FIGURE 6-4. Battery family list
Set the Battery Family to match the battery family being used. The default settings are Battery
Capacity of zero (0) and Battery Family of EnerSys/Genesis NP Series. Setting the Battery Capacity
to zero (0) forces the charger to only float charge the battery. Battery Capacity must be changed
to allow cycle charging.
(p. 17) shows the default settings for each battery family. The
settings are based on the following equation:
V
charge
(T) = C
0
+ C
1
(T-25°C) + C
2
(T-25°C)
2
Where:
T = Battery temperature in ° C.
C
2
= 0 for linear charge voltage vs. temperature relation.
CH201 12V Charging Regulator
16
Summary of Contents for CH201
Page 1: ...06 2020 Copyright 2020 Campbell Scientific CSL I D 1352 ...
Page 2: ......
Page 4: ......
Page 6: ......
Page 8: ......
Page 10: ...Appendix A Downloading an operating system 31 Table of Contents ii ...
Page 42: ...FIGURE A 1 Downloading a new operating system CH201 12V Charging Regulator 32 ...
Page 43: ......