background image

7

5. To increase the fan speed to MED, press switch for MED setting. Refer

figure 5.

6. To increase the fan speed to HIGH, press switch for HIGH setting.

Refer figure 6.

7. To turn the burner to LOW setting, press switch for LOW setting. Refer

figure 7.

On low burner setting it is more efficient to operate the fan speed on

LOW.

8. If the burner fails to ignite, wait 20 seconds and repeat the ignition

procedure. See below.

To turn burner OFF

To turn burner ON

    

9. In case of a power failure return the switches to the OFF  setting (refer

figure 2). When power returns, wait 20 seconds and start re-ignition

as per point 3.

5

6

7

18

Service instructions. (Do not modify this appliance).

General

1. Service work to be carried out by an authorised service person only.
2. Unplug from wall socket or turn off power at main switchboard if heater

is hard wired.

3. Always shut off the gas supply and ensure that the heater is cool before

commencing any service operations.

4. Always check for gas soundness after servicing.

To replace the primary glass

1. Refer page 11, steps 9 to 11, of the installation instructions.
2 Refit glass and replace in reverse order ensuri the inside surface of the

glass is clean and free from finger marks.

To replace the outer glass

1. Remove the top two glass retaining posts using a 4mm allan key. Sup-

port the bottom of the glass and remove the two lower glass retaining

posts. Refit glass in reverse order ensuring the inside surface of the glass

is clean and free of finger marks.

Note: ensure the inside surface of the glass is clean and free from finger

marks.

To replace the gas control

1. Remove the lower pedestal front by unscrewing four  M3 screws. Refer

page 11, figures 11 and 12, of the installation instructions.

2. The blue module (ignition device) needs to be removed to allow re-

moval of the gas control. Remove LH screw from front lower section of

ignition device. Remove screw from front of rectifier lead located below

domed cap on gas control.

3. Unplug polarise plug (wires feeding to module and gas control) and

remove spark/sense electrode connections, earth connection from mod-

ule and earth connection form gas control. Remove the module from the

gas control.

4. Disconnect the gas inlet (1/2” compression nut) connection at entry to

gas control and the 16mm nut at the outlet of the gas control.

5. Remove the three M3 screws from the cradle retaining the gas control.

Remove gas control.

6. Replace gas control and ignition device in reverse order and check for

gas tightness.

Note: check the gas pressure on high and low burner settings. Refer ‘gas

control’, pages 13 and 14.

To replace the ignition (module) device

1. Refer ‘to replace the gas control’ and perform steps 1 to 3, but do not

remove the earth connection from the gas control.

2. Remove RH screw from front lower section of ignition device.
3. Unplug wire connector from ignition device.
4. Replace ignition device in reverse order.

To replace the room circulation fan

1. Remove the lower pedestal front by unscrewing four M3 screws. Refer

Summary of Contents for FITZFS-SDSEB-NG

Page 1: ...proved for use with Natural and Propane gases Please leave instructions with the owner FITZROY FREESTANDING USER INSTRUCTIONS INSTALLATION INSTRUCTIONS SERVICE INSTRUCTIONS FREESTANDING MODELS FITZFS...

Page 2: ...g installation Gas control Gas pressure point Installation tips Flue installation 16 17 Flue kit Service instructions 18 20 General To replace primary glass To replace outer glass To replace the gas c...

Page 3: ...ith manufacturer s instruc tions this warranty may be void The customer must keep their Tax Invoice as proof of purchase of this product and compliance certificate as proof of required installation Mo...

Page 4: ...ammable material on or near the heater 4 Keep curtains clothing furniture and other flammable materials at least 900mm from front rear and sides of the heater At the owner s discretion curtain clearan...

Page 5: ...Testing the effectiveness of the flue Before testing the flue confirm air vents are unobstructed If an exhaust fan or other heating appliances are present switch them on This is to test that there is...

Page 6: ...ol lay out refer to figure 2 3 To turn heater on press switch to POWER ON position There is a 5 second delay before the burner ignites At this setting the burner is on LOW and the fan speed is on LOW...

Page 7: ...switch for LOW setting Refer figure 7 On low burner setting it is more efficient to operate the fan speed on LOW 8 If the burner fails to ignite wait 20 seconds and repeat the ignition procedure See...

Page 8: ...heater fitted with the glass front All cleaning should be carried out when the heater is cold Clean the outer glass with a liquid solution such as Windex or similar Do not use harsh abrasive cleaners...

Page 9: ...essure 1 13 kPa Nat Gas 2 75 kPa Propane Fan 3 speed Controller Electronic direct spark Power requirement 240 VAC 10 Amp Power consumption 90 VA maximum Optional Accessories Silver trim Cathedral ceil...

Page 10: ...d furnishing refer to warning 3 4 on page 4 For minimum clearances refer fig 9 and 10 4 Remove the carton from the heater and lift from pallet Check that the heater is suitable for the gas available R...

Page 11: ...e either side Refer figure 12 10 Remove the heater front by pulling it towards you gently to partly disengage it from the body of the heater then gently lift it up vertically to completely disengage i...

Page 12: ...ront log No 4 Right back log Position the four individually numbered logs in the following order on the burner head as shown in figures 17 20 The male locating pins in the burner head must engage with...

Page 13: ...rope Check that the gas pressure is correctly adjusted If the heater still does not operate to specification refer to the trouble shooting chart on pages 20 21 or contact Sampford IXL in your state P...

Page 14: ...clockwise to decrease pressure 20 Switch the heat button back to Low Flame position as indicated in figure 25 a retain spanner in position and using a screwdriver as per figure 25 b adjust the central...

Page 15: ...service agents please refer page 19 Installation tips Make sure that the heater is fully commissioned and be certain to con duct a test of the integrity of the flue operation taking into account any...

Page 16: ...s have been observed For clearances refer page 10 2 The centre line of the flue is 115mm to rear of appliance including rear spacers 3 Carry out installation as per figure 26 ceiling plate installatio...

Page 17: ...17 27...

Page 18: ...tion instructions 2 The blue module ignition device needs to be removed to allow re moval of the gas control Remove LH screw from front lower section of ignition device Remove screw from front of rect...

Page 19: ...rgise dependant on room temperature The burner should now operate on high setting To replace the fan pressure switch 1 Remove the lower pedestal front by unscrewing four M3 screws Refer page 11 figure...

Page 20: ...e to this appliance For service to this appliance or spare parts contact the CANNON distributor Sampford IXL 52 70 Sparks Avenue Fairfield Vic 3078 Phone 1300 727 421 Fax 1300 727 425 email service sa...

Page 21: ...way switch connector will be energised as soon as the flame has been sensed 5 Confirm spark is produced A blue spark can be seen when the heater ignition when heater is turned on process starts Ensure...

Page 22: ...than 1 5 micro amps at all times Take precaution because the ionisation probe can have a high negative voltage and can cause shock 11 Fuse blowing If the fuse continues to blow check the solenoid coi...

Page 23: ...23...

Page 24: ...INS S F F F Part No F2904 Revision D 2009 Cannon FITZROY FREESTANDING...

Reviews: