Cable types and minimum thicknesses
Cable length (m)
up to 20
from 20 to 30
Power supply 230 V AC
3G x 1.5 mm²
3G x 2.5 mm²
24 V AC/DC fl ashing beacon
2 x 0.5 mm²
2 x 0.5 mm²
TX Photocells
2 x 0.5 mm²
2 x 0.5 mm²
RX photocells
4 x 0.5 mm²
4 x 0.5 mm²
12 V DC electric lock
2 x 1 mm²
2 x 1.5 mm²
Command and control devices
*no. x 0.5 mm²
*no. x 0.5 mm²
* no. = see product assembly instructions
Warning: the cable cross-section is indicative and varies according to the motor power and cable length.
When operating at 230 V and outdoors, use H05RN-F cables compliant with 60245 IEC 57 (IEC); when operating
indoors, use H05VV-F cables compliant with 60227 IEC 53 (IEC). For power supplies up to 48 V, you can use FROR 20-22 II
cables compliant with EN 50267-2-1 (CEI).
To connect the antenna, use RG58 cable (up to 5 m).
To connect to the CRP, use a UTP CAT5 cable (up to 1,000 m long).
If the cable lengths diff er from those specifi ed in the table, defi ne the cable cross-sections according to the actual
power draw of the connected devices and in line with regulation CEI EN 60204-1.
For multiple, sequential loads along the same line, recalculate the values in the table according to the actual power
draw and distances. For information on connecting products not covered in this manual, please see the documentation
accompanying the products themselves.
To connect the encoder, use a FROHE 300/500 V shielded cable (3 x 0.5 mm²).
BUS cable table
We recommend using a FROR 2 x 0.5 mm cable, maximum 50 m in length from the control board.
Single branch length (m)
max. 50 m
BUS cable
2 x 0.5 mm²
The total length of all branches can be a maximum of 150 m.
The cable cannot be shielded.