Scanner 1141 Hardware User Manual
88
enters the overcharge (“VoverCharge”) state.
Once VoverCharge is reached, the bulk charger will be left on based on a set period of time at or
above the overcharge voltage. To prevent battery damage, the overcharge state is terminated
immediately if the battery voltage reaches more than 0.5V above the overcharge voltage.
The float state is always entered once the overcharge state is terminated.
The pulse-mode method of charging is done by monitoring the battery voltage and turning the
switch on whenever charging is deemed necessary. A DC supply can be used, provided it is
current-limited to 10A.
•
Smart Charger Constant Current / Constant Voltage
When the smart charger is used with the bulk charger, the bulk charger will quickly recharge a
depleted battery to approximately 80% capacity. The smart charger then brings the battery to a
full charge and maintains the charge until bulk charging is once again required.
The smart charger provides up to 3 amps of charging current and delivers a constant current into
the battery until it reaches the programmed overvoltage setpoint. At this point, the charger will
transition to its constant voltage mode, while continuing to deliver charge into the battery until it
is fully charged. The battery is considered to be fully charged when the charging current has
fallen to a preset level (as programmed according to the size of the battery being charged). At this
charge termination point, the charger is switched to float mode, and the programmed float voltage
is maintained by delivering charge to the battery as necessary.
The "trickle state" exists when battery voltage is severely discharged to a point below a preset level
called (“vTrickle”). When the battery voltage is below “vTrickle,” the smart charger will charge the
battery voltage up to the “vTrickle” level at a lower trickle current.
The power supplies on the main board allow the user to input a single variable voltage. The power
supply provides the various regulated voltages required by the RTU. In applications where a lead
acid battery is integral, the power supply recharges that battery. This function can continue whether
the RTU is switched on or not. As applicable, all power supplies report the input voltage and the
battery voltage to the mainboard. This information is available for remote monitoring.
Sealed Lead Acid Battery
A sealed lead acid battery is paired with a temperature-compensated charge controller for charging the
battery. A high-side bi-directional current monitor may be used to measure the current flowing into the
battery (charging) or out of the battery (discharging). It is an optional item that provides a power system
troubleshooting aid.
1. Input Current Limit:
10A maximum
2. Maximum Input Voltage
28 VDC
3. Input Voltage:
Transient protection on input
Voltage
drop
of
3
VDC
nominal
Summary of Contents for NUFLO 1141C
Page 1: ...Manual No 30165009 Rev 01 NUFLOTM Scanner 1141 RTU Hardware User Manual ...
Page 28: ...Scanner 1141 Hardware User Manual 28 Figure 3 1 Scanner 1141 main circuit board ...
Page 66: ...Scanner 1141 Hardware User Manual 66 ...
Page 67: ...Chapter 6 Parts List and Order Code 67 Chapter 6 Parts List and Order Code Scanner 1141C ...
Page 68: ...Scanner 1141 Hardware User Manual 68 Scanner 1141L ...
Page 69: ...Chapter 6 Parts List and Order Code 69 Scanner 1141G ...
Page 91: ...Appendix A Specifications 91 Outline Dimensions Scanner 1141C ...
Page 92: ...Scanner 1141 Hardware User Manual 92 Scanner 1141L Front and Side Views ...
Page 94: ...Scanner 1141 Hardware User Manual 94 Scanner 1141G ...
Page 96: ...Scanner 1141 Hardware User Manual 96 Drawing 1 Installation ...
Page 97: ...Appendix B Control Drawings 97 Drawing 2 Power Supply ...
Page 98: ...Scanner 1141 Hardware User Manual 98 Drawing 3 Communications Serial Ports ...
Page 99: ...Appendix B Control Drawings 99 Drawing 4 Status Pulse Inputs Outputs ...
Page 100: ...Scanner 1141 Hardware User Manual 100 Drawing 5 RTD Inputs Analog Inputs Outputs ...
Page 101: ...Appendix B Control Drawings 101 Drawing 6 Analog Outputs ...
Page 102: ...Scanner 1141 Hardware User Manual 102 ...
Page 117: ...117 ...
Page 118: ...118 ...
Page 119: ......
Page 120: ......