Advanced Graphic Data Manager
Technical data
137
10.5
Performance characteristics
10.5.1
Reference operating conditions
Ambient temperature: 25 °C ±5 K (77 °F ±9 °F)
Air humidity: 55% ±10% r.h.
10.5.2
Maximum measured error
See Input, see Section 10.1.1
10.5.3
Temperature drift
Cu50, Cu53, Cu100, Pt46 and Pt50: max. ±0.02%/K (of measuring range)
All other ranges: max. ±0.01%/K (of measuring range)
10.5.4
Long-term drift
To IEC 61298-2: max. ±0.1%/year (of measuring range)
10.6
Installation
10.6.1
Orientation
Operating position as per DIN 16 257, NL 90 ±30°
10.6.2
Installation instructions
(Panel mounting, see Section 3)
• Installation depth without terminal cover: approx. 158 mm (6.22") (incl. terminals and fastening
clips)
• Installation depth with terminal cover: approx. 197 mm (7,76")
• Panel cutout: 138
+1
x 138
+1
mm (5.43
+0.04
x 5.43
+0.04
")
• Panel thickness: 2 to 40 mm (0.08 to 1.58")
• Max. viewing angle range: from the display central axis 50° in all directions
• Securing to DIN 43 834
10.7
Environment
10.7.1
Ambient temperature range
-10 to 50 °C (14 to 122 °F)
10.7.2
Storage temperature
-20 to +60 °C (-4 to 140 °F)
10.7.3
Climate class
To IEC 60654-1: B1
10.7.4
Degree of protection
Front-panel IP65 (IEC 60529, Cat. 2) NEMA 4
Rear-panel IP20 (IEC 60529, Cat. 2)