Advanced Graphic Data Manager
Commissioning and use during operation
67
Totalization
Using the totalization function, the volume (in m) can be calculated from
an analog signal (e.g. flow in m/h). Picklist:
no
, yes
34000/000 to
34000/007
Totalization base
Select the corresponding time base. Example: ml/s –> time base seconds
(s); m/h –> time base hours (h).
Picklist:
second (s)
, minutes (min), hour (h), day (d)
34005/000 to
34005/007
Total. eng. unit
Here, enter the unit for the volume determined by totalization (e.g. "m").
34010/000 to
34010/007
Low flow cut off
Specify how the device should execute low flow cut off.
Picklist:
area around zero point
, absolute value
34015/000 to
34015/007
Low flow cut off
Analog values that are lower than the set threshold value (absolute value)
are not integrated ("low flow cut off") User input: 6-digit; factory setting:
0
34020/000 to
34020/007
Calc. factor
Factor for converting the integrated value (e.g. the transmitter returns l/s
–> integration base = second –> desired unit is m –> enter 0.001 as the
factor).
34025/000 to
34025/007
Totalizer:
Initial setting for the totalizer. Useful when continuing
measurements recorded to date with an (electro)-mechanical counter.
Factory setting:
0
34035/000 to
34035/039
Submenu: Fault mode
Only in the Expert setup
Settings that specify how this channel behaves in the event of a fault (e.g.
if an input channel has a cable open circuit or the system tries to divide by
0).
In the event of an error
Specify the value/status the unit continues to work with if the result of the
calculation is invalid.
Picklist: last valid value, range start, meas. range end, zero, LOW, HIGH,
free configuration,
value is invalid
Note:
The picklist entries depend on the "The result is" option.
35000/000 to
35000/007
Error value
(Only if "In event of an error - free configuration" is selected.)
The unit continues calculating with this value if a fault occurs. See table
Page 58
35005/000 to
35005/007
Fault switches
Switches the selected relay under fault conditions. The terminal numbers
are shown in brackets.
Picklist:
not used
, relay x (xx-xx)
Note:
If there are several reasons for triggering a relay (e.g. 2 different limit
values), this must be set to "Collective relay" under "Setup -> Outputs ->
Relay -> Relay x".
35010/000 to
35010/007
Copy settings
Copies settings from actual channel to selected channel.
30100/000 to
30100/007
"Inputs" menu
items
Configurable parameters
(factory settings are highlighted in bold)
Direct
access
code