9
Operating Instructions
Transducer for AC voltage SINEAX U 553
Safety precautions to be strictly observed are marked
with following symbols in the Operating Instructions:
Contents
1. Read first and then … ................................................ 9
2. Brief description .......................................................... 9
3. Technical data ............................................................. 9
4. Mounting ................................................................... 10
5. Electrical connections ............................................... 10
6. Adjustable measuring range by DC calibration ......... 11
7. Commissioning and maintenance ............................. 11
8. Releasing the transducer .......................................... 11
9. Instruments admissions ............................................ 11
10. Dimensional drawing ................................................. 12
11. Declaration of conformity .......................................... 12
1. Read first and then …
The proper and safe operation of the device
assumes that the Operating Instructions is
read carefully
and the safety warnings given
in the various Sections
4. Mounting
5. Electrical connections
6. Adjustable measuring range
by DC calibration
are
observed
.
The device should only be handled by appropriately trained
personnel who are familiar with it and authorised to work
in electrical installations.
Unauthorized repair or alteration of the unit invalidates
the warranty.
2. Brief description
The SINEAX U 553 measuring transducer is used to convert
a sine-wave or distorted AC voltage.
The output signal, in the form of a
load independent
DC
current or voltage, is proportional to the measured value.
3. Technical data
Measuring input
Nominal frequency:
50/60 or 400 Hz
Nominal input
voltage:
0 - 20 to 0 - 690 V
Measuring output
DC current:
0(0.2) - 1 to 0(4) - 20 mA
Burden voltage:
15 V
R
ext
max. [k
Ω
]
≤
15 V
I
AN
[mA]
I
AN
= Full output value
DC voltage:
0(0.2) - 1 to 0(2) - 10 V
R
ext
[k
Ω
] min.
≥
U
A
[V]
2 mA
Response time:
50 or 300 ms
Power supply
AC/DC power pack (DC or 40 - 400 Hz)
Rated voltage
Tolerance
85 - 230 V DC / AC
DC – 15 to + 33%
AC ± 15%
24 - 60 V DC / AC
Power consumption:
≤
1.5 W resp.
≤
3 VA
Options
Connected to the low
tension terminal side:
24 V AC or 24 - 60 V DC,
see Fig. 3
Power supply from
measuring input
(self powered):
≥
24 - 60 V AC or 85 - 230 V AC,
see Fig 4
Please note the max. and min. measuring input
voltage!
Type label
inscription
Input voltage
range
= internal power
supply range
Tolerance
Power
supply
connection
Self powered
by 1/2
(int. 24-60 V)
24 - 60 V AC
± 15%
Internal
measuring
input
Self powered
by 1/2
(int. 85-230 V)
85 - 230 V AC
Accuracy
(acc. to IEC 60 688)
Reference value:
Output end value
Basic accuracy:
Class 0.5
Safety
Pollution degree:
2
Installation category: III
Environmental conditions
Operating temperature: – 10 to + 55 °C
Storage temperature: – 40 to + 70 °C
Relative humidity of
annual mean:
≤
75%
Altitude:
2000 m max.
Indoor use statement!
External resistance:
External resistance: