Appendix D. SDI-12 Sensor Support
D-4
D.2.2 CR200(X) Series Datalogger Example
1.
Connect a single CS650 to the datalogger as follows:
Green to Control Port C1/SDI12
Black, Orange, Clear to G
Red to B
2.
In the
LoggerNet Connect
screen navigate to the Datalogger menu and select
Terminal Emulator. The “Terminal Emulator” window will open. In the
Select Device menu, located in the lower left-hand side of the window, select
the CR200Series station.
3.
Click on the Open Terminal button.
4.
Press the <enter> key until the datalogger responds with the “
CR2XX>
”
prompt. At the “
CR2XX>
” prompt, make sure the All Caps Mode box is
checked and enter the command
SDI12
<enter>. The response “SDI12>”
indicates that the CS650 is ready to accept SDI-12 commands.
5.
To query the CS650 for its current SDI-12 address, key in
?!
<enter> and the
CS650 will respond with its SDI-12 address. If no characters are typed within
60 seconds, then the mode is exited. In that case, simply enter the command
SDI12 again and press <enter>.
Figure D-1. SDI-12 transparent mode on CR200(X)-series datalogger using
control port C1/SDI12 and changing SDI-12 address from 0 to 1
6.
To change the SDI-12 address, key in
aAb!<enter>
where
a
is the current
address from the above step and
b
is the new address. The CS650 will change
its address and the datalogger will respond with the new address. To exit
SDI-12 transparent mode select the Close Terminal button.