24
Minimum Off
Time
Minimum off time for each stage
0:10 to 5:00
minutes
Default = 0:50
minutes
Pump Delay
Boiler post pump time after
burner has shut off, in seconds.
OFF, 0:20 to
9:55 min, On
Default = 1:00
min
Temperature
Units
Select the desired unit of
measurement
o
F,
o
C
Default =
o
F
8.6
MODE 3: SETPOINT OPERATION: VIEW DISPLAY
From the Home display;
1) Press [ITEM] to view the following parameters:
Display
Parameter
Name
Parameter Description
Parameter
Range
Boiler Outlet
Temperature
Real-time Outlet Temperature to Boiler
14 to 266
o
F
(-10
to 130
o
C)
Boiler Inlet
Temperature
Real-time Inlet Temperature to Boiler
14 to 266
o
F
(-10
to 130
o
C)
Boiler Delta
T
Real-time temperature difference
between the outlet sensor and the inlet
sensor.
-99 to 252
o
F
(-72 to 140
o
C)
Tank
Temperature
Real-time Tank Temperature to Boiler
14 to 266
o
F
(-10
to 130
o
C)
Total Run
Time Since
Installation
Monitors the amount of operational
time since the unit was installed. The
two digits are the thousands of hours
and the three digit display shows the
hundreds of hours.
Press
simultaneously to reset
the counter
Alternates
between 00 and
999
Summary of Contents for MICOFLAME GRANDE Series
Page 2: ......
Page 4: ......
Page 20: ...16 Figure 7 Typical Heating System ...
Page 21: ...17 Figure 8 Typical Low Water Temperature System Figure 9 Typical Instantaneous Water System ...
Page 47: ...43 ...
Page 48: ...44 ...
Page 49: ...45 16 EXPLODED VIEW MicoFlame Grande ...
Page 50: ...46 EXPLODED VIEW MicoFlame Grande Outdoor and or Condensing ...