9. Troubleshooting
Table 9.1 Fault message and description
1.Remove all DC input, reconnect and
restart inverter one by one.
2.Identify which string cause the fault and
check the isolation of the string.
DCinj-FAULT
High DC injection current
1.Check AC and DC connection
2.Check inverter inside cable connection.
1.Restart inverter or contact installer.
Alarm Message
Failure description
Solution
PV ISO-PRO
01/02
PV isolation protection
ILeak-PRO
01/02/03/04
Leakage current protection
RelayChk-FAIL
Relay check fail
NOTE
If the inverter displays any alarm message as listed in Table 9.1; please
turn off the inverter (refer to Section 6.2 to stop your inverter) and wait for 15
minutes before restarting it (refer to Section 6.1 to start your inverter). If the
failure persists, please contact your local distributor or the service center.
Please keep ready with you the following information before contacting us.
1. Serial number of Canadian Solar Three Phase Inverter;
2. The distributor/dealer of Canadian Solar Three Phase Inverter (if available);
3. Installation date.
4. The description of problem (i.e. the alarm message displayed on the LCD and the status
of the LED status indicator lights. Other readings obtained from the Information submenu
(refer to Section 6.2) will also be helpful.);
5. The PV array configuration (e.g. number of panels, capacity of panels,
number of strings, etc.);
6. Your contact details.
INI-FAULT
Initialization system fault
1.Restart inverter or contact installer.
12Power-FAULT
12V power supply fault
DSP-B-FAULT
Comm. failure between main
and slave DSP
Reve-DC
One of the DC string is
reversely connected
1. Please check the inverters’ PV string polarity,
if there are strings reversely connected wait for
the night when the solar irradiance is low and the
PV string current down below 0.5A. Turn off the
two DC switchs and fix the polarity issue.
9. Troubleshooting
Screen OFF
with DC applied
Inverter internally damaged
1.Do not turn off the DC switches as it will
damage the inverter.
2.Please wait for the solar irradiance reduces
and confirm the string current is less than
0.5A with a clip-on ammeter and then turn
off the DC switches.
3.Please note that any damages due to wrong
operations are not covered in the device
warranty.
NOTE
Before grid connection, if the string has negative current, it means the
voltage between the two strings of one MPPT is unbalanced.
One of two string may have more PV panels than another one.
.60.