7. Operating

ATTENTION:

An automatic test for pump operation is
made after 48 hours inactivity.

7.1. Operating  with  2  float

switches

See the connection diagram of the float switches
at paragraph 5.2.1.
Float switch G1 starts up and stops the pump.
Float  switch  G2,  with  a  higher  intervention  level
than  float  switch  G1,  acts  as  a  high-level  alarm
and starts up pump if float switch 1 is faulty.

Activation of the 2 float switches function.

The control panel is set by the manufacturer for
the 2 float switches functioning. This setting, at the
moment of switching on, causes the switching on
of the FAILURE LED for approximately 1 second.
Proceed as follows, if the control panel is set to
operate  with  3  float  switches,  whilst  the  2  float
switches function is required:

- switch  off  the  electrical  current  by  rotating  the

main  selector  switch  with  the  door-locking
device,

- press the AUT-STOP pump button and keeping

the  button  pressed,  rotate  the  main  selector
switch with the door-locking device and switch
on the current,

- wait  until  the  FAILURE  LED  lights  for

approximately 1 second and release the button,

- the  control  panel  is  now  set  to  function  with  2

float switches.

7.2. Operating  with  3  float

switches

See the connection diagram of the float switches
at paragraph 5.2.2.
Float switch G1 starts up the pump.
Float  switch  G2,  with  a  lower  intervention  level
stops pump.
Float  switch  G3,  with  a  higher  intervention  level
than  float  switch  G1,  acts  as  a  high-level  alarm
and starts up pump if float switch G1 is faulty.

Activation of the 3 float switches function

The control panel is set by the manufacturer for
the 2 float switches functioning. This setting, at the
moment of switching on, causes the switching on
of the FAILURE LED for approximately 1 second.
Proceed as follows, if the control panel is set to
operate with 3 float switches:

- switch  off  the  electrical  current  by  rotating  the

main  selector  switch  with  the  door-locking
device.

- press the AUT-STOP pump button and keeping

the  button  pressed,  rotate  the  main  selector
switch with the door-locking device and switch
on the current.

- wait until the FAILURE LED flashes 3 times and

then release the button.

- the  control  panel  is  now  set  to  function  with  3

float switches.

When  the  control  panel  is  set  to  function  with  3
float  switches,  at  the  moment  of  starting-up,  the
FAILURE LED does not signal.

8. Motors with thermal protectors

The motors can have:

- thermal  protectors  with  cables  to  bring  the

signals  to  the  terminal  block  of  the  control
panel.

- a construction without thermal protectors.

The  control  panel  must  be  set  to  signal  the
intervention of the thermal protectors.

8.1. Motors 

with 

thermal

protectors with  external

signals 

At the moment of switching
on  the  control  panel,  the
MAXIMUM LEVEL led lights
up  for  1  second  with  this
setting.
The  intervention  of  the
thermal protectors causes:

- the stopping of the pump.
- the  quick  flashing  of  the

relative OVERLOAD led.

When the thermal protectors in the winding cools
down,  the  pump  is  ready  to  restart  its  normal
functioning.

4.

70

.1

05

7.

11 - 12

9 - 10 

7      8

12

Summary of Contents for QTLD 1D 12A-FA

Page 1: ...ith three phase motor Coffret lectrique de commande 1 pompe de drainage avec moteur triphas 1 QTLD 1D 12A FA ISTRUZIONI ORIGINALI PER L USO P 394 02 I Pagina 2 Italiano ORIGINAL OPERATING INSTRUCTIONS...

Page 2: ...eratura ambiente 5 40 C Grado di protezione IP 55 Dimensioni cassetta 255x200x205 mm Peso kg 2 5 3 Costruzione Esecuzione standard Quadro di comando e protezione per una pompa sommergibile per drenagg...

Page 3: ...tico 5 Led pompa in stop 6 Pulsante AUT STOP 7 Pulsante MAN Consente di fare la prova di avviamento manuale della pompa La pompa funziona solo con pulsante premuto 8 Led LIVELLO MASSIMO Segnala che il...

Page 4: ...sere collegato direttamente ai morsetti di uscita del contattore 5 1 1 Inversione del senso di rotazione Con alimentazione trifase verificare che il senso di rotazione corrisponda a quello indicato da...

Page 5: ...o aperto e in tensione ATTENZIONE Quadro aperto e in tensione Operare solo sul trimmer per la taratura della corrente Taratura della corrente di protezione della pompa Riferimenti potenziometro sulla...

Page 6: ...funzione di allarme per alto livello e di avviamento della pompa nel caso di rottura del galleggiante G1 Attivazione del funzionamento con 3 galleggianti Il quadro settato di fabbrica per il funziona...

Page 7: ...Se il motore privo di termoprotettori il quadro deve essere settato come funzionamento con termoprotettori con segnali esterni e si deve fare un ponte fra i morsetti 7 8 9 Quadri per allarme remoto A...

Page 8: ...er voltages on request Ambient temperature from 5 40 C Protection IP 55 Dimensions 255x200x205 mm Weight kg 2 5 3 Components Standard construction Control panel with protection for one submersible dra...

Page 9: ...anual starting up test of the pump The pump function only with the button pressed 8 MAXIMUM LEVEL LED signals that the level in the tank has reached maximum level 9 FAILURE LED signals faults of the f...

Page 10: ...nection The motor must be connected directly to the output terminals of the contactors 5 1 1 Inversion of the rotational direction Utilising the three phase electrical feed check that the rotational d...

Page 11: ...failure disconnected motor cable broken impeller etc To set the amperometric protection the control panel must be open and electrically fed ATTENTION Control panel open and electrically fed Operate on...

Page 12: ...itch G1 acts as a high level alarm and starts up pump if float switch G1 is faulty Activation of the 3 float switches function The control panel is set by the manufacturer for the 2 float switches fun...

Page 13: ...s without thermal protectors If the motor do not has thermal protectors the control panel must be set as per functioning with thermal protectors with external signal and a bridge must be made between...

Page 14: ...biante 5 40 C Protection IP 55 Dimensions du coffret 315x235x170 mm Poids kg 2 5 3 Construction Ex cution standard Coffret de contr le et de protection de une pompe submersible pour drainage avec mote...

Page 15: ...nuel la pompe fonctionne seulement si le bouton est enfonc Bouton RESET 1 Voyant pr sence tension 2 Voyant pompe en fonctionnement 3 Voyant protection thermique amp rom trique Avec clignotement normal...

Page 16: ...t aux bornes de sortie des contacteurs 5 1 1 Inversions du sens de rotation Avec une alimentation triphas e v rifier que le sens de rotation corresponde celui qui est indiqu par la fl che pr sente sur...

Page 17: ...ur la carte de base et voyant rouge sur la carte lectronique DR 1000 l arri re de la porte du coffret D marrer la pompe et v rifier le voyant rouge Si le voyant est teint tourner lentement le trimmer...

Page 18: ...e en cas de rupture du flotteur G1 Activation de l op ration avec 3 flotteurs Le coffret est r gl en d usine pour fonctioner avec 2 flotteurs Ce r glage au moment de l activation du coffret provoque l...

Page 19: ...8 2 Moteurs sans protecteurs thermiques Si le moteur est d pourvus de protecteurs thermiques le coffret doit tre r gl comme fonctionnant avec protections thermiques avec signaux externes et il faut r...

Page 20: ...3 1 1 DR 1000 4 5 5 1 5 1 1 5 2 5 2 1 2 5 2 2 3 5 3 5 4 6 7 7 1 2 7 2 3 8 8 1 8 2 9 10 11 12 1 QTLD 1D 12A FA 6 12 A 2 400V 3 10 50 60 Hz 5 40 C IP 55 255x200x205 2 5 3 12 DR 1000 DR 1000 RA 100E RA...

Page 21: ...2 3 RESET RESET 4 5 6 AUT STOP 7 MAN 8 9 FAILURE 10 RESET STOP AUT MAN RESET 1 9 8 2 3 4 5 6 7 10 POWER ON PRESENZA RETE FAILURE DR 1000 AVARIA SISTEMA MAX LEVEL LIVELLO MASSIMO RESET STOP MAN AUT P1...

Page 22: ...6 5 2 2 3 1 2 3 4 5 6 5 3 7 8 T1 T2 T3 4 70 1056 7 M 3 P1 contattore M 3 P2 T1 T2 T3 contattore 5 6 Stop G1 G2 3 4 Start Allarme Alarm 4 70 1086 1 1 G3 5 6 G1 3 4 Start Stop Allarme Alarm G2 1 2 4 70...

Page 23: ...entrale lectronique DR 1000 Voyant de protection amp rem trique Carte de base Potentiom tre de r glage du courant Voyant Potentiom tre 4 70 1086 6 23 10 DR 1000 6 DR 1000 5 4 RA 100E RA 100A 9 10 4 70...

Page 24: ...7 48 7 1 2 5 2 1 G1 G2 G1 2 2 FAILURE 1 3 2 AUT STOP FAILURE 1 2 7 2 3 5 2 2 G1 G2 G3 G1 G1 3 2 FAILURE 1 3 AUT STOP 3 FAILURE 3 3 FAILURE 8 3 1 1 8 1 MAXIMUM LEVEL 1 4 70 1057 1 11 12 9 10 7 8 24...

Page 25: ...LIVELLO MASSIMO MAN 1 FAILURE 8 2 7 8 9 220 230 75 3600 RA 100E 110x150x70 RA 100A 6 200x250x100 25...

Page 26: ...ESENZA RETE FAILURE DR 1000 AVARIA SISTEMA MAX LEVEL LIVELLO MASSIMO RESET STOP MAN AUT P1 CE ON OFF 4 70 1085 disp QUADRO ELETTRICO DI COMANDO POMPA DA DRENAGGIO ATTENZIONE IL QUADRO ESEGUE UNA PROVA...

Page 27: ...11 Interno quadro Inside of the box Int rieur coffret T FU1 FU3 FU2 FU4 DR 1000 TA KM 5 7 9 11 13 1 3 5 7 9 11 13 15 QS1 T3 T2 T1 N L 2 3 4 5 6 7 8 9 1 10 11 T1 T2 T3 KM 4 70 1090 disp1 4 70 1090 dis...

Page 28: ...ty for conformity with the standards laid down therein DECLARATION OF CONFORMITY I GB Montorso Vicentino 03 2011 Il Presidente Licia Mettifogo DECLARATION DE CONFORMITE Nous CALPEDA S p A d clare sous...

Reviews: