7. Normal operation
7. Normal operation
5. Reac-power (Not Required)
Description: Inverter will generate reactive power based on changing output power.
Note: This Setting is NOT required by Rule21 Standards.
This function is for maintenance personnel only, wrong operation
will prevent the inverter from reaching maximum power.
6. P-factor (Not Required)
Description: Inverter will change power factor based on changing output power.
Note: This Setting is NOT required by Rule21 Standards.
This function is for maintenance personnel only, wrong operation
will prevent the inverter from reaching maximum power.
YES=<ENT> NO=<ESC>
Power
Factor
:
+
1
.
00
Figure 7.34 Fixed-PF
Figure 7.35 PF Range
7.VgWatt-UL (Not Required)
Description: Inverter will change the active output power based on voltage change.
Note: This Setting is NOT required by Rule21 Standards.
This function is for maintenance personnel only, wrong operation
will prevent the inverter from reaching maximum power.
0,6
0,6
1,0
-1,0
P/P
n
under-excited
Q/P
n
under-excited
over-excited
over-excited
I
II
IV
III
-0,2
.49.
.48.
Rated 800V Grid
V1:(640-800V) Default 736V V2: (800-960V) Default 848V
V3:(800-960V) Default 880V V4: (800-960V) Default 920V
P1:100% P2:100% P3: 0% P4:0%
Figure 7.33 Volt-VAR
Voltage1
:
0796V
Voltage2
:
0880V
4.Fixed-PF
Description: Inverter will output power with fixed power factor.
Setting Range: -0.8 to +0.8
Default value is PF = 1
8. Enable both Volt-Var and Volt-Watt modes
Description: Rule21 requires both Volt-var and Volt-watt modes can be enabled.
To set both modes (Volt-var in high priority)
Step 1: Select and set Volt-watt mode at first.
Step 2: Enter "Working Mode" again and select and set Volt-var mode then.
Step 3: To check the priority, a new mode will appear as "V-Q & V-P" which
indicates (Q) Volt-var is in high priority.
Figure 7.36 Work Mode
YES=<ENT> NO=<ESC>
Work Mode
:
V-Q & V-P