8.11
MODE 6: OUTDOOR RESET OPERATION: ADJUST DISPLAY
From the Home display;
1) Press
simultaneously to view the following parameters:
Display
Parameter
Name
Parameter Description
Parameter
Range
Mode
Operating mode for the boiler.
NOTE: A complete description of
each mode can be found in section
8.4 Modes of Operation in this
manual.
1 to 8
Default = 1
Boil Max
Maximum boiler target temperature
120 to 225
o
F
(48 to 107
o
C)
Default = 210
o
F
(99
o
C)
Pump Delay
Boiler post pump time after burner
has shut off, in seconds.
OFF, 0:20 to
9:55 min, On
Default = 1:00
min
Temperature
Units
Select the desired unit of
measurement
o
F,
o
C
Default =
o
F
8.12
MODE 7 & 8: EXTERNAL TEMPERATURE TARGET OPERATION: VIEW DISPLAY
From the Home display;
1) Press [ITEM] to view the following parameters:
Display
Parameter
Name
Parameter Description
Parameter
Range
Boiler Outlet
Temperature
Real-time Outlet Temperature to Boiler
14 to 266
o
F
(-10
to 130
o
C)
Boiler Inlet
Temperature
Real-time Inlet Temperature to Boiler
14 to 266
o
F
(-10
to 130
o
C)
Boiler Delta
T
Real-time temperature difference
between the outlet sensor and the inlet
sensor.
-99 to 252
o
F
(-72 to 140
o
C)
Summary of Contents for MICOFLAME GRANDE Series
Page 2: ......
Page 4: ......
Page 20: ...16 Figure 7 Typical Heating System ...
Page 21: ...17 Figure 8 Typical Low Water Temperature System Figure 9 Typical Instantaneous Water System ...
Page 47: ...43 ...
Page 48: ...44 ...
Page 49: ...45 16 EXPLODED VIEW MicoFlame Grande ...
Page 50: ...46 EXPLODED VIEW MicoFlame Grande Outdoor and or Condensing ...