CPS-EC1500(R2) MANUAL

                 

Camtec Power Supplies GmbH  -  Gewerbestrasse 30  -  76327 Pfinztal  -  Germany      

P.13/13 (01/2017-02-1)

 

Phone +49(721)46596-0  -   Fax +49(721)46596-77  -   

www.camtec-gmbh.com

 - 

[email protected]

 

(Subject to alterations. This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death) 

 
 

Safety regulations: Please read these instructions completely before using the equipment. Keep these 
instructions on to hand. The device may only be operated by trained specialist staff. 

 

Installation: 

1) The device is designed for devices and systems 
that meet the standard requirements for hazardous 
voltages, power, and fire prevention. 
2.) Installation and service only by trained persons. 
The AC power must be switched off. The work is to be 
labelled; accidental reconnection of the system must 
be prevented. 
3.) Opening the device, its modification, loosening 
bolts, or operation outside the specified herein 
specification or in an unsuitable environment, has the 
immediate loss of warranty to follow. We disclaim any 
responsibility for any resulting damage to persons or 
things. 
4.) Note: The device must not be operated without an 
upstream circuit breaker (CB). We recommend the use 
of B-Type 16A. It is prohibited to use the unit without 
PE. It may be necessary upstream device has a power 
switch. 

 

Warning

Non-compliance these warnings can result in fire 
and serious injury or death.

 

1. Never operate device

 

without PE connection. 

2. Before connecting the device to the AC 
network, make wires free of voltage and assure 
accidentally switch on. 
3. Allow neat and professional cabling. 
4. Never open nor try to repair the unit. Inside 
are dangerous voltages that can cause electrical 
shock hazard. 
5. Avoid metal pieces or other conductive 
material to fall into the item

 

6. Do not operate the device in damp or wet 
conditions 
7. Do not operate the unit under EX-conditions 

 
 
 
 
 

All parameters base on 15 minutes run-in @ full load / 25°C / 230Vac 50/60Hz, as otherwise stated. 

Summary of Contents for CPS-EC1500

Page 1: ... 2V per load line Electronic inrush current limiter 20 7Apeak Inhibit function Interlock External shutdown Boost Charge Mode Precise dynamic response to load change Designed for long life under full stress Strong input filters Hold up time 20ms High reliability shock vibration proof Overload and short circuit protection Efficiency up to 94 EMI EMS EN61000 6 2 3 EN55032 EN61010 1 EN61010 2 201 EN62...

Page 2: ...per margin is 0 5 The tolerance of the lower margin is 5 0 Output Current Monitoring The CPS EC power supply features a 0 5Vdc signal output It is a real time linear signal and indicates the current consumption of the load The measuring point is directly at the output connection of the device Boost Charge Mode The CPS EC1500 offers a boost charge mode The defined current limiting can be triggered ...

Page 3: ...0Vac Inhibit Function Interlock Yes protective forced isolation to the inputs and the output 3000Vac Derating 60 C 70 C 2 5 C Accuracy 1 5 interface Load Regulation 0 05 0 100 Start up from Shutdown Typ 420ms Start up from Inhibit Typ 420ms Response to Load Change 1ms 10 100 100 10 Base Load None required open circuit proof Efficiency 230Vac 92 94 at 90 load Short Circuit Protection Continuous Ope...

Page 4: ...ne AWG22 AWG6 0 25 1 5mm Sense Aux 3000Vac to input Boost Charge Open Collector AWG22 AWG6 0 25 1 5mm BC 3000Vac to input output Power Good Relay b contact AWG22 AWG6 0 25 1 5mm DC OK 3000Vac to input output can also be used with a simple passive switch All potentiometers and all the inputs and the outputs of the analogue interface provide a forced isolation It is to ensure a protective isolation ...

Page 5: ...cause damages to the power supply unit To basically prevent from interferences enable to twist sense compensation lines To reduce inductive influences make sure that the load wires are installed close to each other Driving a pulsative load requires a large electrolytic and a ceramic capacitor Make sure that C1 C2 are not oscillating with load wires It would cause ripple voltage into the load lines...

Page 6: ...ment range of the CPS EC series up to 400Vdc If the DC voltage is ok the relay is closed if the power supply unit is in false operation in the shutdown or in the inhibit mode the relay is open Considering the lower and the upper margin of the AC voltage detection it is to say that the CPS EC series starts at 150Vac The unit starts with 210Vdc when a DC voltage applies to the input The below table ...

Page 7: ...argin the output voltage drops down and the unit delivers constant current Similar is when the upper margin of the voltage allows the current to be dropped by the power reduction behavior of the CPS EC series The C V setting must meet the Pmax 1500W Model Value UA1 V Value IA1 A Value UA2 V Value IA2 A Pmax CPS EC1500 024 30 50 0 24 62 5 1500 1500W CPS EC1500 036 45 33 3 36 41 7 1500 1501W CPS EC1...

Page 8: ...8 1 The CPS EC1500 models are to be operated with floating output when connected in series Such the output terminals must not be connected to earth GND PE Due to the dielectric strength of the internal components used only the models with an output voltage of 90Vdc and later are approved for series operation Other power supplies are not approved for series operation above 60Vdc If the units are re...

Page 9: ...test equipment raising the voltage slowly b Short circuit L1 and N and all the DC output terminals c Use only test voltages of 50 60Hz The outputs are unearthed and therefore they have no resistance to GND PE d If the residual voltage is 60Vdc observe the safety standards Use only specially insulated screwdriver to trim the Ua Ia Connections AC Main Input PE wire N wire L wire DC Mains DC voltage ...

Page 10: ...t in injury or death Mechanics Mechanics Stable metal aluminum housing IP20 To allow adequate convection a free air space of 50mm top bottom and 5mm sidewalls is required for active devices 15mm space from the sidewalls For free air convection it is necessary to install the unit horizontal Use the DIN Rail installation equipped standard with the patented 35mm DIN Rail brackets according to EN60275...

Page 11: ...and for active devices 15mm space from the sidewalls For proper air convection it is necessary to install the CPS EC1500 One can use the DIN Rail installation equipped standard with our patented 35mm DIN Rail bracket according to EN60275 It is easy to mount dismount while snaping it onto the 35mm DIN Rail no tools necessary A wall mount back plate option is available too It is not allowed to insta...

Page 12: ... 46228 pt 1 min max 2 5 10mm 0 2 1 5mm Plug gauge in accordance with EN 60999 a x b ø 5 4 x 5 1mm 5 3mm 2 4 x 1 5mm 2 3mm Pitch P 10 16mm 3 5mm Wire Stripping Length fine wired Nominal Cross Section Wire End Ferrule Stripping Length Wire End Ferrule Stripping Length 0 25mm H0 25 5 5mm H0 25 10 HBL 8mm 0 5mm H0 5 6 6mm H0 5 12 OR 8mm 1 0mm H1 0 6 6mm H1 0 12 GE 8mm 2 5mm H2 5 12 12mm H2 5 19D BL 14...

Page 13: ...ication loosening bolts or operation outside the specified herein specification or in an unsuitable environment has the immediate loss of warranty to follow We disclaim any responsibility for any resulting damage to persons or things 4 Note The device must not be operated without an upstream circuit breaker CB We recommend the use of B Type 16A It is prohibited to use the unit without PE It may be...