Shutdown 

All CPS-EC units are featured with an external shutdown (switch/open collector).  
When the connection is open the power-supply operates. When the  
connection is closed the power supply goes into a standby mode  
(short-circuited). The power supply powers up as soon as the shutdown 
connections is opened. The signal through the connections is 1Vdc max. . The 
shutdown connections have an internal pull-up resistor with 4700 

Ω

 at the plus 

line (max. +12V inserted). 

 

Boost Charge 

The CPS-EC1500 features a boost charge mode (switch/open collector). When 
the connection is open the power-supply operates the set current. When it is 
closed (short-circuited) the power supply de10% current boost. The overall 
power of 1500W cannot be exceeded. The boost charge is no power-boost, and it 
is recommended to set the current limiting to 

90%.The factory set is 100%. 

The  boost  charge  releases  as  soon  as  the  connection  is  opened.  The  signal 
through  the  connection  is  1Vdc  max.  .  The  boost  charge  connections  have  an 
internal pull-up resistor with 4700 

Ω

 at the plus line (max. +12V inserted). 

 

DC-OK (Power Good Relay) 

The DC ok relay indicates if the output voltage is low and if the AC voltage is low. 
The contact is galvanic insulated to the AC input and the DC output connections. 
The isolation is 3000Vac with a forced isolation and covers the overall adjustment 
range of the CPS-EC series up to 400Vdc. If the DC voltage is ok the relay is 
closed, if the power supply unit is in false operation, in the shutdown or in the 
inhibit mode, the relay is open. Considering the lower and the upper margin of the 
AC voltage detection it is to say that the CPS-EC series starts at 150Vac. The unit 
starts with 210Vdc when a DC voltage applies to the input.  
 
The below table of values shows the hysteresis of the lower and upper threshold 
margins where the DC OK Relay indicates a low voltage. The nominal voltage of the cell voltage of a typical 
lead acid battery VRLA & vented GEL & AGM is listed (OPsZ, OPzS, OPzV, OGi, OGiV, GiV types). 
WARNING!

 

Regarding the DC-output voltage setting range it is important to consider that this data sheet shows 

the guaranteed values. In practice the range will be wider and with some models the lower margin of the setting 
range will be below the DC ok high margin of the DC-ok relay. Make sure that the output voltage setting will 
properly stay above the DC ok high margin to avoid false messages from the relay. ^ 
 

Hysteresis & Threshold Margins 

Model 

Nominal [V] 

DC ok low 

DC ok 
high 

No. of Cells 

Nominal Cell [V] 

Input ok low 

Input ok high 

CPS-EC1500.024  24V 

21,6Vdc 

22,8Vdc 

12 

26,76 – 28,80Vdc 

140Vac 
175Vdc 

150Vac 
210Vdc 
 
(the power 
supply unit starts 
at 
150Vac/210Vdc) 

CPS-EC1500.036  36V 

32,4Vdc 

34,2Vdc 

18 

40,14 – 43,20Vdc 

CPS-EC1500.048  48V 

43,2Vdc 

45,6Vdc 

24 

53,52 – 57,60Vdc 

CPS-EC1500.060  60V 

54,0Vdc 

57,0Vdc 

30 

66,90 – 72,00Vdc 

CPS-EC1500.072  72V 

64,8Vdc 

68,4Vdc 

36 

80,28 – 86,40Vdc 

CPS-EC1500.110  110V 

99,0Vdc 

104,5Vdc 

54 

120,42 – 129,60Vdc 

CPS-EC1500.150  150V 

118,8Vdc 

125,4Vdc 

CPS-EC1500.220  220V 

198,0Vdc 

209,0Vdc 

108 

240,84 – 259,20Vdc 

CPS-EC1500.400  400V 

297,0Vdc 

313,5Vdc 

165 

367,95 – 396,00Vdc 

DC OK Indication 

Power Supply Status 

Normal 

Low [V] 

Over Temperature 

Shut Down Closed 

Inhibit Open 

Relay Operation status 

Closed 

Open 

Open 

Open 

Open 

 

 

+12V 

+12V 

Summary of Contents for CPS-EC1500

Page 1: ... 2V per load line Electronic inrush current limiter 20 7Apeak Inhibit function Interlock External shutdown Boost Charge Mode Precise dynamic response to load change Designed for long life under full stress Strong input filters Hold up time 20ms High reliability shock vibration proof Overload and short circuit protection Efficiency up to 94 EMI EMS EN61000 6 2 3 EN55032 EN61010 1 EN61010 2 201 EN62...

Page 2: ...per margin is 0 5 The tolerance of the lower margin is 5 0 Output Current Monitoring The CPS EC power supply features a 0 5Vdc signal output It is a real time linear signal and indicates the current consumption of the load The measuring point is directly at the output connection of the device Boost Charge Mode The CPS EC1500 offers a boost charge mode The defined current limiting can be triggered ...

Page 3: ...0Vac Inhibit Function Interlock Yes protective forced isolation to the inputs and the output 3000Vac Derating 60 C 70 C 2 5 C Accuracy 1 5 interface Load Regulation 0 05 0 100 Start up from Shutdown Typ 420ms Start up from Inhibit Typ 420ms Response to Load Change 1ms 10 100 100 10 Base Load None required open circuit proof Efficiency 230Vac 92 94 at 90 load Short Circuit Protection Continuous Ope...

Page 4: ...ne AWG22 AWG6 0 25 1 5mm Sense Aux 3000Vac to input Boost Charge Open Collector AWG22 AWG6 0 25 1 5mm BC 3000Vac to input output Power Good Relay b contact AWG22 AWG6 0 25 1 5mm DC OK 3000Vac to input output can also be used with a simple passive switch All potentiometers and all the inputs and the outputs of the analogue interface provide a forced isolation It is to ensure a protective isolation ...

Page 5: ...cause damages to the power supply unit To basically prevent from interferences enable to twist sense compensation lines To reduce inductive influences make sure that the load wires are installed close to each other Driving a pulsative load requires a large electrolytic and a ceramic capacitor Make sure that C1 C2 are not oscillating with load wires It would cause ripple voltage into the load lines...

Page 6: ...ment range of the CPS EC series up to 400Vdc If the DC voltage is ok the relay is closed if the power supply unit is in false operation in the shutdown or in the inhibit mode the relay is open Considering the lower and the upper margin of the AC voltage detection it is to say that the CPS EC series starts at 150Vac The unit starts with 210Vdc when a DC voltage applies to the input The below table ...

Page 7: ...argin the output voltage drops down and the unit delivers constant current Similar is when the upper margin of the voltage allows the current to be dropped by the power reduction behavior of the CPS EC series The C V setting must meet the Pmax 1500W Model Value UA1 V Value IA1 A Value UA2 V Value IA2 A Pmax CPS EC1500 024 30 50 0 24 62 5 1500 1500W CPS EC1500 036 45 33 3 36 41 7 1500 1501W CPS EC1...

Page 8: ...8 1 The CPS EC1500 models are to be operated with floating output when connected in series Such the output terminals must not be connected to earth GND PE Due to the dielectric strength of the internal components used only the models with an output voltage of 90Vdc and later are approved for series operation Other power supplies are not approved for series operation above 60Vdc If the units are re...

Page 9: ...test equipment raising the voltage slowly b Short circuit L1 and N and all the DC output terminals c Use only test voltages of 50 60Hz The outputs are unearthed and therefore they have no resistance to GND PE d If the residual voltage is 60Vdc observe the safety standards Use only specially insulated screwdriver to trim the Ua Ia Connections AC Main Input PE wire N wire L wire DC Mains DC voltage ...

Page 10: ...t in injury or death Mechanics Mechanics Stable metal aluminum housing IP20 To allow adequate convection a free air space of 50mm top bottom and 5mm sidewalls is required for active devices 15mm space from the sidewalls For free air convection it is necessary to install the unit horizontal Use the DIN Rail installation equipped standard with the patented 35mm DIN Rail brackets according to EN60275...

Page 11: ...and for active devices 15mm space from the sidewalls For proper air convection it is necessary to install the CPS EC1500 One can use the DIN Rail installation equipped standard with our patented 35mm DIN Rail bracket according to EN60275 It is easy to mount dismount while snaping it onto the 35mm DIN Rail no tools necessary A wall mount back plate option is available too It is not allowed to insta...

Page 12: ... 46228 pt 1 min max 2 5 10mm 0 2 1 5mm Plug gauge in accordance with EN 60999 a x b ø 5 4 x 5 1mm 5 3mm 2 4 x 1 5mm 2 3mm Pitch P 10 16mm 3 5mm Wire Stripping Length fine wired Nominal Cross Section Wire End Ferrule Stripping Length Wire End Ferrule Stripping Length 0 25mm H0 25 5 5mm H0 25 10 HBL 8mm 0 5mm H0 5 6 6mm H0 5 12 OR 8mm 1 0mm H1 0 6 6mm H1 0 12 GE 8mm 2 5mm H2 5 12 12mm H2 5 19D BL 14...

Page 13: ...ication loosening bolts or operation outside the specified herein specification or in an unsuitable environment has the immediate loss of warranty to follow We disclaim any responsibility for any resulting damage to persons or things 4 Note The device must not be operated without an upstream circuit breaker CB We recommend the use of B Type 16A It is prohibited to use the unit without PE It may be...

Reviews: