35
Table 8 – Firing Modes Model 2000 (Two Burners)
Burner 1
Burner 2
Two
Stages
Stage 1
Low Fire
Low Fire
Stage 2
High Fire
High Fire
Three
Stages
Stage 1
Low Fire
Low Fire
Stage 2
High Fire
Low Fire
Stage 3
High Fire
High Fire
Four
Stages
Stage 1
Low Fire
Low Fire
Stage 2
Low Fire
Low Fire
Stage 3
High Fire
Low Fire
Stage 4
High Fire
High Fire
Table 9 – Firing Modes Model 2500 and 3000 (Three Burners)
Burner 1
Burner 2
Burner 3
Two
Stages
Stage 1
Low Fire
Low Fire
Low Fire
Stage 2
High Fire
High Fire
High Fire
Three
Stages
Stage 1
Low Fire
Low Fire
Low Fire
Stage 2
High Fire
Low Fire
Low Fire
Stage 3
High Fire
High Fire
High Fire
Four
Stages
Stage 1
Low Fire
Low Fire
Low Fire
Stage 2
High Fire
Low Fire
Low Fire
Stage 3
High Fire
High Fire
Low Fire
Stage 4
High Fire
High Fire
High Fire
Table 10 – Firing Modes Model 3500 and 4000 (Four Burners)
Burner 1
Burner 2
Burner 3
Burner 4
Two
Stages
Stage 1
Low Fire
Low Fire
Low Fire
Low Fire
Stage 2
High Fire
High Fire
High Fire
High Fire
Three
Stages
Stage 1
Low Fire
Low Fire
Low Fire
Low Fire
Stage 2
High Fire
High Fire
Low Fire
Low Fire
Stage 3
High Fire
High Fire
High Fire
High Fire
Four
Stages
Stage 1
Low Fire
Low Fire
Low Fire
Low Fire
Stage 2
High Fire
High Fire
Low Fire
Low Fire
Stage 3
High Fire
High Fire
High Fire
Low Fire
Stage 4
High Fire
High Fire
High Fire
High Fire
Summary of Contents for MICOFLAME GRANDE Series
Page 2: ......
Page 4: ......
Page 20: ...16 Figure 7 Typical Heating System ...
Page 21: ...17 Figure 8 Typical Low Water Temperature System Figure 9 Typical Instantaneous Water System ...
Page 47: ...43 ...
Page 48: ...44 ...
Page 49: ...45 16 EXPLODED VIEW MicoFlame Grande ...
Page 50: ...46 EXPLODED VIEW MicoFlame Grande Outdoor and or Condensing ...