Advanced Graphic Data Manager
Commissioning and use during operation
75
Set point
Counter alarm set point in the engineering units set up, e.g. m, piece, ... .
37035/000 to
37035/099
Hysteresis type
Only for the "Upper or lower set
point" type
"Percentual":
set hysteresis in %.
"Absolute": enter hysteresis in the preset engineering unit (e.g. °C, bar,
etc.)
37040/000 to
37040/099
Hysteresis (%)
Only for "Percentual" hysteresis
type
The alarm condition is only canceled when the signal has changed into
the normal operation range by the preset value.
Factory setting: 1.0%
37045/000 to
37045/099
Hysteresis (abs.)
Only for "Absolute" hysteresis
type
The alarm condition is only canceled when the signal has changed into
the normal operation range by the preset value.
Factory setting: 0.0
37050/000 to
37050/099
Time delay in
Configure the engineering unit for entering the time delay.
Picklist:
seconds
, minutes, hours
37054/000 to
37054/099
Time delay
In order to be interpreted as an alarm the signal must exceed or undercut
the preset value by at least the time set up.
User input:
0
to 999
37055/000 to
37055/099
Switches relay
Switches the respective relay in alarm condition. The terminal numbers
are shown in brackets.
Picklist:
not used
, relay x (xx-xx)
Note:
If there are several reasons for triggering a relay (e.g. 2 different
limit values), this must be set to "Collective relay" under "Setup ->
Outputs -> Relay -> Relay x".
37060/000 to
37060/099
LV messages
"Do not acknowledge"
: the tag name is highlighted in red to signal an
alarm condition (no message is output).
"Acknowledge": in the event of an alarm, a message is also displayed and
this message has to be acknowledged.
Note:
The screensaver is automatically disabled in the event of a limit
value message!
37065/000 to
37065/099
Save event
Stores a message in the event log on limit value violation.
Picklist: no,
yes
37070/000 to
37070/099
Event text LV on
If the limit value is violated, this text (including date and time) is shown
on the display and stored in the event log. Only available when "LV
messages" is set to "Acknowledge" or "Save event" is set to "Yes". If no
text is entered, the unit generates its own text (e.g. Analog 1 >100%).
22-character entry.
37075/000 to
37075/099
Event text LV off
The same as "Event text LV on", but on return from alarm to normal
condition. 22-character entry.
37080/000 to
37080/099
Record duration of LV on
The duration of the limit value violation can be recorded. The duration
is appended to the limit value "Off" event text (format:
<hhhh>h<mm>:<ss>). Times when the power has failed do not affect
the duration. If the limit value was violated before the power failure and
is still violated when the power is restored, the duration continues to be
counted.
Picklist:
no
, yes
37085/000 to
37085/099
"Application"
menu items
Configurable parameters
(factory settings are highlighted in bold)