10.3 Connecting the power supply leads
Connect the power supply leads to terminals 5 (
) and
10 (
).
A two-pole switch must be included in the supply connection
where facility for switching SINEAX TV 808 off is desired.
Note:
An external supply fuse must be provided for DC
supply voltages > 125 V.
11. Confi guration
The SINEAX TV 808 unit has to be opened before it can be
confi gured (see Section “8. Withdrawing and inserting the
device”).
11.1 Standard input ranges
Soldered jumpers are provided for the coarse setting of the
input ranges and the fi ne adjustment is accomplished using
the potentiometers “Zero” and “Span”.
100 must be added to the designations of the soldered jumpers
in the table for channel 1 and 200 for channel 2.
Example:
Input range for input 1 and input 2 = 0…20 mA.
Jumpers 1, 5, 6 and 11 must be inserted for this range.
– The corresponding jumpers for channel 1 are B101, B105,
B106 and B111.
– The corresponding jumpers for channel 2 are B201, B205,
B206 and B211).
Current [mA]
Soldered jumpers
0 … 0.1
1, 3 7, 10, 11
0 … 0.2
1, 3 8, 11
0 … 0.5
1, 4 9, 10, 11
0 … 1
1, 4 7, 10, 11
0 … 2
1, 4 8, 11
0 … 5
1, 5 6, 7, 8, 10, 11
0 … 10
1, 5 10, 11
0 … 20
1, 5 6, 11
0.2 … 1
1, 4 8, 10, 11
12, 15
1 … 5
1, 4 6, 9
12, 15
2 … 10
1, 5 6, 7, 10, 11
12, 15
4 … 20
1, 5 6, 7, 8, 11
12, 15
– 0.1 … 0 … + 0.1
1, 3 8, 11
13, 14, 16
– 0.2 … 0 … + 0.2
1, 3 7, 9
13, 14, 16
– 0.5 … 0 … + 0.5
1, 4 7, 10, 11
13, 14, 16
– 1 … 0 … + 1
1, 4 8, 11
13, 14, 16
– 2 … 0 … + 2
1, 4 6, 9
13, 14, 16
– 5 … 0 … + 5
1, 5 10, 11
13, 14, 16
– 10 … 0 … + 10
1, 5 6, 11
13, 14, 16
– 20 … 0 … + 20
1, 5 6, 7
13, 14, 16
Voltage [V]
Soldered jumpers
0 … 0.06
6, 9, 10, 11
0 … 0.1
7, 8, 10, 11
0 … 0.2
6, 8, 9, 11
0 … 0.5
6, 7, 8, 9, 10
0 … 1
2
6, 7, 8, 10, 11
0 … 2
2
7, 8, 9, 11
0 … 5
2
8, 10
0 … 10
1
10, 11
0 … 20
1
6, 11
0 … 40
1
8
0.2 … 1
2
9, 10, 11
12, 15
1 … 5
2
6, 8, 9, 10
12, 15
2 … 10
1
6, 7, 10, 11
12, 15
4 … 20
1
6, 7, 8, 11
12, 15
– 0.1 … 0 … + 0.1
6, 8, 9, 11
13, 14, 16
– 0.2 … 0 … + 0.2
6, 7, 9, 10
13, 14, 16
– 0.5 … 0 … + 0.5
2
7, 8, 10, 11
13, 14, 16
– 1 … 0 … + 1
2
7, 8, 9, 11
13, 14, 16
– 2 … 0 … + 2
2
6, 8, 9, 10
13, 14, 16
– 5 … 0 … + 5
1
10, 11
13, 14, 16
– 10 … 0 … + 10
1
6, 11
13, 14, 16
– 20 … 0 … + 20
1
8
13, 14, 16
11.2 Standard output ranges
Soldered jumpers are provided for the coarse setting of the
output ranges and the fi ne adjustment is accomplished using
the potentiometers “Zero” and “Span”.
Current
[mA]
Soldered jumpers
Voltage
[V]
Soldered jumpers
Channel
1
Channel
2
Channel
1
Channel
2
0 … 20
B120
B220
0 … 20
B120
B122
B123
B220
B222
B223
4 … 20
B121
B221
2 … 10
B121
B122
B123
B221
B222
B223
± 20
–––
–––
± 10
B122
B123
B222
B223
11.3 Specifi c user output ranges
Units that have been confi gured for a specifi c user output
range cannot be subsequently reconfi gured.
B21
2
B21
3
B21
4
B21
5
B21
6
B21
7
B207
B208
B209
B210
B211
B201
B202
B203
B204
B205
B221
B220
B122
B123
B113
B114
B115
B116
B117
B107
B108
B109
B110
B111
B101
B102
B103
B104
B105
B206
B106
Span 1
Zero 1
Span 2
Zero 2
B121
B120
B223
B222
B112
Fig. 8. Position of the soldered jumpers B…, potentiometer “Zero”
and “Span”.