32
Minimum On
Time
Minimum on time for each stage
0:10 to 5:00
minutes
Default = 0:30
minute
Minimum Off
Time
Minimum off time for each stage
0:10 to 5:00
minutes
Default = 0:50
minutes
Pump Delay
Boiler post pump time after burner
has shut off, in seconds.
OFF, 0:20 to 9:55
min, On
Default = 1:00
min
External
Input Signal
(Mode 8
ONLY)
Select the range for the external input
signal that adjusts the boiler target.
0:10 or 2:10
Default = 0:10
Offset (Mode
8 ONLY)
Select the amount of temperature
offset to add to the boiler target
calculated from the external input
signal.
-10
to 10
o
F
(-5
to 5
o
C)
Default = 0
o
F
Temperature
Units
Select the desired unit of
measurement
o
F,
o
C
Default =
o
F