CPS-i3000(R2) MANUAL
Camtec Power Supplies GmbH - Gewerbestrasse 30 - DE-76327 Pfinztal / Germany
P.14/22 (04/2016.01.5)
Tel. +49 (721) 46596 - 0 Fax +49 (721) 46596 - 77
www.camtec-gmbh.com
-
(Subject to alterations. This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death)
C/V Chart and Operating Point
The output voltage set Vout is always linear proportional to the control signal
Ureg.
The desired control signal is selected via the DIP switcher:
0-5V, 0-10V, 0-20mA oder 4-20mA.
Model
Value UA1 (V)
Value IA1 (A)
Value UA2 (V)
Value IA2 (A)
Pmax (IA1/IA2)
CPS-i3000.018
18Vdc
150A
14,4Vdc
185A
2700/2664W
CPS-i3000.030
30Vdc
100A
24Vdc
125A
3000/3000W
CPS-i3000.060
60Vdc
50A
48Vdc
62,5A
3000/3000W
CPS-i3000.090
90Vdc
33,3A
72Vdc
41,5A
2997/2988W
CPS-i3000.150
150Vdc
20A
120Vdc
25A
3000/3000W
CPS-i3000.300
300Vdc
10A
240Vdc
12,5A
3000/3000W
Inrush Current Limiter (electronic)
The power supply unit has an electronic current
limiter (230Vac=14,6A
rms
/20,7A
peak
).
It is a precisely working circuit instead of a usual
simple NTC solution. The accuracy is ±10%,
regardless of the operating temperature and the
duty cycles (interval
≥
10s). We recommend the
smallest circuit breaker a characteristic B with 25A.
Temperature Monitoring & Derating
The maximum ambient temperature during
operation is + 60°C. If the overtemperature
protection is activated, the power supply but
not the fan is switched off.
The measuring point is 50mm outside the
power supply at the front side (fan/blower
input). The power supply unit starts
automatically when it has cooled down.