![Campbell CS650 User Manual Download Page 23](http://html1.mh-extra.com/html/campbell/cs650/cs650_user-manual_3864678023.webp)
User Manual
11
shows the SDI-12 wiring for the CS650 water content reflectometer.
SDI-12 data is transmitted to a CRBasic datalogger odd numbered control port or
U terminal. Wiring information for RS-232 communications is provided in
Section
Table 7-1. CS650 Wiring Code for SDI-12
Colour
Function
Datalogger Connection
Green
SDI-12 Data
SDI-12 Input, Control Port,
or U* configured for SDI-12
measurement
Red
SDI-12 Power
12 V
Black
SDI-12 Reference
G
Clear
Shield
G
Orange
Not Used
G
The orange Rx wire is only used for RS-232 Tx/Rx communication,
and should be grounded when using SDI-12.
7.4
Programming
Short Cut
is the best source for up-to-date datalogger programming code.
Programming code is needed,
when creating a program for a new datalogger installation
when adding sensors to an existing datalogger program
If your data acquisition requirements are simple, you can probably create and
maintain a datalogger program exclusively with
Short Cut
. If your data
acquisition needs are more complex, the files that
Short Cut
creates are a great
source for programming code to start a new program or add to an existing custom
program.
Short Cut
cannot edit programs after they are imported and edited in
CRBasic Editor
.
A
Short Cut
tutorial is available in Section
. If you wish to
import
Short Cut
code into
CRBasic Editor
to create or add to a customized
program, follow the procedure in Appendix
Importing Short Cut Code into a
. Programming basics for CRBasic dataloggers are
provided here. Complete program examples for select CRBasic dataloggers can
be found in Appendix
. Programming basics and
programming examples for Edlog dataloggers are provided at
www.campbellsci.com\old-manuals
The
SDI12Recorder()
measurement instruction programs CRBasic dataloggers
(CR6, CR200(X)-series, CR800-series, CR1000, CR3000, and CR5000) to
measure the sensor. This instruction sends a request to the sensor to make a
measurement and then retrieves the measurement from the sensor. See Section
, for more information.
When using a CR200(X), the
SDI12Recorder()
instruction has the following
syntax:
NOTE