The front of DR 1000 electronic card features the
following signals and controls:
- Power on led.
- Failure led.
- Maximum level led.
- Pump running led.
- Overload led pump.
- Pump automatic operation led.
- Pump STOP led.

AUT-STOP 

pushbutton

to 

select

automatic selection (green led on) or pump
stop (red led on).

MAN  pushbutton

for  manual  test  (the

pump runs only with pushed button).

RESET pushbutton

.

1

Power on LED.

2

Pump operating LED.

3

Thermal/amperometric overload LED

- with  normal  flashing:  power  relay  faulty,

burnt-out  fuse,  disconnected  motor  cable
(motor without absorption).

To restore: press the RESET button.

- with  quick  flashing:  thermal  contact

breaker  intervention.  It  stops  flashing
when  the  thermal  contact  breaker  resets
the contact.

- constantly  switched  on:  intervention  by

the control panel amperometric protection.

To restore: press the RESET button.

4

Pump LED in automatic function mode.

5

Pump LED at stop.

6

AUT/STOP button.

7

MAN  button:  permits  the  manual  starting-up
test of the pump. The pump function only with
the button pressed.

8

MAXIMUM LEVEL LED: signals that the level
in the tank has reached maximum level.

9

FAILURE  LED:  signals  faults  of  the  float
switches because the signals do not arrive at
the control panel in a correct way.

10 RESET  button:  resets  the  functioning  of  the

pump  after  an  amperometric  protection
intervention.

MAN

STOP

AU

T

RESET




10 

POWER ON 

PRESENZA RETE 

FAILURE 

DR 1000

AVARIA SISTEMA 

MAX LEVEL 

LIVELLO MASSIMO 

RESET 

STOP 

MAN 

AUT 

P1 

9

3.1.1. Settings of the DR 1000 electronic card

(1

= Manufacturer’s settings

At the moment of starting-up, check the FAILURE LED and the MAXIMUM LEVEL LED.

FAILURE Led.

If the LED lights up for 1 second: the control panel is set to operate with 2

float switches. 

(1

If the LED remains off: the  control  panel  is  set  to  operate  with  3  float

switches.

MAXIMUM LEVEL Led.

If the LED lights up for 1 second: the control panel is set to operate with the

thermal protectors with external signals.

(1

If the LED remains off: the control panel is set to operate with thermal protector

without external signals (single-phase motor).

Summary of Contents for QTLD 1D 12A-FA

Page 1: ...ith three phase motor Coffret lectrique de commande 1 pompe de drainage avec moteur triphas 1 QTLD 1D 12A FA ISTRUZIONI ORIGINALI PER L USO P 394 02 I Pagina 2 Italiano ORIGINAL OPERATING INSTRUCTIONS...

Page 2: ...eratura ambiente 5 40 C Grado di protezione IP 55 Dimensioni cassetta 255x200x205 mm Peso kg 2 5 3 Costruzione Esecuzione standard Quadro di comando e protezione per una pompa sommergibile per drenagg...

Page 3: ...tico 5 Led pompa in stop 6 Pulsante AUT STOP 7 Pulsante MAN Consente di fare la prova di avviamento manuale della pompa La pompa funziona solo con pulsante premuto 8 Led LIVELLO MASSIMO Segnala che il...

Page 4: ...sere collegato direttamente ai morsetti di uscita del contattore 5 1 1 Inversione del senso di rotazione Con alimentazione trifase verificare che il senso di rotazione corrisponda a quello indicato da...

Page 5: ...o aperto e in tensione ATTENZIONE Quadro aperto e in tensione Operare solo sul trimmer per la taratura della corrente Taratura della corrente di protezione della pompa Riferimenti potenziometro sulla...

Page 6: ...funzione di allarme per alto livello e di avviamento della pompa nel caso di rottura del galleggiante G1 Attivazione del funzionamento con 3 galleggianti Il quadro settato di fabbrica per il funziona...

Page 7: ...Se il motore privo di termoprotettori il quadro deve essere settato come funzionamento con termoprotettori con segnali esterni e si deve fare un ponte fra i morsetti 7 8 9 Quadri per allarme remoto A...

Page 8: ...er voltages on request Ambient temperature from 5 40 C Protection IP 55 Dimensions 255x200x205 mm Weight kg 2 5 3 Components Standard construction Control panel with protection for one submersible dra...

Page 9: ...anual starting up test of the pump The pump function only with the button pressed 8 MAXIMUM LEVEL LED signals that the level in the tank has reached maximum level 9 FAILURE LED signals faults of the f...

Page 10: ...nection The motor must be connected directly to the output terminals of the contactors 5 1 1 Inversion of the rotational direction Utilising the three phase electrical feed check that the rotational d...

Page 11: ...failure disconnected motor cable broken impeller etc To set the amperometric protection the control panel must be open and electrically fed ATTENTION Control panel open and electrically fed Operate on...

Page 12: ...itch G1 acts as a high level alarm and starts up pump if float switch G1 is faulty Activation of the 3 float switches function The control panel is set by the manufacturer for the 2 float switches fun...

Page 13: ...s without thermal protectors If the motor do not has thermal protectors the control panel must be set as per functioning with thermal protectors with external signal and a bridge must be made between...

Page 14: ...biante 5 40 C Protection IP 55 Dimensions du coffret 315x235x170 mm Poids kg 2 5 3 Construction Ex cution standard Coffret de contr le et de protection de une pompe submersible pour drainage avec mote...

Page 15: ...nuel la pompe fonctionne seulement si le bouton est enfonc Bouton RESET 1 Voyant pr sence tension 2 Voyant pompe en fonctionnement 3 Voyant protection thermique amp rom trique Avec clignotement normal...

Page 16: ...t aux bornes de sortie des contacteurs 5 1 1 Inversions du sens de rotation Avec une alimentation triphas e v rifier que le sens de rotation corresponde celui qui est indiqu par la fl che pr sente sur...

Page 17: ...ur la carte de base et voyant rouge sur la carte lectronique DR 1000 l arri re de la porte du coffret D marrer la pompe et v rifier le voyant rouge Si le voyant est teint tourner lentement le trimmer...

Page 18: ...e en cas de rupture du flotteur G1 Activation de l op ration avec 3 flotteurs Le coffret est r gl en d usine pour fonctioner avec 2 flotteurs Ce r glage au moment de l activation du coffret provoque l...

Page 19: ...8 2 Moteurs sans protecteurs thermiques Si le moteur est d pourvus de protecteurs thermiques le coffret doit tre r gl comme fonctionnant avec protections thermiques avec signaux externes et il faut r...

Page 20: ...3 1 1 DR 1000 4 5 5 1 5 1 1 5 2 5 2 1 2 5 2 2 3 5 3 5 4 6 7 7 1 2 7 2 3 8 8 1 8 2 9 10 11 12 1 QTLD 1D 12A FA 6 12 A 2 400V 3 10 50 60 Hz 5 40 C IP 55 255x200x205 2 5 3 12 DR 1000 DR 1000 RA 100E RA...

Page 21: ...2 3 RESET RESET 4 5 6 AUT STOP 7 MAN 8 9 FAILURE 10 RESET STOP AUT MAN RESET 1 9 8 2 3 4 5 6 7 10 POWER ON PRESENZA RETE FAILURE DR 1000 AVARIA SISTEMA MAX LEVEL LIVELLO MASSIMO RESET STOP MAN AUT P1...

Page 22: ...6 5 2 2 3 1 2 3 4 5 6 5 3 7 8 T1 T2 T3 4 70 1056 7 M 3 P1 contattore M 3 P2 T1 T2 T3 contattore 5 6 Stop G1 G2 3 4 Start Allarme Alarm 4 70 1086 1 1 G3 5 6 G1 3 4 Start Stop Allarme Alarm G2 1 2 4 70...

Page 23: ...entrale lectronique DR 1000 Voyant de protection amp rem trique Carte de base Potentiom tre de r glage du courant Voyant Potentiom tre 4 70 1086 6 23 10 DR 1000 6 DR 1000 5 4 RA 100E RA 100A 9 10 4 70...

Page 24: ...7 48 7 1 2 5 2 1 G1 G2 G1 2 2 FAILURE 1 3 2 AUT STOP FAILURE 1 2 7 2 3 5 2 2 G1 G2 G3 G1 G1 3 2 FAILURE 1 3 AUT STOP 3 FAILURE 3 3 FAILURE 8 3 1 1 8 1 MAXIMUM LEVEL 1 4 70 1057 1 11 12 9 10 7 8 24...

Page 25: ...LIVELLO MASSIMO MAN 1 FAILURE 8 2 7 8 9 220 230 75 3600 RA 100E 110x150x70 RA 100A 6 200x250x100 25...

Page 26: ...ESENZA RETE FAILURE DR 1000 AVARIA SISTEMA MAX LEVEL LIVELLO MASSIMO RESET STOP MAN AUT P1 CE ON OFF 4 70 1085 disp QUADRO ELETTRICO DI COMANDO POMPA DA DRENAGGIO ATTENZIONE IL QUADRO ESEGUE UNA PROVA...

Page 27: ...11 Interno quadro Inside of the box Int rieur coffret T FU1 FU3 FU2 FU4 DR 1000 TA KM 5 7 9 11 13 1 3 5 7 9 11 13 15 QS1 T3 T2 T1 N L 2 3 4 5 6 7 8 9 1 10 11 T1 T2 T3 KM 4 70 1090 disp1 4 70 1090 dis...