background image

  

Aspect 

ST 

 

 

4001

093
6-10

21

 

 

 

 

 

Installation manual 

 

ENG 

ENG 

 

 

 

 

 

Summary of Contents for Aspect L ST

Page 1: ...Aspect L ST 40010936 1021 Installation manual ENG ENG ...

Page 2: ...L 1 1 1 1 2 1 3 1 4 1 5 A ...

Page 3: ...L 2 2 1 2 2 2 3 2 4 2 5 2 6 2 7 ...

Page 4: ...L 3 3 1 3 2 3 3 ...

Page 5: ...several hours so that the lacquer coating will have an opportunity to set and possible vapours released can be safely removed by ventilation We advise you to be outside the room as much as possible during this process Please note that all transport packaging should be removed children or pets should not be present in the room 3 Installation requirements 3 1 The fire The appliance must be built int...

Page 6: ...ppliance are not damaged Clear a safe space to store the frame and the glass Remove the frame if necessary and the glass and take the separately wrapped parts out of the appliance Prepare the gas connection to the gas control valve 4 4 Placing the appliance Take the installation requirements into account see chapter 3 Place the appliance into the proper position and if necessary adjust the height ...

Page 7: ...ed from the burner plate but it should be level throughout the entire length Place the imitation logs according to instructions see fig 3 1 or the instruction card It is optional whether you apply chips to the combustion chamber or not Prevent chips from covering the burner this has a negative effect on the fire image Start the pilot en main burner according to the instructions in the user s manua...

Page 8: ... client Recommend that the appliance be serviced annually by a competent person in order to guarantee a safe use and a long lifespan Advise and instruct the client about maintenance and cleaning of the glass Emphasize the risk of burning in fingerprints Instruct the client about the operation of the appliance and the remote control unit including the replacement of the batteries and adjusting the ...

Page 9: ... vice versa are not reckoned in the calculation The wall terminal always counts as 1 metre If there is transit under 45 then the real vertical and horizontal lengths should be calculated 11 1 Points of particular interest In case of a wall terminal the entire flue system including the wall terminal should be constructed of 200 130 flue pipes In case of a roof terminal the entire flue system should...

Page 10: ... D 1 x 2 m 2 m Total 4 m Count the vertical lengths Flue pipe length A 1 m Roof terminal G 1 m Total 2 m Sample calculation 2 Count the horizontal lengths Flue pipe lengths J L 0 5 0 5 1 m Bends K M 2 2 m 4 m Wall terminal 1 m Total horizontal length 6 m Count the vertical lengths Flue pipe length H 1 m Total 1m ...

Page 11: ...nstallation than the fire most install with the 150 100 mm flue pipe Horizontaal m 0 1 2 3 4 5 6 7 8 9 10 0 x 0 x x x x x x x x x 0 5 x 0 0 0 0 x x x x x x 1 x 30 0 0 0 0 0 0 0 0 0 1 5 30 50 50 40 40 30 30 30 0 0 0 2 30 60 60 50 50 40 40 30 30 0 0 3 40 65 65 60 60 50 50 40 40 30 x 4 40 70 70 65 65 60 50 50 40 x x 5 50 70 70 70 65 65 60 50 x x x 6 55 75 75 65 65 60 60 x x x x 7 60 75 75 75 65 65 x ...

Page 12: ... h 780 750 Burner pressure at full mark mbar 9 5 23 5 24 5 Injector main burner mm ST500 7x0 79 ST510 7x0 83 ST160 7x0 48 ST180 7x0 50 ST160 7x0 48 ST180 7x0 50 Reduced input restraint mm 2 1 1 3 1 3 Pilot assembly Sit145 Sit145 Sit145 Code Nr 36 Nr 23 N 23 Diameter inlet outlet mm 200 130 200 130 200 130 Gas control valve GV60 GV60 GV60 Gas connection 3 8 3 8 3 8 Electrical connection V 220 220 2...

Page 13: ...L 12 14 Dimentions ...

Page 14: ...L 13 ...

Page 15: ...14 L ...

Page 16: ...www faber nl info faber nl Saturnus 8 NL 8448 CC Heerenveen Postbus 219 NL 8440 AE Heerenveen T 31 0 513 656500 F 31 0 513 656501 ...

Reviews: