C-2
Appendix C
MC-III™ Panel Mount Flow Analyzer
The Floating Point-32 bit (FP32) data type follows the IEEE-754 format and consists of 32 bits contained in a
single register.
The word ordering for multiple register data types, such as floating-point numbers or long integers, is for the
most significant word to appear first in the message.
The Unsigned Word (U16) type is used for 16-bit integers and fits into one register.
The Packed ASCII (PA) type contains two bytes that are two unsigned characters. Generally, multiple Packed
ASCII types are arranged consecutively for implementing strings. For example, the device’s well name is a
string of 10 unsigned characters that is implemented as 5 Packed ASCII registers. Here is an example of a
well name that contains the string, “Test Well 413.”
Register
Hexadecimal #
ASCII Characters
210
54 65
Te
211
73 74
St
212
20 57
<SPACE>W
213
65 6C
el
214
6C 20
l<SPACE>
215
34 31
41
216
33 FF
3<UNUSED>
Unused characters at the end of each string will report 0xFF hexadecimal.
Registers
Each register has an Access type: read-only or read-write, as described below.
Access Type
Description
Read Only (RO)
Register can only be read.
Read/Write (R/W)
Register can be read and written.
The registers are grouped into Modbus
®
map blocks based on function. The MC-III contains the following
map functions.
Function
Starting Register
System Configuration
1000
Real Time
1200
Input Configuration
2000
Output Configuration
4000
Holding Register (16-bit)
8000 and 17001
Holding Register (32-bit)
7000
Control Registers
70
Wellsite Parameters
200
Summary of Contents for NUFLO MC-III
Page 1: ...NUFLO TM MC III Panel Mount Flow Analyzer User Manual Manual No 2350326 01 Rev 02 ...
Page 36: ...36 Section 3 MC III Panel Mount Flow Analyzer ...
Page 66: ...66 Section 4 MC III Panel Mount Flow Analyzer Figure 4 30 4 20 mA output test screen ...
Page 86: ...86 Section 5 MC III Panel Mount Flow Analyzer ...
Page 100: ...B 2 Appendix B MC III Panel Mount Flow Analyzer ...
Page 118: ...C 18 Appendix C MC III Panel Mount Flow Analyzer ...
Page 119: ...C 19 MC III Panel Mount Flow Analyzer Appendix C ...