex or similar Do not use harsh abrasive cleaners...

Page 9: ...essure 1 13 kPa Nat Gas 2 75 kPa Propane Fan 3 speed Controller Electronic direct spark Power requirement 240 VAC 10 Amp Power consumption 90 VA maximum Optional Accessories Silver trim Cathedral ceil...

Page 10: ...d furnishing refer to warning 3 4 on page 4 For minimum clearances refer fig 9 and 10 4 Remove the carton from the heater and lift from pallet Check that the heater is suitable for the gas available R...

Page 11: ...e either side Refer figure 12 10 Remove the heater front by pulling it towards you gently to partly disengage it from the body of the heater then gently lift it up vertically to completely disengage i...

Page 12: ...ront log No 4 Right back log Position the four individually numbered logs in the following order on the burner head as shown in figures 17 20 The male locating pins in the burner head must engage with...

Page 13: ...rope Check that the gas pressure is correctly adjusted If the heater still does not operate to specification refer to the trouble shooting chart on pages 20 21 or contact Sampford IXL in your state P...

Page 14: ...clockwise to decrease pressure 20 Switch the heat button back to Low Flame position as indicated in figure 25 a retain spanner in position and using a screwdriver as per figure 25 b adjust the central...

Page 15: ...service agents please refer page 19 Installation tips Make sure that the heater is fully commissioned and be certain to con duct a test of the integrity of the flue operation taking into account any...

Page 16: ...s have been observed For clearances refer page 10 2 The centre line of the flue is 115mm to rear of appliance including rear spacers 3 Carry out installation as per figure 26 ceiling plate installatio...

Page 17: ...17 27...

Page 18: ...tion instructions 2 The blue module ignition device needs to be removed to allow re moval of the gas control Remove LH screw from front lower section of ignition device Remove screw from front of rect...

Page 19: ...rgise dependant on room temperature The burner should now operate on high setting To replace the fan pressure switch 1 Remove the lower pedestal front by unscrewing four M3 screws Refer page 11 figure...

Page 20: ...e to this appliance For service to this appliance or spare parts contact the CANNON distributor Sampford IXL 52 70 Sparks Avenue Fairfield Vic 3078 Phone 1300 727 421 Fax 1300 727 425 email service sa...

Page 21: ...way switch connector will be energised as soon as the flame has been sensed 5 Confirm spark is produced A blue spark can be seen when the heater ignition when heater is turned on process starts Ensure...

Page 22: ...than 1 5 micro amps at all times Take precaution because the ionisation probe can have a high negative voltage and can cause shock 11 Fuse blowing If the fuse continues to blow check the solenoid coi...

Page 23: ...23...

Page 24: ...INS S F F F Part No F2904 Revision D 2009 Cannon FITZROY FREESTANDING...

Reviews: