background image

 

 

www.canadiansolar.com       

Rev IM/GN-CM-EN/1.0          Copyright© October, 2020 Canadian Solar Inc.        7

 

5.1    MODULE WIRING 

Correct wiring scheme 

   

 

Cable management scheme should be reviewed and approved by the EPC contractor; in particular required 
cable  lengths  should  be  cross-checked  considering  the  specificities  of  the  tracker  structure  like  bearing 
house gaps. If longer cable or additional jumper cable is requested, please contact Canadian Solar’s sales 
representative in advance. 

 

Ensure that the wiring is correct before starting up the system. If the measured open circuit voltage (Voc) 
and short-circuit current (Isc) differ from the specifications, this indicates that there is a wiring fault.     

 

When  modules  have  been  pre-installed  but  the  system  has  not  been  connected  to  the  grid  yet,  each 
module string should be kept under open-circuit conditions and proper actions should be taken to  avoid 
dust and moisture penetration inside the connectors. 

 

The maximum distance between two adjacent module frames should be within 50 mm (1.96in) for the side 
with mounting clamps, and within 25 mm (0.98in) for the side without mounting clamps, in order to meet 
the system cable scheme. 

Correct connection of plug connectors 

   

 

Make sure that all connections are safe and properly mated. The PV connector should not be subjected to 
stress from the exterior. Connectors should only be used to connect the circuit. They should never be used 
to turn the circuit on and off.   

 

Connectors are not waterproof when unmated. When installing modules, connector should be connected 
to each other as soon as possible or appropriate measures (like using connector endcaps) should be taken 
to avoid moisture and dust penetrating into the connector. 

 

Do not clean or precondition the connectors using lubricants or any unauthorized chemical substances. 

 

Use of suitable materials     

 

Only use dedicated solar cable and suitable connectors (wiring should be sheathed in a sunlight-resistant 
conduit  or,  if  exposed,  should  itself  be  sunlight-resistant)

 

that  meet  local  fire,  building  and  electrical 

regulations. Please ensure that all wiring is in perfect electrical and mechanical condition.     

 

Installers  may  only  use  single-conductor  cable  listed  and  labeled  as  USE-2  or  PV  wire  which  is  90°C  wet 
rated in North America, and single conductor cable, 2.5-16 mm² (5-14 AWG), 90°C wet rated in other areas 
(i.e. TUV 2PfG1169 or EN50618 approved), with proper insulation which is able to withstand the maximum 
possible system open-circuit voltage.   

 

Only  copper  conductor  material  should  be  used.  Select  a  suitable  conductor  gauge  to  minimize  voltage 
drop and ensure that the conductor ampacity complies with local regulations (

i.e.

 NEC 690.8(D)).. 

Cable and connector protection 

   

 

Secure  the  cables  to  the  mounting  system  using  UV-resistant  cable  ties.  Protect  exposed  cables  from 
damage by taking appropriate precautions (e.g. placing them inside a metallic raceway like EMT    conduit). 
Avoid exposure to direct sunlight. 

 

A  minimum  bending radius of  60  mm (2.36  in)  is required  when  securing  the  junction box  cables  to  the 
racking system. 

 

Do not place connectors in locations where water could easily accumulate. 
 

Summary of Contents for CS5AH-180M

Page 1: ...ABILITY 1 2 0 SAFETY PRECAUTIONS 1 3 0 MECHANICAL ELECTRICAL SPECIFICATIONS 2 4 0 UNPACKING AND STORAGE 4 5 0 MODULE INSTALLATION 4 5 1 MODULE WIRING 7 5 2 GROUNDING 8 6 0 MOUNTING INSTRUCTIONS 8 6 1...

Page 2: ...nguage versions of this document the English version shall prevail Please refer to our product lists and documents published on our website at http www canadiansolar com as these lists are updated on...

Page 3: ...e junction box cover closed at all times Do not disassemble a module or remove any module part Do not artificially concentrate sunlight on a module Do not connect or disconnect modules when current fr...

Page 4: ...circuit voltage can be calculated using the following formula CVoc 1 Voc 25 T T is the lowest expected ambient temperature at the system installation site Voc C is the voltage temperature coefficient...

Page 5: ...n to avoid module backsheets being damaged by sharp objects as scratches may directly affect product safety Do not leave modules unsupported or unsecured Do not change the wiring of bypass diodes Keep...

Page 6: ...Temperature and humidity Please consult the Canadian Solar Inc technical support department for more information on the use of modules in special climates such as an altitude greater than 2000m Do no...

Page 7: ...en designing the system The recommended maximum series fuse rating is stated in a table in the Annex C Modules should be safely fixed to bear all expected loads including wind and snow loads A minimum...

Page 8: ...erproof when unmated When installing modules connector should be connected to each other as soon as possible or appropriate measures like using connector endcaps should be taken to avoid moisture and...

Page 9: ...less steel unless otherwise specified Canadian Solar Inc does not provide grounding hardware One grounding method is recommended for Canadian Solar Inc classic modules as described below For alternati...

Page 10: ...modules can be installed in either landscape or portrait orientations Refer to the detailed instructions for further guidance Please note that in areas with heavy snowfall 2400 Pa further countermeas...

Page 11: ...de using four standard mounting holes Mounting rails run perpendicularly to the long frame side An additional support bar should be placed below the module as shown below Maximum Load Uplift load 2400...

Page 12: ...oad 2400 Pa Downforce load 5400 Pa Compatible module types CS6XH P and CS6XH M 7 0 MAINTENANCE Do not make modifications to any component of the PV module diode junction box plug connectors or others...

Page 13: ...nadiansolar com Rev IM GN CM EN 1 0 Copyright October 2020 Canadian Solar Inc 12 performed by qualified personnel only Please refer to Annex D Module Cleaning Guide for additional information on this...

Page 14: ...as described below All the requirements of the standard module installation manual and specific tracker detailed installation instructions should apply Tracker 1P Clamping method Overlap support lengt...

Page 15: ...10 41 6 5 07 49 4 5 38 15 CS5PH 235P 235 50 8 4 63 62 6 4 93 15 1602 1061 40 1602 1061 35 20 30 CS5PH 240P 240 51 0 4 71 62 8 5 00 15 CS5PH 245P 245 51 4 4 79 63 0 5 07 15 CS5PH 250P 250 51 4 4 87 63...

Page 16: ...290 30 6 9 48 36 9 10 08 20 CS6PH 295M 295 30 9 9 55 37 1 10 14 20 CS6PH 300M 300 31 2 9 62 37 3 10 19 20 CS6PH 305M 305 31 5 9 69 37 5 10 25 20 CS6PH 310M 310 31 8 9 75 37 7 10 31 20 CS6XH 345M 345...

Page 17: ...t in injury Ensure that the array has been disconnected to other active components such as inverter or combiner boxes before starting with the cleaning Wear suitable protection clothes insulated glove...

Page 18: ...be applied as long as the method is efficient enough considering the existing conditions Method B Wet cleaning If excessive soiling is present on the module surface a non conductive brush sponge or o...

Reviews: